Engineering Guidelines

GENERAL

This section provides engineering guidelines for network designers who are incorporating an
MX410 or MX412 system into their network.

POWER REQUIREMENTS

Table 2-1
provides the current draw at –48 VDC (operating range of –42 VDC to –60 VDC) and
±24 VDC (operating range of ±22 VDC to ±27 VDC) with redundant PSUs installed.
Table 2-1. Current Draw at –48 VDC and ±24 VDC
Part Number
1189500L1
1189512L1
Table 2-2
provides data for determining the recommended fuse for the fuse and alarm panel
that services the MX410/MX412.
System Voltage
–48 VDC
±24 VDC
61189500L1-1B
Section 2
Equipment
MX410
MX412

Table 2-2. Fuse Recommendations

Maximum Current Draw
at –48 VDC
0.23 amps
0.36 amps
Recommended Fuse
2 amps, slow-blow
2 amps, slow-blow
Maximum Current Draw
at ±24 VDC
0.41 amps
0.76 amps