Connection diagrams - UL Type 12
ACS580-0P Type 12 units are configured for wiring access from the top and bottom.
Top is dedicated for entry; the bottom for exit. The following figures show the layout
and wiring connection points. For drive control wiring see section Connecting the
control cables in
control and power wires.
DR1
R1
Fuses
ACS580-0P with Bypass
ACS580 Hardware
Cable Entry
T1
50VA
L1
L2
L3
M1
M2
CB1
2/5/7.5HP
3/7.5/10A
15A
1TB
4
5
5
7
8
9
10
13
14
10-13A
4
5
5
7
8
9
10
13
14
OL1
Control
T1
T2
Terminals
Cable Exit
Motor
Ground Lug
CX12-21
Supplemental Installation Manual for ACS580-0P
Manual. Maintain appropriate separation of
Input Power
Terminals
Input
Ground Lug
WARNING
RISK OF FIRE OR ELECTRIC SHOCK-
The opening of the branch-circuit protective device may
be and indication that a fault current has been
interrupted. All current-carrying parts and other
components protected by this device should be
examined and replaced if damaged. If burnout of a
current element of an overload relay occurs, the
complete overload relay must be replaced.
CAUTION
Fan
VOLTAGE MAY BE PRESENT FROM MORE
THAN ONE SOURCE AND SHOULD BE
DISCONNECTED FOR SERVICING.
Exhaust
ATTENTION
PEUT ETRE SOUS TENSION DE PLUS D'UNE
SOURCE D'ALIMENT ELECTRIQUE. COUPER TOUTES LES
SOURCES D'ALIMENTATION AVANT LE DEPANNAGE.
OFF
DRIVE
Air
Inlet
Allow 6" between enclosures for cooling
T3
Motor
Terminals
!
WARNING
Wait at least 5 minutes after disconnecting
supply before continuing to work.
Consult the Installation & Start-Up Manual
before working on the frequency converter.
ATTENTION!
!
Attendre au moins 5 min apres sectionnement
de l'alimntation pour travailler sur l'appareil.
Consulter le Manuel d'installation et de mise
end route avant d'intervenir sur le convertisseur
de frequence.