745
Transformer Management Relay
Output Relays
! OUTPUT RELAY 1
5–88
This ordering of parameters of an equation, where the gate (or "operator") follows
the input (or "value") is commonly referred to as "Postfix" or "Reverse Polish"
notation.
OUTPUT 2 FLEXLOGIC
O1: Percent Diff OP
OUTPUT 2 FLEXLOGIC
O2: Inst Diff OP
OUTPUT 2 FLEXLOGIC
O3: Virtual Output 1
OUTPUT 2 FLEXLOGIC
O4: Logic Input 1
OUTPUT 2 FLEXLOGIC
O5: XOR (2 inputs)
OUTPUT 2 FLEXLOGIC
O6: Logic Input 2
OUTPUT 2 FLEXLOGIC
O7: NOT
OUTPUT 2 FLEXLOGIC
O8: Output Relay 2
OUTPUT 2 FLEXLOGIC
O9: AND (2 inputs)
OUTPUT 2 FLEXLOGIC
1O: OR (4 inputs)
OUTPUT 2 FLEXLOGIC
11: END
OUTPUT 2 FLEXLOGIC
20: END
FIGURE 5–47: FlexLogic™ Example Implemented
Any equation entered in the 745 that does not make logical sense according to the
notation described here, will be flagged as a self-test error. The
message will be displayed until the error is corrected.
FlexLogic Eqn
PATH: SETPOINTS
!"
S5 OUTPUTS
[!]
OUTPUT 1 NAME:
Solid State Trip
OUTPUT 1 OPERATION:
MESSAGE
Self-Resetting
OUTPUT 1 TYPE:
MESSAGE
Trip
OUTPUT 1 FLEXLOGIC
MESSAGE
01: Percent Diff Op
OUTPUT 1 FLEXLOGIC
MESSAGE
20: END
This section contains the settings (including the FlexLogic™ equation) to configure
output relays 1 to 8.
•
OUTPUT 1(8) NAME: Press ENTER edit the name of the output. The text may be
changed from
Solid State Trip
Press ENTER to store the edit and advance to the next character position.
•
OUTPUT 1(8) OPERATION: Select "Latched" to maintain the Output 1(8)
contacts in the energized state, even after the condition that caused the
contacts to operate is cleared, until a reset command is issued (or automatically
after one week). Select "Self-reset" to automatically de-energize the contacts
after the condition is cleared. The solid state output (Output 1) remains closed
until externally reset by a momentary interruption of current, unless wired in
parallel with an electromechanical relay (Outputs 2 to 8) in which case it turns
off when the relay operates.
•
OUTPUT 1(8) TYPE: Select "Trip" to turn the Trip LED on or "Alarm" to turn
the Alarm LED on when this output operates. Otherwise, select "Control". Note
http://www.GEindustrial.com/multilin
Output Relay 2
OPERATE
!
OUTPUT RELAYS
!
OUTPUT RELAY 1(8)
Range: Enabled, Disabled
Range: Self-Resetting, Latched
Range: Trip, Alarm, Control
Range: any FlexLogic™ input or gate
↓
Range: any FlexLogic™ input or gate
one character at a time, using the VALUE keys.
S5 Outputs
SELF TEST ERROR:
GE Multilin