Fluidwell F Series Operation Manual

Fluidwell F Series Operation Manual

Flowrate indicator
Hide thumbs Also See for F Series:

Advertisement

Quick Links

F010-U
FLOWRATE INDICATOR
Signal input flowmeter: 0-10V
Options: Intrinsically Safe.
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F Series

  • Page 1 F010-U FLOWRATE INDICATOR Signal input flowmeter: 0-10V Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    ▪ Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and consult “Fluidwell F0..-..-XI - Documentation for Intrinsic Safety”. DISPOSAL ▪ At the end of its life this product should be disposed of according to local regulations regarding waste electronic equipment.
  • Page 3: About The Operation Manual

    Manual FW-F010-U-M_v0403_04_EN.docx © 2019 Fluidwell bv - The Netherlands. Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
  • Page 4: Table Of Contents

    Page 4 CONTENTS MANUAL Safety instructions ..........................2 Disposal ............................2 Safety rules and precautionary measures .................... 2 About the operation manual ......................... 3 Contents manual ........................... 4 Introduction ........................5 Operational ........................6 Configuration ........................8 Installation ........................16 Intrinsically safe applications ..................
  • Page 5: Introduction

    Page 5 INTRODUCTION 1.1. SYSTEM DESCRIPTION OF THE F010-U Functions and features The flowrate indicator model F010-U is a microprocessor driven instrument designed to display the actual flowrate. This product has been designed with a focus on: ▪ ultra-low power consumption to allow long-life battery powered applications (type PB / PC), ▪...
  • Page 6: Operational

    Page 6 OPERATIONAL 2.1. GENERAL ▪ The F010-U may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ▪ Take careful notice of the “Safety rules, instructions and precautionary measures" in the front of this manual.
  • Page 7 Page 7 2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the F010-U will always act at Operator level. The information displayed is dependant upon the SETUP-settings. The signal generated by the connected flowmeter is measured by the F010-U in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 8: Configuration

    Page 8 CONFIGURATION 3.1. INTRODUCTION This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided. ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility.
  • Page 9 Page 9 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
  • Page 10 Page 10 To change or select a value: To change a value, use  to select the digits and  to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 11 Page 11 3.2.2. OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES FLOWRATE UNIT mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P TIME UNIT sec - min - hour - day DECIMALS...
  • Page 12 Page 12 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - FLOWRATE The display update time for flowrate is one second or more. MEASUREMENT UNIT SETUP - 11 determines the measurement unit for flowrate. The following units can be selected: mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P.
  • Page 13 Page 13 2 - DISPLAY BARGRAPH The bar graph (pie graph) displayed at operator level is percentage-wise related to the input signal: minimum signal is 0% (setup 44) and maximum signal is 100% (setup 45). With this function, the bar graph can be enabled / disabled. Following selections are available: OFF - ON The functions below will only effect the optional LED-backlight.
  • Page 14 Page 14 4 - FLOWMETER SIGNAL The F010-U can process the 0-10V signal in two ways: ▪ Interpolation: the signal is processed linear R = S x I ▪ Square root: for differential pressure √ R = S where: R = Rate: the calculated flowrate S = Span: the maximum flowrate at 10V.
  • Page 15 Page 15 4 - FLOWMETER (CONTINUED) TUNE MIN / 0V With this setting it is possible to calibrate the input value for 0V as the signal from the flowmeter might not be exact 0.0V at flowrate zero. This function will measure the real output value at flow zero. ▪...
  • Page 16: Installation

    Page 16 INSTALLATION 4.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 17 Page 17 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 18 Page 18 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 19 Page 19 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION ▪ ▪ Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object. ▪ ▪ This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
  • Page 20 Page 20 4.4.2. TERMINAL CONNECTORS WITH POWER SUPPLY - TYPE : PB / PD / PL / PX For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: SENSOR SIGNAL POWER SUPPLY SENSOR POWER SUPPLY BACKLIGHT ANALOG INPUT UNIT SUPPLY TYPE: U: 0-10V...
  • Page 21 Page 21 Terminal 4-5: POWER SUPPLY UNIT - TYPE PD / PX: To power the unit an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX) or 16-30V DC (type PD). Connect the "-"...
  • Page 22 Page 22 4.4.3. TERMINAL CONNECTORS WITH POWER SUPPLY - TYPE : PF / PM For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: POWER SUPPLY SENSOR SIGNAL TYPE: TYPE U: PF / PM 0-10V INPUT SIGNAL Fig.
  • Page 23 Page 23 REMARKS: TERMINAL CONNECTORS: Terminal GND- 01- 02; POWER SUPPLY only available with type PF / PM: erminal PTION SENSOR SUPPLY PF 24V AC  10% 8.2, 12, 24V max. 400mA@24V DC PF 24V DC  10% 8.2, 12, 24V max. 400mA@24V DC PM 115-230V AC ...
  • Page 24: Intrinsically Safe Applications

    ▪ For installation under FM: this intrinsically safe device must be installed in accordance with the Certificate / Project ID: 3033306. ▪ The control drawing number FWCD-0004 can be found in the document named: “Fluidwell F0..-U-XI - Documentation for Intrinsic Safety”.
  • Page 25 FWCD-0004. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
  • Page 26 Page 26 5.3. CONFIGURATION EXAMPLE INTRINSICALLY SAFE APPLICATIONS: Configuration example Configuration example IIA - IIB and IIC application - F010-U-PD-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight Backlight option: type ZB = max. 200 mA For example = max.
  • Page 27 Page 27 5.4. Battery replacement instructions SAFETY INSTRUCTIONS • Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. • Only use batteries which are certified for use in hazardous areas. The use of standard batteries in hazardous area's is not safe and prohibited.
  • Page 28: Maintenance

    Page 28 MAINTENANCE 6.1. GENERAL DIRECTIONS ▪ Mounting, electrical installation, start-up and maintenance of the instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ▪...
  • Page 29: Appendix A: Technical Specification

    Page 29 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits 5 ½ 26mm (1") and eleven 8mm (0.31"). Various symbols and measuring units. Piegraph 10 segment range indication in relation to its measuring range 0-100% Refresh rate User definable: 8 times/sec - 15 secs.
  • Page 30 Page 30 Sensor excitation Type PB / PC / PX Sensor supply voltage: 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Please note: this is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches.
  • Page 31 Page 31 OPERATIONAL Operator functions Displayed functions • flowrate. • measuring and time unit • piegraph 0-100% Flowrate Digits 5 ½ digits. Units mL, L, m3, Gallons, KG, Ton, lb, bl, cf, RND, ft3, scf, Nm3, Nl, igal - no units. Decimals 0 - 1 - 2 - 3 - 4 or 5.
  • Page 32: Appendix B: Problem Solving

    Page 32 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F010-U is going to be installed or while it is in operation. Flowrate displays "0 / zero" while there is flow: Check: ▪...
  • Page 33: Appendix C: Declaration Of Conformity

    Page 33 APPENDIX C: DECLARATION OF CONFORMITY FW-F010-U-M_v0403_04_EN.docx...
  • Page 34: Appendix D: Control Drawing

    Page 34 APPENDIX D: CONTROL DRAWING FW-F010-U-M_v0403_04_EN.docx...
  • Page 35: Index Of This Manual

    Page 35 INDEX OF THIS MANUAL actual settings low current backlight low-battery color main-function density maintenance bargraph manual version battery life time 13, 28 model battery replacement operational configuration operator level contents pass code 15, 32 dimensions Piegraph 7, 13 display update time power supply 21, 23...
  • Page 36 54 pass code 0000 55 tagnumber 0000000 FW-F010-U-M_v0403_04_EN.docx Fluidwell bv PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - © 2019 - FW-F010-U-M_v0403_04_EN.docx...

This manual is also suitable for:

F010-u

Table of Contents