6.5.3. RMS Phase B Block

Start Address: 3060
Block Size: 20 Registers
Modbus Read Function Code: 03
Always transfer the Whole Block.
Addr
Parameters
ess
3060
VA
B
3062
W
B
3064
VAR
B
3066
PF
B
3068
V
BC
3070
V
B
3072
A
B
3074
F
B
3076
RESERVED3
3078
INTR
B
6.5.4.

6.5.5. RMS Phase C Block

Start Address: 3090
Block Size: 20 Registers
Modbus Read Function Code: 03
Always transfer the Whole Block.
Add
Parameters
ress
3090
VA
C
3092
W
C
3094
VAR
C
3096
PF
C
3098
V
CA
3100
V
C
3102
A
C
3104
F
C
3106
RESERVED4 Reserved for future use
3108
INTR
C
48
Description
RMS Phase B Apparent Power
RMS Phase B Active Energy
RMS Phase B Reactive Energy
RMS Phase B PF
RMS Phase B Line to Line Voltage
RMS Phase B Line to Neutral
Voltage
RMS Phase B Current
RMS Phase B Frequency
Reserved for future use
Number of Power Interruptions
Description
RMS Phase C Apparent Power
RMS Phase C Active Energy
RMS Phase C Reactive Energy
RMS Phase C PF
RMS Phase C Line to Line Voltage
RMS Phase C Line to Neutral
Voltage
RMS Phase C Current
RMS Phase C Frequency
Number of Power Outages
Sub Meters
Data Type
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Unsigned Long
32-bit Unsigned Long
Data Type
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Unsigned Long
32-bit Unsigned Long