Installation - Carrier 40TGF UP Series Installation Manual

4-way cassette air conditioner
Hide thumbs Also See for 40TGF UP Series:
Table of Contents

Advertisement

Available languages

Available languages

Discharge direction
As shown in the figure below, air discharge directions
can be selected according to the shape of the room and
the location of the indoor unit installation.
3 directions
2 directions
Use a shielding plate kit (sold separately) to change
discharge directions.
Discharge directions are limited. Follow the
installation manual supplied with the shielding plate
kit.
Shielding plate
(sold separately)
REQUIREMENT
When using the air conditioner with 2-way / 3-way
discharge system, a strong wind blows directly if the
ceiling height is lower than the standard.
Therefore, change the setting switch according to height
of the ceiling by wired remote controller (sold separately).
17-EN
4

Installation

REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
Do not put a heavy article on the indoor unit. (Even units are packaged)
Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
External view
Ceiling bottom
Knockout square hole
surface
for divide duct
B
For Ø150
840 Unit external dimension
Knockout square
hole for divide duct
For Ø150
690 ± 20 Hanging bolt pitch
860 to 910 Ceiling opening dimension
950 Panel external dimension
Ceiling bottom
surface
Knockout for
simple OA
For Ø100
Z view
Ceiling bottom surface
Ceiling panel (sold separately)
Knockout square hole for humidifier
Model
0131UP, 0181UP, 0241UP, 0301UP
0361UP, 0401UP, 0481UP, 0601UP
– 9 –
Ceiling bottom surface
Refrigerant pipe
connecting port
(Liquid)
Electrical
control box
Take-in port
of wires
Refrigerant pipe
connecting port
(Gas)
Drain pipe
connecting
port
Ceiling
bottom
surface
Knockout square hole
for divide duct
For Ø150
Hanging bolt M10 or Ø3/8
(Locally procured)
Knockout square hole for divide duct
For Ø150
A
B
256
120
319
183
(Unit:mm)
860 to 910 Ceiling open dimension
18-EN