VAMP  150 Operation And Configuration Instructions

VAMP 150 Operation And Configuration Instructions

Motor protection relay
Table of Contents

Advertisement

VAMP 150
Motor protection relay
Operation and configuration
instructions
Technical description

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VAMP 150 and is the answer not in the manual?

Questions and answers

Summary of Contents for VAMP VAMP 150

  • Page 1 VAMP 150 Motor protection relay Operation and configuration instructions Technical description...
  • Page 2 VAMP 150 Motor protection relay VAMP Ltd Operation and Configuration Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 3: Table Of Contents

    6.1. PC user interface...............25 6.1.1. Using the VAMPSET program........25 6.2. Remote control connections ..........25 7. Commissioning configuration ........26 7.1. Factory settings..............26 7.1.1. Configuration during commissioning....26 7.1.2. Configuration examples .........27 VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 4 VAMP 150 Motor protection relay VAMP Ltd Operation and Configuration Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 5: General

    Operation and Configuration General This part of the manual describes the general functions of the motor protection relay VAMP 150 and includes the relay operation instructions. It also includes instructions on parameterization and configuration of the relay and instructions on changing of settings.
  • Page 6: Operating Safety

    Any operational measure must be carried voltages! voltages! voltages! out according to national and local handling directives and instructions. Carefully read through the relay operation instructions before any relay operational measures are carried out. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 7: User Interface

    Operation and Configuration User interface 2.1. General The VAMP 150 relay can be controlled in three ways: Locally with the push-buttons on the relay front panel • Locally with a PC connected to the serial port on the relay •...
  • Page 8: Display

    VAMP Ltd Operation and Configuration 2.2.1. Display The VAMP 150 relay is provided with a clear 10 character alphanumerical LED display, which normally shows a scrolling text. Use the SERVICE/Setup/Bright menu to set the brightness of the display. The display is dimmed after a preset time.
  • Page 9: Indicators

    Error Error operates in parallel with the indicator Alarm Alarm Alarm Alarm starting of protection stage Trip Trip tripping of protection stage Trip Trip VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 10: Communication Via Local Panel

    5. Push LEFT for at least 2 s to exit from the setting state of a parameter without changing the setting value or, 6. Push ENTER to confirm and store the parameter setting. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 11: Function Menu Quick Reference

    Figure 3.1-1 The principle of the menu structure and navigation in the menus. 3.2. Function menu quick reference The structure of the menu is clear and straightforward. The main menu holds nineteen submenus, each with varying numbers of submenus and parameters. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 12 VAMP 150 Motor protection relay VAMP Ltd Operation and Configuration Figure 3.2-1 Main menu of the VAMP 150 relay. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 13: Basic Menu Structure Of Protection Functions

    The level is automatically closed 10 minutes after a key being pushed last or a setting being performed via the local port. Closing can also be performed by giving the password 9999. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 14: Opening Operating Levels

    The set password can only be changed locally using a PC connected to the local RS 232 port on the relay. The change is allowed/prohibited with the parameter ChgPwd = 0/1 in the SERVICE/Setup menu. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 15: Operating Measures

    Operation via the local MMI 4.1.1. Measured data The measured values can be read from the MEASURES menu and its submenus shown in the figure below. Figure 4.1.1-1 Measures menu of VAMP 150 relay. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 16: Operation Indicators

    4. Push the LEFT key to return to the Event info menu (by pressing twice you can return to the main menu) 5. Push the DOWN key to return to the Event list menu: Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 17: Forced Control (Force)

    Force: level 7. The Force: level has a selection list. Push the UP and DOWN keys to select the desired output relay, which is controlled on and off by forced control: VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 18: Setting Range Limits

    The scroll speed of the text in the display can be adjusted in the SERVICE/Setup/ScrolDelay: menu. 4.1.7. Setting date and time Date, time and style is set in the SERVICE/Setup/Date, Time and Style menus. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 19: Configuration And Setting Of Parameters

    Set the Date and time in the SERVICE position of the main • menu, see chapter 5.10. NOTE! Some of the parameters, for instance the password, can only be altered via the RS 232 serial communication port using a PC. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 20: Principle Of Parameter Setting

    5. Use the ENTER key to confirm the function or push the LEFT key for >2 s to cancel the function. 6. Push the LEFT key twice to return to the main menu. Figure 5.1-1 Changing parameters. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 21: Enabling And Disabling Protection Functions (Enable)

    Circuit Breaker Failure Protection stage (CBFP) • Ena N> Frequent start protection (N>) • RESET Reset the software of the VAMP 150 relay and reset latches • (Reset and Latch) NOTE! Disabling a protection function will remove the item from the menu.
  • Page 22: Scaling Of Measuring Transformers

    Polarity of the input signal (DI1pol), either normally open • (NO) or normally closed (NC) circuit. Remote release of latches using digital input (RemRel) • Selection to event register (OnEvent and OffEvent) • Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 23: Configuring Communication Protocols Com

    • Subnet mask (NetMsk) • IP address of the Name Server • IP address of the SNTP Server (NTPSvr) • Local Port Transfer rate of local serial bus (bit/s) • VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 24: Analog Output Ma Output

    Setup of screen scroll delay (ScrlDelay) • Changing of password (ChgPwd) • Changing of date, time and date style (Date, Time, Style) • DeviceInfo Serial number of the device (SerN) • Software version (Prgver) • Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 25: Pc Software

    REMOTE communication protocols (see details in Chapter 2.5.2. in technical description). Additional operation instructions for various bus types are to be found in their respective manual. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 26: Commissioning Configuration

    The scaling is done in the software block of the measured signals, Figure 7.1.1-1. Thus the scaling affects all the protection functions. Figure 7.1.1-1 Principle for scaling the measured values of the VAMP 150 relay. 3. Activation of the desired protection functions, ENABLE menu, see Chapter 5.2.
  • Page 27: Configuration Examples

    Transforming ratios of measurement transformers Motor niminal current Imot 400 A Current transformer (CT) CTprim 500 A (SCALING/IL Scale) CTsec CToprim 100 A Residual current transformer (CTo) CTosec (SCALING/Io Scale) Ioinp VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 28 DOUT menu, see Chapter 5.5. In the example, relay T1 is programmed to open the circuit breaker with a trip signal (for example I>>) selected in the DOUT menu. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 29 5. Technical data ..............39 5.1. Connections ..............39 5.1.1. Measuring circuitry ..........39 5.1.2. Auxiliary voltage ............39 5.1.3. Digital input...............39 5.1.4. Trip contacts (T1 and T2).........40 5.1.5. Alarm contacts (A1...A3) and IF......40 VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 30 5.3.2. Residual current protection ........44 5.3.3. Frequent start protection ........45 5.3.4. Arc protection (option) ..........45 5.4. Disturbance Recorder (DR) ..........45 6. Dimensional drawing ............46 7. Order information..............47 8. Reference Information............48 Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 31: Introduction

    Application The versatile basic protection functions, the wide variety of additional functions and several available communication protocols render the motor protection relay VAMP 150 an ideal protection relay for circuit breaker controlled three phase asynchronous motors. The modern technology in association with an extensive self- supervision system and a reliable construction ensures an extremely high availability for the VAMP 150 protection relay.
  • Page 32 40 - 265 V dc/ac, optionally 24 V dc. Built-in disturbance recorder for evaluating primary and • secondary, as well as neutral currents of the protected object. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 33: Functions

    VAMP 150 Technical Description Functions The individual protection functions of the VAMP 150 motor protection relay can independently of each other be enabled or disabled according to the requirements of the application. See the configuration instructions, Chapter 5 and 7, in the first part of this manual.
  • Page 34 Block 16 samples / cycle Digital inputs Settings k212_16 Figure 2.1-2. Block diagram of a signal processing and protection software. Figure 2.1-3. Block diagram of a basic protection function. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 35: Relay Protection Functions

    Setting value as per unit value I>>> Type Operation charact./ definite time (I>) NI, VI Operation charact./ inverse EI, LTI time (I>) t>, t>>, Operation time t>>> Time multiplier at inverse time (I>) VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 36 2. The fastest possible operating time is about 60 ms at inverse time characteristic according to curve types VI and Figure 2.2.1-2. Block diagram of the three-phase overcurrent stages I>> and I>>>. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 37 VAMP Ltd Motor protection relay VAMP 150 Technical Description Figure 2.2.1-3. Normal Inverse (IEC 60255-3) characteristic. ⋅ − > Figure 2.2.1-4. Very Inverse (IEC 60255-3) characteristic. ⋅ − > VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 38 VAMP 150 Motor protection relay VAMP Ltd Technical Description Figure 2.2.1-5. Extremely Inverse (IEC 60255-3) characteristic. ⋅ − > Figure 2.2.1-6. Long Time Inverse (IEC 60255-3) characteristic. ⋅ − > Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 39: Stall Protection I > (48)

    Figure 2.2.2-1. Operation time delay of the stall protection stage I >. If the measured current is less than the specified start current the operation time will be longer than the specified start START time T and vice versa. START VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 40 Recorded SCntr Start counter (Start) reading values TCntr Trip counter (Trip) reading xImot Max. value of fault. EDly Elapsed time as compared to the set operate time, 100% = tripping Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 41: Thermal Overload Stage T> (49M)

    Θ and parameters k Θ40 . See Figure 2.2.3-1. Θ70 1.20 1.10 1.00 0.90 0.80 0.70 0.60 (°C) Figure 2.2.3-1. Ambient temperature correction of the overload stage T>. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 42 Max. value of fault current as compared to I FltT Max. value of fault temperature EDly Elapsed time as compared to the set operate time, 100% = tripping Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 43 The value of ambient temperature factor k depends on the Θ setting Θ and I . See Figure 2.2.3-1. MAX40 MAX70 Figure 2.2.3-2. Behaviour of VAMP 150 T> protection stage VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 44: Unbalance Protection I2> (46)

    K =0.2 K =0.05 K =1 I /I 2 MOT Figure 2.2.4-1. Inverse operation delay of current unbalance stage I >. The longest delay is limited to 1000 seconds (=16min 40s). Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 45: Incorrect Phase Sequence Protection I2

    Recorded SCntr Start counter (Start) reading values TCntr Trip counter (Trip) reading Max. value of fault current EDly Elapsed time as compared to the set operate time, 100% = tripping VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 46: Undercurrent Protection I< (37)

    2.2.7. Sensitive earth-fault protection I >(50/51N) The earth-fault unit of the motor protection relay VAMP 150 is provided with two energizing inputs rated 5 A and 1 A. The earth-fault unit measures the fundamental frequency component Io. In the VAMP 150 relay this means that the...
  • Page 47 Start counter (Start) reading values TCntr Trip counter (Trip) reading Max. value of fault current in primary value EDly Elapsed time as compared to the set operate time, 100% = tripping VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 48: Frequent Start Protection N> (66)

    The stage will give a start signal when the second last start has been done. The trip signal is normally activated and released when there are no starts left. Figure 2.2.8-1 shows an application. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 49 Tot Mot Number of total motor starts Strs Mot Strs/h Number of motor starts in last hour El. Time Elapsed time from the last from mot motor start Strt VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 50: Arc Fault Protection (Option) Arci> (51L>), Arci > (51Nl>)

    (BO) in the output matrix, DO menu. The binary output can be used to forward light information to another relay, e.g. VAMP 150. The binary output can be connected to a maximum of three binary inputs of another relay.
  • Page 51 ArcCn arc activations TCntr Cumulative trip counter, only selected ArcCn arc activations Maximum value of fault current as per times Ion EDly Elapsed time as compared to the set operating time, 100%=tripping VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 52: Circuit-Breaker Failure Protection Cbfp (50Bf)

    Parameter: Parameter: Parameter: Value/unit: Value/unit: Value/unit: Value/unit: Setting CBRel Relay to be supervised values t> Operation time [s] Recorded SCntr Start counter (Start) reading values TCntr Trip counter (Trip) reading Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 53: Measurement Functions Of The Relay

    • 2.4. Output relay and blocking functions In the VAMP 150 relay all start and trip signals of the protection stages can be freely routed to the output relays and operation indicators according to the requirements of the application. The functions can also be blocked and for this purpose both internal relay signals and external control signals can be used.
  • Page 54: Output Relay Matrix

    In Figure 2.4-1, an active blocking is indicated with a black dot ( • ) in the crossing point of a blocking signal and a signal to be blocked. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 55: Communication

    VMA3CG VPA3CG VEA3CG or VX008-4 + VX007- + VX007- + VX015- ModBus SPA-Bus ProfiBus IEC-60870- 5-103 ModBus/ Transparent TCP/IP Table 2.5.2-1 Communication protocols and physical interfaces on REMOTE serial port. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 56: Disturbance Recorder

    Manual trig Size Size of one recording MAX time Maximum time of recordings MAX size Maximum size of recordings Recorder Links Connected links links AddLink Add links ClrLnks Clear links Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 57: Self-Supervision

    If the relay is fully operational with the auxiliary power supply, the IF contact is on the open position. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 58: Application Examples

    Starting of the motor is possible again because the temperature is now below the setting Θ . A start at this moment would ALARM rise the temperature near the trip level Θ = 100% but not TRIP over it. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 59 Figure 3.1-2. Example of modelled motor temperatures by the thermal overload stage when current has been cut off enough long so that the motor has cooled down. The temperature curve 5 describes an inhibited start attempt. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 60: Trip Circuit Supervision

    The user may also configure a dedicated digital input event text, e.g. "TRIP CIRCUIT FAILURE", to be displayed on the local display of the protective relay whenever there is a trip circuit failure. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 61 CB position is marked with an extra parallel line. The resistor device VR10CB offers an active input state for the digital input although the open coil auxiliary contact is open. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 62: Connections

    VAMP Ltd Technical Description Connections Figure 4-1. Connections on the rear panel of the VAMP 150 relay. The VAMP 150 relay is connected to the protected object through the following measuring and control connections: Phase currents IL1, IL2 and IL3 (terminals X1: 1-6) •...
  • Page 63: Auxiliary Voltage

    + = X1:11 and - = X1:12. 4.3. Output relays The VAMP 150 relay is equipped with five configurable output relays and a separate output relay for the self-supervision system Trip relays T1 and T2 (terminals X2: 19 - 20 and 16 - 17) •...
  • Page 64: Arc Protection

    X4: 3 GND (connect between relays) X4: 4 Arc sensor 1 + X4: 5 Arc sensor 1 - X4: 6 Arc sensor 2 + X4: 7 Arc sensor 2 - Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 65: Block Diagram

    VAMP Ltd Motor protection relay VAMP 150 Technical Description 4.7. Block diagram Figure 4.7-1. Block diagram of the motor protection relay VAMP 150. VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 66: Connection Diagram

    VAMP 150 Motor protection relay VAMP Ltd Technical Description 4.8. Connection diagram Figure 4.8-1. VAMP 150 connection diagram. Relay contact positions when no auxiliary power supply connected. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 67: Technical Data

    <= 6% near the limits of the voltage range Max. permitted interruption time < 50 ms (110 V dc) 5.1.3. Digital input Number of inputs External control voltage 18 - 265 V ac/dc Burden < 2 mA VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 68: Trip Contacts (T1 And T2)

    5.1.8. mA output Number of outputs Output signal 0/1 - 5 mA or 0/4 - 20 mA or any between 0...20mA Load resistance RL < 600 ΩW Accuracy Class 1 Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 69: Arc Option Card

    80 - 1000 MHz, 10 V/m, 80% AM (1 kHz) - GSM test EN 61000-4-3 900 MHz, 10 V/m, pulse modulated 1 MHz burst IEC 60255-22-1 1 kV, differential mode 2,5 kV, common mode Voltage interruption IEC 60255-11 VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 70: Test Voltages

    *) EI = Extremely Inverse, VI = Very Inverse, NI = Normal inverse, LTI = Long Time Inverse **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 71 <40 ms Resetting time <60 ms Resetting ratio 0.97 Accuracy: - starting ±3% of set value or ±5% or ±100 ms of rated value - operate time ±1% or ±100 ms VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 72: Residual Current Protection

    *) EI = Extremely Inverse, VI = Very Inverse, NI = Normal inverse, LTI = Long Time Inverse **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 73: Frequent Start Protection

    1 min Recording time (one record) 0.1 s – 12 000 min (must be shorter than MAX time) Pre trigger rate 0 – 100% Number of selected channels 0 – 12 VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 74: Dimensional Drawing

    VAMP 150 Motor protection relay VAMP Ltd Technical Description Dimensional drawing Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 75: Order Information

    TTL/RS232 Converter Cable ( for Modem MD42, ILPH, ..) Cable length 4m VA 1 DA-6 Arc Sensor Cable length 6m VYX078 Raising Frame for 100-serie Height 40mm VYX079 Raising Frame for 100-serie Height 60mm VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 76: Reference Information

    P.O. Box 810 FIN-65101 Vaasa, Finland Street address: Yrittäjänkatu 15 Tel. +358 (0)20 753 3200 Fax.+358 (0)20 753 3205 URL: http://www.vamp.fi 24h support phone: Tel . +358 (0)20 753 3264 Email: vampsupport@vamp.fi Vamp 24h support phone : +358 (0)20 753 3264 VM150.EN005...
  • Page 77 VAMP Ltd Motor protection relay VAMP 150 Technical Description VM150.EN005 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 78 We reserve the rights to changes without prior notice VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 P.O Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: vamp@vamp.fi VM150.EN005...

Table of Contents