Applicable controls

A wired remote controller is required for applicable controls.
Purchase a wired remote controller (sold separately).
REQUIREMENT
When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes approx. 5 minutes until the remote controller
becomes available.
Approx. 5 minutes
Power
"SETTING"
"SETTING"
Remote
flashes
goes out
controller
on
is available
<When power is turned on for the second (or later)
time>
It takes approx. 1 minute until the remote controller
becomes available.
Approx. 1 minutes
Power
"SETTING"
"SETTING"
Remote
on
flashes
goes out
controller
is available
Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
Use the wired remote controller to change the
settings.
* The settings cannot be changed using the wireless
remote controller, sub remote controller, or remote-
controllerless system (for central remote controller
only). Therefore, install the wired remote controller to
change the settings.
31-EN
Changing of settings of for
applicable controls
Basic procedure for changing settings
Change the settings while the air conditioner is not
working.
(Be sure to stop the air conditioner before making
settings.)
1
3
4
6
1
5
2
1
Procedure
Push
button and temp. setup
button
simultaneously for 4 seconds or more.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [01].
If the CODE No. is not [01], push
button to erase
the display content, and repeat the procedure from
the beginning.
(No operation of the remote controller is accepted for
a while after
button is pushed.)
(* Display content varies with
the indoor unit model.)
2
Procedure
Each time you push
button, indoor unit
numbers in the control group change cyclically. Select
the indoor unit you want to change settings for.
The fan of the selected unit runs and the louvers start
swinging. You can confirm the indoor unit for which you
want to change settings.
3
Procedure
Using temp. setup
/
buttons, specify CODE
No. [
].
4
Procedure
Using timer time
/
buttons, select SET DATA
[
].
5
Procedure
Push
button. When the display changes from
flashing to lit, the setup is completed.
To change settings of another indoor unit, repeat
2
from Procedure
.
To change other settings of the selected indoor unit,
3
repeat from Procedure
.
Use
button to clear the settings.
To make settings after
button was pushed, repeat
2
from Procedure
.
6
Procedure
When settings have been completed, push
to determine the settings.
When
button is pushed, "SETTING" flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
– 16 –
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
For the CODE No. in Procedure
, specify [5d].
4
Select the SET DATA for Procedure
"Height list of ceiling possible to be installed" table in
this manual.
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. board.
The settings can also be changed with the switch on
the indoor microcomputer P.C. board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
button
SW501-2
SW501-1
MCU(IC501)
SET DATA
SW501-1
0000
OFF
(Factory default)
0001
ON
0003
OFF
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
from the
SW501-2
OFF
OFF
ON
EN
ID
32-EN