GE Multilin MIGII Instruction Manual page 122

Digital protection for electrical machines
Table of Contents

Advertisement

6.2 OUTPUTS AND LEDS CONFIGURATION
Table 6–2: OUTPUTS AND LEDS ELEMENTS
MIXED 1
LEDS
MISCELLANEOUS 2
MIXED 2
Virtual trip signals are activated as soon as the protection unit trip conditions are present, independently from the trip
enable setting. This signal can be used to activate LEDs or auxiliary outputs. If the user wants the protection unit to trip,
then the trip enable setting must be activated. In this case, the relay will activate the trip contact.
6
6-8
52 Closed
Breaker closed
Motor started
Motor status (Started = 1, Stopped = 0)
EEPROM failure
Active when a failure is detected in EEPROM management
User settings
This element is green when the default settings are active and red when the user's
settings are active
READY
Active when the relay is in service and at least one element has its trip enabled
Close Breaker
Active when the close breaker operation is performed
Active Table
T1 or T2
Local/Remote
It's Local when the HMI is inside the MAIN SETTINGS, ADVANCED SETTINGS or
OPERATIONS menu
MIGII Digital Protection for Electrical Machines
6 I/0 CONFIGURATION
GEK-113188A