6.5 (Optional) Setting Sensor Parameters

Set sensor parameters based on site requirements.
Table 6-3 Setting sensor parameters
Main Menu
Second-Level
Menu
Parameters
Power System
Settings
Issue 05 (2020-04-07)
Third-Level
Menu
Other
Parameters
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Rated Capacity to 150 Ah.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set Rated
Capacity to 300 Ah.
Third-Level
Menu
Sensor Config.
Para
Copyright © Huawei Technologies Co., Ltd.
Fourth-Level
Default
Menu
Value
Battery2
Yes
Connected
Battery3
Yes
Connected
Battery4
Yes
Connected
Rated Capacity
150 Ah
Installation Time
-
Fourth-Level
Menu
Door sensor
Water sensor
Smoke sensor
Ambient Temp.
Sensor
Ambient Humi.
Sensor
6 Commissioning
Setting
NOTE
If N battery strings
are connected, set
Battery 1 Connected
to Battery N
Connected to Yes,
and set the other
parameters to No.
Rated capacity of
the batteries in a
battery string.
NOTE
The batteries
connected to one
circuit breaker or fuse
are called a battery
string.
Set this parameter to
the current date.
Default
Setting
Value
None
Set to Yes or
None based
None
on site
requirements.
None
None
None
45