Parameterizing
7.2 Parameterizing via the operator interface
7.2.3

Basic parameters

Measuring inputs can be parameterized in the "BASIC PARAMETERS" menu item.
Voltage input
Selection
CONNECTION TYPE
USE PTs
PT PRIMARY
(USE PTs
PT SECONDARY
(USE PTs
52
Range
Selection of connection type
3P4W:
3 phases, 4 conductors
3P3W:
3 phases, 3 conductors
ON:
Measurement using voltage transformers.
When measuring via voltage transformers, the
device must know the voltage transformation
ratio. For this purpose, the primary and sec-
ondary voltages must be specified in the fields
"PT PRIMARY" and "PT SECONDARY".
When changing from direct measurement to
measurement using voltage transformers, the
device accepts the last set reference measur-
ing voltage as the secondary voltage and as
the primary voltage.
Measurement directly on the low-voltage sys-
tem.
When changing from measurement using
voltage transformers to direct measurement,
the device accepts the last set secondary volt-
age as the reference measuring voltage.
1 ... 999999 V, freely adjustable
ON)
1 ... 400 V, freely adjustable
ON)
OFF:
Equipment Manual, 05/2020, L1V30610008B-01
Factory
setting
3P4W
OFF
400 V
400 V
PAC1020