Connection; Safety Instructions - Siemens SENTRON PAC1020 Manual

7km power monitoring device
Hide thumbs Also See for SENTRON PAC1020:
Table of Contents

Advertisement

Connection

4.1

Safety instructions

Notes
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this equipment before working on this device.
Open transformer circuits will result in electric shock and arc flash hazards.
Will cause death, serious personal injury, or equipment damage.
Do not open the secondary circuit of the current transformers under load. Short circuit the
secondary current terminals of the current transformer before removing this device. It is
imperative that you follow the safety instructions for the current transformers you are
using.
Protection of the supply voltage and voltage measuring inputs
The miniature circuit breakers in the supply voltage and the voltage measuring inputs are
only used for cable protection. The method of cable protection must be selected according
to the design of the supply cable.
You may use miniature circuit breakers up to 20 A (C). Choose a method of cable protection
that conforms to the relevant regulations.
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
DANGER
DANGER
CAUTION
4
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7km1020-0ba01-1da0

Table of Contents