Siemens SIMPRO-100 Instruction Manual page 123

Motor protection relay
Table of Contents

Advertisement

SIMPRO-100
9.5.3.2
Output, Input, & Element
Columns
Table 9.5 summarizes the event report output,
input, and relay element control columns. Not all
relays include all the element types.
Column
Symbol
Heading
All columns
Element/input/output not picked up
or not asserted.
S
Motor
Motor starting.
R
Motor running.
Motor stopped.
J
Load
Load Jam Trip picked up.
l
Load Loss Alarm picked up.
L
Load Loss Trip picked up.
A
46
Current Unbalance Alarm picked up.
T
Current Unbalance Trip picked up.
T
47
Phase Reversal Trip.
A
49
Thermal Element Alarm picked up.
T
Thermal Element Trip picked up.
Q
50 O/C
Negative-Sequence Definite-Time
Overcurrent Element picked up and
time delay expired.
1
Level 1 Phase Definite-Time
Overcurrent Element picked up and
time delay expired.
2
Level 2 Phase Definite-Time
Overcurrent Element picked up and
time delay expired.
b
Both Level 1 and Level 2 Phase
Overcurrent Elements picked up and
time delays expired.
1
50G O/C
Level 1 Residual Overcurrent
Element picked up and time delay
expired.
2
Level 2 Residual Overcurrent
Element picked up and time delay
expired.
b
Both Level 1 and Level 2 Residual
Overcurrent Elements picked up and
time delays expired.
PRIM-2400C
Definition
Column
Symbol
Heading
w
Wdg
A Winding RTD has exceeded the
alarm temperature.
W
One or two Winding RTDs have
exceeded the trip temperature.
b
Brg
A Bearing RTD has exceeded the
alarm temperature.
B
One or two Bearing RTDs have
exceeded the trip temperature.
o
Oth RTD
An Other RTD has exceeded the
alarm temperature.
O
One or two Other RTDs have
exceeded the trip temperature.
a
Amb RTD
The Ambient RTD has exceeded the
alarm temperature.
A
The Ambient RTD has exceeded the
trip temperature.
T
Out T1
TRIP contact output asserted.
1
Contact output OUT1 asserted.
b
Both TRIP and OUT1 asserted.
2
Out 23
Contact output OUT2 asserted.
3
Contact output OUT3 asserted.
b
Both OUT2 and OUT3 asserted.
A
Out A
Contact output ALARM asserted.
1
In 12
Contact input IN1 asserted.
2
Contact input IN2 asserted.
b
Both IN1 and IN2 asserted.
3
In 34
Contact input IN3 asserted.
4
Contact input IN4 asserted.
b
Both IN3 and IN4 asserted.
5
In 56
Contact input IN5 asserted.
6
Contact input IN6 asserted.
b
Both IN5 and IN6 asserted.
7
In 7
Contact input IN7 (from
SIMPRO-100-RTD) asserted.
Table 9.5
Output, Input, and Element Event Report
Columns
9
Event Analysis
Definition
121

Advertisement

Table of Contents
loading

Table of Contents