Available languages

Filter sign setting
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
For the CODE No. in Procedure
, specify [01].
4
For the [SET DATA] in Procedure
, select the SET
DATA of filter sign lighting time from the following
table.
SET DATA
Filter sign lighting time
0000
None
0001
150 H
0002
2500 H (Factory default)
0003
5000 H
0004
10000 H
Horizontal wind direction
1
Push
and TEMP.
buttons for 4
seconds or more when the air conditioner is
not working.
flashes.
Indicates CODE No. "01."
2
Select an indoor unit to be set by pushing
button (left side of the button).
Indoor unit number changes each time you
push the button.
Unit No.
Unit No.
Unit No.
1-1
1-2
1-3
Not
Unit No.
display
1-4
The fan of the selected unit runs and the louvers
start swinging.
3
Change the CODE No. to "45" with
TEMP.
buttons.
4
Select wind direction setting with
TIME
buttons.
Wind direction
Wind direction setting
setting code
Smudge reducing position
0000
(Air direction to reduce ceiling
contamination)
Cold draft position
0002
(Air direction to control cold air fall)
[Factory default]
33-EN
5
Push
button to check the setting.
The display state changes from flashing to
lighting, and the setting is fixed.
6
Push
button to end the setting.
* When the cold draft position is selected, ceiling
contamination is less reduced.
Swing type
1
Push
for 4 seconds or more when the
air conditioner is not working.
flashes.
Indicates CODE No. "F0."
2
Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit
numbers change as follows:
Unit No.
Unit No.
Unit No.
1-1
1-2
1-3
Not
Unit No.
display
1-4
The fan of the selected unit runs and the louvers
start swinging.
3
Select a swing type by pushing TIME
buttons.
Swing SET DATA
Swing SET DATA
Swing of louvers
Standard swing
0001
(Factory default)
0002
Dual swing
0003
Cycle swing
CAUTION
Do not set the swing SET DATA to "0000".
(This setting may cause a failure of the louvers.)
– 17 –
About "Dual swing"
"Dual" means that louvers 01 and 03 are directed
and swing in one direction and louvers 02 and 04 are
directed and swing in the opposite direction.
(When louvers 01 and 03 are directed downward,
louvers 02 and 04 are directed upward.)
About "Cycle swing"
The four louvers swing independently at respective
timings.
Electrical control box
03
Refrigerant
pipe
04
Drain pipe
01
4
Push
button.
5
Push
button to complete the setting.
Louver lock (No swing)
1
Push
(right side of the button) for 4
seconds or more when the air conditioner is
not working.
flashes.
Indicates CODE No. "F1."
2
Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit
numbers change as follows:
The fan of the selected unit runs and the
louvers start swinging.
Unit No.
Unit No.
Unit No.
1-1
1-2
1-3
Unit No.
02
1-4
3
Select a louver you want to lock by pushing
TEMP.
buttons.
4
Select the wind direction of the louver you
do not want to swing by pushing
TIME
buttons.
(1)
(2)
Setting data
0001
0002
0003
(4)
(5)
0004
0005
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
5
Determine the setting by pushing
When the setting has been determined,
lights up.
6
Push
button to complete the setting.
0001-0005
(Louver lock position code)
(3)
button.
34-EN