User Manual
F010-P
FLOW RATE INDICATOR
Signal input:
pulse, NAMUR or coil flowmeter signal
Options:
intrinsically safe
backlight
F-Series - Field mounted indicators for safe and hazardous areas
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F Series

  • Page 1 User Manual F010-P FLOW RATE INDICATOR Signal input: pulse, NAMUR or coil flowmeter signal Options: intrinsically safe backlight F-Series - Field mounted indicators for safe and hazardous areas More info: www.fluidwell.com/fseries...
  • Page 2: Table Of Contents

    User Manual F010-P TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
  • Page 3 F010-P User Manual INTRINSICALLY SAFE APPLICATIONS ................34 Identification........................34 Electrical installation in hazardous areas................ 35 7.2.1 Installations based on FM or CSA Certificate ..............35 7.2.2 Electrical data - Control drawing..................36 7.2.3 Installations based on ATEX or IECEx Certificate ............37 7.2.4 Electrical data - Annex 1....................
  • Page 4: About This Manual

    ● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.03.xx...
  • Page 5: Safety

    F010-P User Manual SAFETY PERSONAL SAFETY ● Explosion hazard: Never open the unit when explosive atmosphere is present, and the unit is connected to a power supply or consuming device like the internal battery supply. ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ●...
  • Page 6: Introduction

    User Manual F010-P INTRODUCTION SYSTEM DESCRIPTION The flow rate indicator model F010-P is a microprocessor-driven instrument designed to show the current flow rate. Fig. 1: The F010 This manual describes the daily use, configuration and installation of the F010-P with pulse input from a flowmeter and its available options.
  • Page 7: Installation Example

    F010-P User Manual Options ● Intrinsic safety (Type XI) ● Power and sensor supply (Types PB, PC, PD, PF, PM, PX, in various combinations) ● Panel mount enclosure (Types HB, HC) ● Flame-proof enclosure (Type XF) ● Display backlight (Type ZB). INSTALLATION EXAMPLE Following parts can be recognized in below installation example.
  • Page 8: Operation

    User Manual F010-P OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the F010-P. For this, the F-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
  • Page 9: Backlight (Type Zb)

    F010-P User Manual Normally, the display is updated depending on the refresh rate selected in the configuration settings. By pressing any key, the display switches to refreshing the information 8 times per second. After 30 seconds of key inactivity, the display returns to the configured refresh rate. Fig. 4: Example of display information during process 4.2.2...
  • Page 10: Configuration

    User Manual F010-P CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the F-Series for optimal functionality. Configuration of the F010-P can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
  • Page 11: Changing Configuration Settings

    F010-P User Manual 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
  • Page 12: Setup Menu Overview

    User Manual F010-P SETUP MENU OVERVIEW FLOW RATE DEFAULT UNIT mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P sec - min - hour - day TIME UNIT DECIMALS...
  • Page 13: Menu 2: Display

    F010-P User Manual FLOW RATE UNIT Determines the measurement unit for the flow rate. The type of unit that can be selected depends on the flowmeter unit (volumetric or mass) selected in . The following can be selected: 4.1: FLOWMETER > SIGNAL mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P Changing the measurement unit will have consequences for operator...
  • Page 14: Menu 3: Power Management

    User Manual F010-P 5.4.3 MENU 3: POWER MANAGEMENT POWER MANAGEMENT LCD UPDATE Sets the LCD display refresh rate. The following can be selected: fast - 1 sec - 3 sec - 15 sec - off When a key is pressed, the display refresh rate will switch to ‘fast’ for 30 seconds.
  • Page 15: Menu 5: Others

    F010-P User Manual 5.4.5 MENU 5: OTHERS OTHERS TYPE / MODEL Provides important information on your product. This information may be SOFTWARE VERSION required for maintenance or support. SERIAL NUMBER PASS CODE All SETUP values can be password protected. A four-digit password can be programmed, for example 1234. To disable password protection, enter four zeros (0000).
  • Page 16: Installation

    User Manual F010-P INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 17: Handling The F010-P Enclosure

    F010-P User Manual HANDLING THE F010-P ENCLOSURE 6.2.1 IDENTIFICATION The F-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. Refer to for identification and installation labels Section 7: Intrinsically safe applications [»34] for Intrinsically Safe applications.
  • Page 18: Opening, Assembling And Closing The F-Series

    User Manual F010-P Fig. 9: Example of F0-Series installation label (Safe Area - Type PM or PF) Serial number and year of production The serial number can be reviewed on the identification label, the installation label, or in . The production SETUP 5.3: OTHERS >...
  • Page 19 F010-P User Manual Closing / replacing the cover 1. Re-insert all terminals to their original position. 2. Carefully position the front cover onto the back cover, making sure that the gasket falls nicely into the gutter of the back cover. 3.
  • Page 20: Mechanical Installation

    User Manual F010-P MECHANICAL INSTALLATION 6.3.1 MECHANICAL DIMENSIONS Aluminum and stainless steel enclosures Note: _B_ type enclosure (extended back) not available under CSA or FM certification for intrinsically safe installation 75 mm (2.95") 90 mm (3.54") 130 mm (5.12") 112 mm (4.40") 12mm 12mm 30 mm 30 mm 30mm 30mm...
  • Page 21 F010-P User Manual Non-metallic enclosures 75 mm (2.95") 130 mm (5.12") 112 mm (4.40") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 22: Mounting The F-Series

    User Manual F010-P 6.3.2 MOUNTING THE F-SERIES The enclosure can be installed by itself or with the aid of a mounting plate in the configurations shown below. When the product is installed on a wall or onto a meter, please use components and installation techniques that are suitable for the used materials.
  • Page 23: Electrical Installation

    F010-P User Manual ELECTRICAL INSTALLATION Hazardous area installations The following chapter gives general information regarding the electrical installation of the F010-P. gives additional specific information Section 7: Intrinsically safe applications [»34] regarding intrinsically safe installation and has priority over the information given in this chapter.
  • Page 24: Field Wiring Connections

    User Manual F010-P Connecting Protective Earth to a non-metallic enclosure When the F010-P is supplied with a non-metal enclosure (e.g. plastic), the field mount enclosure meets the requirements of class 2 (double insulated). Therefore any incoming PE conductor can be terminated with an insulating end cap.
  • Page 25: Power Supply

    F010-P User Manual All field wiring enters the F010-P through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F010-P with the correct drilling pattern and thread (metal) or hole (plastic) sizes. The wire screens (shield) are meant to prevent electromagnetic interference and shall be terminated at one side to prevent ground loops.
  • Page 26: Terminal Connectors Safe Area Applications - Type Px, Pd

    User Manual F010-P Fig. 14: Jumper positions sensor supply voltage selection (Type PF or PM) Jumper setting External sensor supply voltage 1.2 / 3.2V DC 8.2V DC 12V DC 24V DC TERMINAL CONNECTORS SAFE AREA APPLICATIONS - TYPE PX, PD Hazardous area installations The following chapter gives general information regarding the electrical installation of the F010-P.
  • Page 27 F010-P User Manual ● COIL LO: sensitivity from about 90mV p-p ● COIL HI: sensitivity from about 20mV p-p With Type ZF or ZG still higher sensitivities are available: ● Type ZF: COIL HI sensitivity from about 10mV p-p ● Type ZG: COIL HI sensitivity from about 5mV p-p. Vref 1.2 V DC 3 Coil 2 Coil...
  • Page 28 User Manual F010-P With Type PD a sensor supply voltage of 8.1V DC can be taken from terminal 6. 6 Type PD: 8.1 V DC 3 +3.2 V DC Selectable low-pass filter 2 Signal Resistance value: 1 Shield see signal selection table Common ground unit Fig. 18: Terminals 1 - 3 (6): PNP signal input...
  • Page 29: Terminals 4-5: Power Supply - Type Px And Pd

    F010-P User Manual NAMUR signal The F010-P is suitable for use with flowmeters with NAMUR signal. The F010-P with Type PD can offer a sensor supply voltage of 8.2V at terminal 6. 6 Type PD sensor supply +8.1 V DC NAMUR 2 Signal Shield...
  • Page 30: Terminal Connectors Safe Area Applications - Type Pf, Pm

    User Manual F010-P TERMINAL CONNECTORS SAFE AREA APPLICATIONS - TYPE PF, PM Hazardous area installations This chapter applies to electrical installation of the F010-P with Type PM or PF. These Types are not fit for use in Hazardous Areas! gives specific information regarding intrinsically Section 7: Intrinsically safe applications [»34] safe installation.
  • Page 31: Terminals 5-7: Flowmeter Input

    F010-P User Manual 6.6.2 TERMINALS 5-7: FLOWMETER INPUT Three basic types of flowmeter signals can be connected to the F010-P: pulse, active pulse or coil. The screen of the signal wire can be connected to the common ground terminal (see Section 6.4.3: Field wiring connections [»24] The input signal type has to be selected with the correct SETUP-function (...
  • Page 32 User Manual F010-P A sensor supply voltage can be taken from terminal 7. 7 Sensor supply Selectable low-pass filter 6 Signal Shield Resistance value: 5 GND see signal selection table Common ground unit Fig. 27: Terminals 5 -7: PNP signal input Active signal The F010-P is suitable for flowmeters with an Active signal output.
  • Page 33 F010-P User Manual NAMUR signal The F010-P is suitable for use with flowmeters with NAMUR signal. Terminal 7 provides a selectable sensor supply ( Section 6.4.5: Sensor supply [»25] 7 Sensor supply NAMUR 6 Signal Shield 820 Ω 5 GND Common ground unit Fig. 30: Terminals 5 -7: Namur signal FW_F010-P_M_v0501-03_EN...
  • Page 34: Intrinsically Safe Applications

    User Manual F010-P INTRINSICALLY SAFE APPLICATIONS IDENTIFICATION The F010-P can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. If Type XI is not indicated your unit is not suitable for Intrinsically Safe applications! Identification label To identify your F0-Series device, all field mount enclosures have a waterproof identification label placed on the outside of the product.
  • Page 35: Electrical Installation In Hazardous Areas

    F010-P User Manual ELECTRICAL INSTALLATION IN HAZARDOUS AREAS ● shows general information regarding the electrical Section 6.4: Electrical installation [»23] installation of your F010-P. The following sections give additional specific information regarding Intrinsically Safe installation, and overrules information given in other sections. ●...
  • Page 36: Electrical Data - Control Drawing

    User Manual F010-P 7.2.2 ELECTRICAL DATA - CONTROL DRAWING trol Dr ing F -P-XI Ce t r ific t a ion F0-SERIES – Type -XI T RMINAL CONNE CTORS F0 ERIE c mm on ground Ce tif r ica e number: CSA.08.2059461 Intr ins call S y afe for Class I/II/III, Division 1...
  • Page 37: Installations Based On Atex Or Iecex Certificate

    F010-P User Manual 7.2.3 INSTALLATIONS BASED ON ATEX OR IECEX CERTIFICATE Installation instructions ● For installation under ATEX directive: this Intrinsically Safe device must be installed in accordance with ATEX directive 2014/34/EU and product certificate KEMA 05ATEX1168 X. ● For installation under IECEx scheme: this Intrinsically Safe device must be installed in accordance with product certificate IECEx KEM 08.0006X.
  • Page 38: Electrical Data - Annex 1

    User Manual F010-P 7.2.4 ELECTRICAL DATA - ANNEX 1 Annex 1 ( mo el p s eci fic) to prod uct certif c i ates KEMA 0 ATEX1168 X, IECEx 00 6 Model F0..-P-XI Int nal supply for use w ith he cert ified replaceable battery type FW -Li A...
  • Page 39: Power Supply

    F010-P User Manual 7.2.5 POWER SUPPLY The F010-P can be powered from an external power supply. For Types PX or PD, an optional internal power supply is also available in the form of an intrinsically safe lithium primary battery (Type PC). When both external and internal power supplies are available, the internal power supply is interrupted and will serve as a backup supply.
  • Page 40: Configuration Examples Intrinsically Safe Applications

    User Manual F010-P Optional battery – Type PC With Type PC your product is equipped with an intrinsically safe, certified long-life Lithium primary battery. The battery will power the F010 when external power is not available, and may be exchanged in hazardous areas. For further information please see Section 8.3: Battery replacement [»44] All electrical connections made to the terminals of the intrinsically safe product (Type XI) must follow...
  • Page 41: F010-P-Px-Xi-(Zb) - Ex Ia Iic/Iiic

    F010-P User Manual 7.4.2 F010-P-PX-XI-(ZB) - EX IA IIC/IIIC Fig. 35: F010-P-PX-XI-(ZB) - Ex ia IIC/IIIC - Intrinsically Safe application Sensor supply voltage on Terminal 3: 1.2-3.2V DC. Please note: Type PX may be used in combination with the battery (Type PC). PX will power the F010-P, the battery will be disabled automatically until the power is disconnected 7.4.3 F010-P-PX-XI-ZB - EX IA IIC/IIIC...
  • Page 42: F010-P-Pd-Xi-Zb - Ex Ia Iic/Iiic

    User Manual F010-P 7.4.4 F010-P-PD-XI-ZB - EX IA IIC/IIIC Fig. 37: F010-P-PD-XI-ZB - Ex ia IIC/IIIC - Intrinsically Safe application Sensor supply voltage on Terminal 3: 1.2-3.2 V DC, Terminal 6: 8.2 V DC. Please note: Type PD may be used in combination with the battery (Type PC). PD will power the F010-P, the battery will be disabled automatically until the power is disconnected Page 42 FW_F010-P_M_v0501-03_EN...
  • Page 43: Maintenance

    F010-P User Manual MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 44: Battery Replacement

    Voltaweg 23, Veghel, the Netherlands - Part. no. / Référence: FW-LiBAT-021 Primary Lithium Battery - Only replace with Fluidwell I.S. battery pack! Pile primaire au lithium - Remplacer uniquement par une pile Fluidwell à Sécurité Intrinsèque! Fig. 39: Marking battery type PC: Intrinsically Safe FWLiBAT-021 (SPC02)
  • Page 45: Battery Replacement Procedure

    F010-P User Manual 8.3.2 BATTERY REPLACEMENT PROCEDURE Before starting the battery replacement procedure, make sure that the marking on the new battery corresponds with the type of installation, as shown in Section 8.3.1: Safety instructions [»44] When used in Intrinsically Safe applications - Type PC: The hook-and-loop fastener that holds the battery is antistatic and thus fit for Hazardous Area use.
  • Page 46: Appendix A - Technical Specification

    User Manual F010-P APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 5½ with height 26mm (1”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate User definable: fast - 1 sec - 3 sec - 15 sec - off Piegraph...
  • Page 47 F010-P User Manual OPERATING TEMPERATURE Safe area -40 °C to +80 °C, -40 °F to +176 °F Intrinsically safe -40 °C to +70 °C, -40 °F to +158 °F For EPL Da -40 °C to +50 °C, -40 °F to +122 °F POWER REQUIREMENTS Type PB SAFE AREA ONLY - Standard lithium primary battery.
  • Page 48: Input

    User Manual F010-P HAZARDOUS AREA (TYPE XI OR XF) Intrinsically safe ATEX appr. KEMA 05ATEX1168 X IECEx appr. IECEx KEM 08.0006X Type XI II 1 G Ex ia IIC T4 Ga Ex ia IIC T4 Ga II 1 D Ex ia IIIC T 100ºC Da Ex ia IIIC T 100ºC Da...
  • Page 49: Appendix B - Troubleshooting

    F010-P User Manual APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the F010-P. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
  • Page 50: Appendix C - Legal Information

    DECLARATIONS OF CONFORMITY EU De cla tio n of Conformi Fluidwell F0‒Series indicators he , February 2022 We, Fluidwell BV, declare under our s e ol respons ibility that the F0 ‒Series indicators are de igne d and will operate conform the following applicable European...
  • Page 51 F010-P User Manual LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: FLOW RATE UNIT TIME UNIT DECIMALS K-FACTOR DECIMALS K-FACTOR CALCULATION CUT-OFF GRAPH MAX 1000 DISPLAY BARGRAPH BACKLIGHT BACKLIGHT BRIGHTNESS POWER MANAGEMENT LCD UPDATE 1 sec BATTERY MODE operational FLOWMETER SIGNAL coil_lo OTHERS...