Auxiliary Voltage; Output Relays; Serial Communication Connections; Current Transducer - VAMP 140 Operation And Configuration Instructions

Overcurrent and earth-fault relay
Table of Contents

Advertisement

VAMP Ltd
4.2.
4.3.
4.4.
4.5.
VM140.EN011
Overcurrent and earth-fault relay
Technical description

Auxiliary voltage

The external auxiliary voltage Uaux (standard 40 to 265 V
ac/dc or 24 V dc, option B) for the relay is connected to the
terminals X1: 11 - 12
Note!
Polarity of the auxiliary voltage U
+ = X1:11 and - = X1:12.

Output relays

The VAMP 140 relay is equipped with five configurable output
relays and a separate output relay for the self-supervision
system
Trip relays T1 and T2 (terminals X2: 19 - 20 and 16 - 17)
Alarm relays A1 - A3 (terminals X2: 13 - 14, 11 - 12 and 9 -
10)
Self-supervision system output relay IF (terminals X2: 7 - 8)
The trip relay T2 can also be used for alarm purposes.

Serial communication connections

RS 232 serial communication connection for computers,
connector LOCAL (RS 232) on the front panel of the relay
Remote control connection, connector REMOTE (TTL) on
the rear panel of the relay (terminal X5). See also Table
2.5.2-1.

Current transducer

The output signal, i.e. 0 - 20 mA or 4 - 20 mA, of the
integrated mA transducer is available on terminal X2: 1 - 2.
Available couplings to the analog output
I
, I
, I
L1
L2
L3
I
0
f
I2/I1
I
Fault
Vamp 24h support phone +358 (0)40 573 6316
aux
, I
L
VAMP 140
(24 V dc, option B):
39