Enabling BBMD and Editing the Broadcast Distribution Table
Parameter
BACnet/IP BBMD Settings
Enable BBMD
Select this checkbox to enable the Router to act as a BBMD.
If the BBMD is being accessed across a NAT Router, then these values must be
configured with the public IP address and Port by which the BBMD can be reached from
across the NAT Router. The Public IP Address and Port would also be used in the
Public IP Address
Broadcast Distribution Table (BDT) of remote BBMD's that need to reach this BBMD
across the NAT Router (see
be left blank.
This MUST be different to the IP Port used on the BACnet/IP Primary connection.
Public IP Port
Default is 47809 (0xBAC1).
Figure
Figure 19: Connection Parameters – BBMD

Figure 20: Edit Broadcast Distribution Table Window

EZ Gateway Start-up Guide
Configuring the Gateway
Definition
20). If no NAT Router is being used, these fields can
21