Cable Installation To Controller; Refitting Cet Bars - Siemens ST950 Handbook

Hide thumbs Also See for ST950:
Table of Contents

Advertisement

Apply silicone sealant
between stool and case
996/4/22026/100
7.3.6

Cable Installation to Controller

Wiring runs should be made neatly and routed to allow enough spare cables for
possible changes/additions at a later date.
Spare cores are to be bundled and routed to a convenient position clear of the
mains. The ends are to be insulated to make the loom secured. Spare cores of ELV
cables are to be loomed separately to the cores of LV cables. Note: normally spare
cores are earthed at the controller end, as this makes Periodic Inspection Insulation
Resistance testing much easier.
If cable idents are required then these are fitted to cores before termination.
All cables into the controller should be fed into the outer case as close to their
termination positions as possible. This is to prevent unnecessary damage being
caused should any cables need to be moved once they are in place. Care must be
taken not to obstruct the Electricity Supply Company cut out with any cabling.
7.3.7

Refitting CET bars

Re-fit the CET bars in the most suitable positions to suit the cable run.
Security classification
Version
Last Editor
Document Name
Copyright © Siemens plc 2020. All Rights Reserved.
Figure 49 - Stool Installation
Unrestricted
7
manpreet.jeerh
ST950 ICM Handbook
Mobility, Intelligent Traffic Systems
Sopers Lane, Poole, Dorset, BH17 7ER
Page
Status
Date
Document No.
Mobility is a division of Siemens Plc
93 of 154
Issued
January 2020
667/HE/45950/000

Advertisement

Table of Contents
loading

Table of Contents