5.4.3 I Operating principles of electrical protection
5.4.3.1 Protection system
The compressor's time delay is configurable (see § "5.3 I Advanced setting parameters (accessible by a qualified
technician)", setting F21). This delay is used by the regulator to avoid continuous ON/OFF cycles. When the compressor
stops following an operating phase, the regulator checks that this time has elapsed before it restarts the compressor. If
not, the compressor can only restart after 5 minutes. This 5 minute period must also elapse before the compressor can
start up when the equipment has just been started.
5.4.3.2 Remote switch
When the remote switch is closed, the switched-off appliance remains switched-off and the running appliance continues
to operate normally. When the remote switch is open, the switched-off appliance remains switched-off and the running
device stops. "OFF" is then displayed on the screen.

5.5 I Wiring diagrams

Wiring diagrams are available at the end of the document see § 5.5 Schémas électriques / Wiring diagrams /
Schaltplan / Elektrischschema / Esquema eléctrico / Esquema eléctrico / Schema elettrico.