7.3 Identifying Component Faults

7.3.1 Identifying AC SPD Faults

Check the color of the AC SPD indication window. Green indicates that the AC SPD is
normal. Red indicates the AC SPD is faulty.

7.3.2 Identifying Circuit Breaker Faults

The following indicate that the circuit breaker is faulty:

7.3.3 Identifying Rectifier Faults

A rectifier is damaged if any of the following conditions is not met:

7.3.4 Identifying SMU Faults

The following indicate that the SMU is faulty:
Issue 05 (2020-04-07)
The DC SPD is faulty.
Check whether the DC SPD detection cable is disconnected. If so, reconnect the cable.
If the DC SPD detection cable is reliably connected, replace the DC SPD.
The circuit breaker cannot be switched to ON/OFF after the short circuit fault for its end
circuit is rectified.
When the circuit breaker is switched to ON and its input voltage is normal, the voltage
between the two ends of the circuit breaker exceeds 1 V.
The input voltage is normal, but the resistance between both ends of the circuit breaker is
less than 1 kΩ when the circuit breaker is OFF.
When the rectifier does not communicate with the SMU and the AC input voltage is
around 220 V, the green indicator on the rectifier is steady on, the yellow indicator is
blinking, the red indicator is off, and the rectifier output is normal.
The SMU can perform equalized charging, float charging, and current limiting control
for the rectifier when the communication cable to the rectifier is correctly connected and
communication is established between the rectifier and the SMU.
The DC output is normal but the green indicator on the SMU is off.
The SMU breaks down or cannot be started. Its LCD has abnormal display or buttons
cannot be operated.
With alarm reporting enabled, the SMU does not report alarms when the power system is
faulty.
The SMU reports an alarm when the power system is not faulty.
The SMU fails to communicate with the connected lower-level devices even though the
communications cables are correctly connected.
Communication between the SMU and all rectifiers fails even though the rectifiers and
the communications cables are normal.