32
575 Volt fuses for packaged drive
575 Volt
Type code
ACS580-0P-02A7-6+F255+G310
ACS580-0P-03A9-6+F255+G310
ACS580-0P-06A1-6+F255+G310
ACS580-0P-09A0-6+F255+G310
ACS580-0P-011A-6+F255+G310
ACS580-0P-017A-6+F255+G310
ACS580-0P-022A-6+F255+G310
ACS580-0P-027A-6+F255+G310
ACS580-0P-032A-6+F255+G310
ACS580-0P-041A-6+F255+G310
ACS580-0P-052A-6+F255+G310
ACS580-0P-062A-6+F255+G310
ACS580-0P-077A-6+F255+G310
ACS580-0P-099A-6+F255+G310
ACS580-0P-125A-6+F255+G310
ACS580-0P-144A-6+F255+G310
*When G418 option is included and on all R8 and R9 drives. (See

Operation

This information is unique to ACS580 bypass configurations (0P+F255+G310). This
drive system uses the ACS580-01 Hand/Auto macro for run operation. See section
Control Macros, Hand/Auto Macro in the ACS580 Standard Control Program
Firmware Manual page 90 for complete information.
ACS580-0P with Bypass
Supplemental Installation Manual for ACS580-0P
Nominal Output
Base
Internal Drive Fuse
Range
Drive
Rating
Frame
Drive
Package
Size
current
power
A
HP
Class
2.7
2
R2
Class CC
3.9
3
R2
Class CC
6.1
5
R2
Class CC
9
7.5
R2
Class CC
11
10
R2
Class CC
17
15
R2
Class CC
22
20
R3
Class T
27
25
R3
Class T
32
30
R3
Class T
41
40
R5
Class T
52
50
R5
Class T
62
60
R5
Class T
77
75
R5
Class T
99
100
R7
Class T
125
125
R7
Class T
144
150
R8
Class T
Bypass Fuse Rating (only
with Type EF Electronic
Overload)*
Current
Class
rating
(amps)
15
Class J
15
Class J
15
Class J
15
Class J
15
Class J
30
Class J
40
Class J
40
Class J
40
Class J
50
Class J
80
Class J
80
Class J
100
Class J
150
Class J
175
Class J
200
n/a
page
9)
Current
rating
(amps)
10
10
10
15
20
30
40
50
50
70
80
100
125
150
200
n/a