Technical Data - Siemens SENTRON PAC1020 Manual

7km power monitoring device
Hide thumbs Also See for SENTRON PAC1020:
Table of Contents

Advertisement

Technical data

Device configuration
• 1 optically isolated digital input
• 1 optically isolated digital output
• 1 RS485 interface for connecting to a PC or network
Measurement
Only for connection to AC voltage systems.
Measurement
Measuring method
Measured value acquisition
Measuring inputs for voltage
Measuring inputs for voltage
Measurable voltage
Zero point suppression level
Measuring category
(acc. to IEC/UL 61010-2-030)
Input resistance (L N)
Max. power consumption per phase
Max. voltage at measuring input
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
Voltage measurement
Current measurement
Power
Frequency
Power factor
Waveform
Frequency of the relative fundamental
Measured value acquisition mode
Rated voltage
Min. measuring voltage U
Max. measuring voltage U
Voltage L-N
Voltage L-L
Category
Impulse withstand voltage
True RMS measurement (TRMS),
zero blind measurement, gapless
True RMS measurement (TRMS),
zero blind measurement, gapless
Zero blind measurement, gapless
Sinusoidal or distorted
50/60 Hz
Automatic line frequency detection
57.7 V/ 100 V ... 230 V/ 400 V
11.5 V
L-N
280 V
L-L
10 V
17 V
CAT III
≥ 9.6 kV (1.2/50 μs)
1.5 MΩ
150 mW
U
300 V
L-N
10
65