Power & Power Factor Measuring Accuracy - Siemens SIMPRO-100 Instruction Manual

Motor protection relay
Table of Contents

Advertisement

7
Commissioning
Expected
Resistance
Temperature
Value (ohms)
Reading (°C)
71.81
-50
100.00
0
131.45
50
167.20
100
207.45
150
252.88
200
294.28
240
Table 7.10 100-Ohm Nickel RTD Type (RTDs 1 – 12)
Expected
Resistance
Temperature
Value (ohms)
Reading (°C)
7.10
-50
9.04
0
10.97
50
12.90
100
14.83
150
16.78
200
18.34
240
Table 7.11 10-Ohm Copper RTD Type (RTDs 1 – 12)
7.3.8
Power & Power Factor
Measuring Accuracy
7.3.8.1
Accuracy Test, Wye Voltages
1. Connect the current sources to the IA, IB, and
IC current inputs (5 A or 1 A, as indicated by
the ITAP setting). Connect the voltage
sources to the VA, VB, and VC inputs in wye
configuration (refer to Figure 7.3, page 103).
2. Using the front-panel Set Relay\Relay
Elements\General Data function or serial port
SHOW command, note the CTR, PTR, and
PHROT settings.
108
Expected
Temperature
1
2
Reading (°F)
-58
32
122
212
302
392
464
Expected
Temperature
1
2
Reading (°F)
-58
32
122
212
302
392
464
RTD Temperatures
3
4
5
6
7
RTD Temperatures
3
4
5
6
7
3. Referring to step Table 7.12, set the current
and voltage source magnitudes. The phase
angles you should apply depend on the
PHROT setting. Use the front-panel Meter
Values\Instantaneous Meter function to verify
the relay measurements.
SIMPRO-100
8
9
10
11
12
8
9
10
11
12
PRIM-2400C