! OUTPUT RELAY 1
5–88
This ordering of parameters of an equation, where the gate (or "operator") follows
the input (or "value") is commonly referred to as "Postfix" or "Reverse Polish"
notation.
OUTPUT 2 FLEXLOGIC
O1: Percent Diff OP
OUTPUT 2 FLEXLOGIC
O2: Inst Diff OP
OUTPUT 2 FLEXLOGIC
O3: Virtual Output 1
OUTPUT 2 FLEXLOGIC
O4: Logic Input 1
OUTPUT 2 FLEXLOGIC
O5: XOR (2 inputs)
OUTPUT 2 FLEXLOGIC
O6: Logic Input 2
OUTPUT 2 FLEXLOGIC
O7: NOT
OUTPUT 2 FLEXLOGIC
O8: Output Relay 2
OUTPUT 2 FLEXLOGIC
O9: AND (2 inputs)
OUTPUT 2 FLEXLOGIC
1O: OR (4 inputs)
OUTPUT 2 FLEXLOGIC
11: END
OUTPUT 2 FLEXLOGIC
20: END
FIGURE 5–47: FlexLogic™ Example Implemented
Any equation entered in the 745 that does not make logical sense according to the
notation described here, will be flagged as a self-test error. The
message will be displayed until the error is corrected.
FlexLogic Eqn
PATH: SETPOINTS
!"
S5 OUTPUTS
[!]
OUTPUT 1 NAME:
Solid State Trip
OUTPUT 1 OPERATION:
MESSAGE
Self-Resetting
OUTPUT 1 TYPE:
MESSAGE
Trip
OUTPUT 1 FLEXLOGIC
MESSAGE
01: Percent Diff Op
OUTPUT 1 FLEXLOGIC
MESSAGE
20: END
This section contains the settings (including the FlexLogic™ equation) to configure
output relays 1 to 8.
OUTPUT 1(8) NAME: Press ENTER edit the name of the output. The text may be
changed from
Solid State Trip
Press ENTER to store the edit and advance to the next character position.
OUTPUT 1(8) OPERATION: Select "Latched" to maintain the Output 1(8)
contacts in the energized state, even after the condition that caused the
contacts to operate is cleared, until a reset command is issued (or automatically
after one week). Select "Self-reset" to automatically de-energize the contacts
after the condition is cleared. The solid state output (Output 1) remains closed
until externally reset by a momentary interruption of current, unless wired in
parallel with an electromechanical relay (Outputs 2 to 8) in which case it turns
off when the relay operates.
OUTPUT 1(8) TYPE: Select "Trip" to turn the Trip LED on or "Alarm" to turn
the Alarm LED on when this output operates. Otherwise, select "Control". Note
http://www.GEindustrial.com/multilin
Output Relay 2
OPERATE
!
OUTPUT RELAYS
!
OUTPUT RELAY 1(8)
Range: Enabled, Disabled
Range: Self-Resetting, Latched
Range: Trip, Alarm, Control
Range: any FlexLogic™ input or gate
Range: any FlexLogic™ input or gate
one character at a time, using the VALUE keys.
S5 Outputs
SELF TEST ERROR:
GE Multilin