DC Wire Gauge & Fusing Continued
Make an Inverter Cable Kit
1. Use a stranded copper cables in all cases.
NOTE: The recommended maximum length of the inverter cable is 15 ft, and it must be fused within 18 inches of
the positive (+) terminal of the battery.
2. Use SGX cross-linked polyurethane insulation type that complies with the high temperature insulation
requirements (125°C.) of SAE J-1127 and vehicle manufacturer requirements. Reference Table 2. For 1/4" ring
lugs, use JST 38-S6.
3. Torque the DC connections on the inverter to 95 in-lbs.
4. Torque the inverter bonding lug to 45 in-lbs for 6 AWG or 40 in-lbs for 8 AWG.
NOTE: Use a 3/8" deep socket wrench to install the ¼"-20 serrated flanged hex bolt.
¼"-20 Serrated Flanged Hex Bolt
Figure 3 Proper Installation of Cable into DC Terminal Cover
12LPC15 Manual
DC Terminal Cover
Cable with Ring Terminal
Page 11