4. MECHANICAL INSTALLATION

The EPM 2000 is panel-mounted and has reliable, rear-mounted terminal strips rated at 600v.
The 91 mm x 91 mm cut-out and 96 mm x 96 mm bezel dimensions adhere to DIN 43700.
Depth required behind the Bezel is 80 mm, plus space for wiring. Two side clamps are
provided for firm mounting.
CAUTION
All Installation, wiring and maintenance instructions to be carried out by
qualified personnel only.
Please read this and the following chapter completely, before
proceeding
These diagrams display the various dimensions of mechanical installations.
SIDE VIEW
30
: