Using The Quick Connect Feature - GE Multilin 469 Quick Reference Manual

Motor management relay
Table of Contents

Advertisement

7.2

Using the Quick Connect feature

16
9.
Enter the physical communications parameters (baud rate and parity) in their
respective fields. Note that when communicating to the 469 from the front port, the
default communications settings are: baud rate = 9600, slave address = 1, parity =
none, bits = 8, and stop bits = 1. These values cannot be changed.
10. Click the Read Order Code button to connect to the 469 device and upload the order
code. If a communications error occurs, ensure that the 469 serial communications
values entered in the previous step correspond to the relay setting values.
11. Click OK when the relay order code has been received. The new device will be added
to the Site List window (or Online window) located in the top left corner of the main
EnerVista 469 Setup window.
The 469 Site Device has now been configured for serial communications. Proceed to
"Connecting to the relay" on page 18 to begin communications.
The Quick Connect button can be used to establish a fast connection through the front
panel RS232 of a 469 relay. The following window will appear when the Quick Connect
button is pressed:
As indicated by the window, the Quick Connect feature will quickly connect the EnerVista
469 setup software to the 469 front port with the following value: 9600 baud, no parity, 8
bits, and 1 stop bit. Select the PC communications port connected to the relay and press
the Connect button.
The EnerVista 469 Setup software will display a window indicating the status of the
communications with the relay. When connected, a new site called "Quick Connect" will
appear in the Site List window. The properties of this new site cannot be changed.
QUICK REFERENCE GUIDE
469 MOTOR MANAGEMENT RELAY – QUICK REFERENCE GUIDE