4.4 I Accessing to system parameters

Modifying the default settings must be performed by a qualified technician only to facilitate
maintenance or future repairs.
To access to the system parameters:
- Unlock the keypad: the main menu is displayed.
- Press
five times :
- Press
. The screen displays "
- Press simultaneously
- Press
. The first number flashes. Press
pressing
,
- Press
to browse through the available parameters (see following table) and press
- Pressing
or
- Press
for 3 seconds to return to the main screen.
The parameters that can be modified are listed in the following table.
Code
Name
L0
Heating priority
Period between 2
L1
filtration pump starts
L2
Timer setting
Power OFF remember
L3
function
Background light
L4
setting
L5
Unit operation mode

4.5 I Wiring diagrams

See the wiring diagrams at the end of the document.
27
icon flashes.
SET
000
".
and
for 3 seconds. A signal tone will sound.
to modify the value and validate by pressing
0 : Heating priority output active (P1P2 powered)
1: Heating priority activated
Filtration pump works 5 min per L1 min (L1 range :
3 - 180) to check if heating is needed
0 : timer function OFF
1 : timer function ON
0 : No background light
1 : light ON constantly
2 : light ON if operating, light OFF if no operation
0 : Heating only
2 : Heating & Cooling
3 Cooling / Heating / Auto / Quick Heating /
Ecosilence / Heating mode / Quick Cooling /
Ecosilence / Cooling mode
or
to enter the password :
,
Range
0 : OFF
1 : ON
1 : Cooling only
138
. Validate each number by
to modify the parameter,
Default
1
120
1
1
2
3