3. INSTALLATION DETAILS

The electrician is responsible for selecting a cable thickness & safety components appropriate
for the specific situation and according to regulations;
Wiring advice*
Power cable size
Earthing advice*
Required nominal
input voltage @
charge point
MCB
RCD
Dynamic Power
Management module
*
The electrician is always responsible for selecting a cable thickness appropriate for the specific situation and
according to regulations;
** The electrician must select a suitable MCB with C-characteristic to match the amperage setting of the charge
point, taking into account MCB manufacturer specifications and EV-Ready guidelines;
NOTE: The charge point can be set between 16A / 20A / 25A and 32A (depending on version), see chapter 5.
INSTALLATIEHANDLEIDING – P23
INSTALLATION MANUAL – P23 | P23
- Wire for the maximum hardware amperage under continuous load;
- Calculate with a COS-Phi of 0.8;
- Calculate with a max allowable voltage drop over the cable of 2%;
- Use shielded cable for underground wiring
Cable grommets sizes
Maximum cable terminal block
TN-system
TT-system
Single phase
C-characteristic**
30mA Type B, or 30mA Type A (Hi, Hpi, Si) in combination with appropriate
equipment that guarantees power shutdown at DC leakage of more than 6mA
Standard cable of 2x 1,5mm
With a maximum length of 100 meter
VERSION 0129NM02INT01
06ANM20INT01
Ø 10mm - Ø 22,5mm
10mm
solid wire
2
6mm
stranded wire with end ferrules
2
PE-cable (Pen conductor is not allowed)
Separately installed grounding electrode < 100
Ohm spreading resistance
230V+N +/-10% 50Hz
2