Relay Protection Functions; Overcurrent Protection I>, I>>, I>>> (50/51) - VAMP 140 Operation And Configuration Instructions

Overcurrent and earth-fault relay
Table of Contents

Advertisement

VAMP Ltd
2.2.
2.2.1.
VM140.EN011
Overcurrent and earth-fault relay
Technical description

Relay protection functions

Overcurrent protection I>, I>>, I>>> (50/51)
The three-phase overcurrent unit comprises three separately
adjustable overcurrent stages, i.e. stage I>, I>> and I>>>.
The overcurrent unit measures the fundamental frequency
component of the phase currents.
Stage I> can be configured for definite time or inverse time
operation characteristic. Stage I>> and stage I>>> have
definite time characteristic.
Figure 2.2.1-1 shows the functional block diagram of stage I>.
Im1
>
Im2
MAX
Im3
Block
Setting I>s
Figure 2.2.1-1 Block diagram of the three-phase overcurrent stage I>.
Parameters of the overcurrent stages:
I>, I>>, I>>> (50/51)
Parameter:
Measured
ILmax
value
Setting
I>, I>>,
values
I>>>
I>, I>>,
I>>>
Curve
t>, t>>,
t>>>
k
Vamp 24h support phone +358 (0)40 573 6316
&
t
t
s
r
t
Delay
Definite / inverse
Inverse time
time
characteristics
Value/unit:
A
A
pu
DT
NI, VI
EI, LTI
s
3vIslohko
&
³1
&
Multiplier
Enable events
Max. value of phase currents
IL1, IL2, IL3 primary values
Setting value in primary
current units
Setting value as per unit
value. Setting done in xIn
Operation charact./ definite
time (I>)
Operation charact./ inverse
time (I>)
Operation time
Time multiplier at inverse
time (I>)
VAMP 140
Start
Register
event
Trip
Register
event
7