E5CK-T

Display Range Over

Meaning
Operation
Motor Calibration Error (Displayed on the No. 2 Display)
Meaning
Action
Operation Procedure
Operation at Error
Though not an error, this is displayed when the process value exceeds the display range when the
control range (setting range ±10%) is larger than the display range (–1999 to 9999).
When less than "–1999"
When greater than "9999"
Control continues, allowing normal operation.
Motor calibration has ended with an error.
First, correctly connect the wiring for the potentiometer, open output, and close output.
Execute the motor calibration again.
When motor calibration is executed, open output will operate and then close output will operate.
However, as the value is incorrect, the result turns out to be an error.
E5CK-T
193