12.1 Process data

Parameter
1)
Setpoint 1
1)
Setpoint 2 (option)
Digital setpoint shift (optional)
Outside temperature (optional)
Pre-definition of external setpoint
1)

12.2 Parameter level

Parameter
Limit value of limit comparator
Switching differential for limit
1)
comparator
1)
Proportional band
Derivative time
Integral action time
1)
Contact spacing
Actuator running time
Switch-on threshold burner /
1)
stage II
Switch-off level stage II
Upper switch-off threshold
Response threshold
Heating curve slope
1).
Parallel displacement
Landis & Staefa Division
Display
SP1
SP2
1)
dSP
TA
SP.E
1)
These parameters are affected by the setting for the decimal place.
Display
1)
AL
HYSt
Pb.1
dt
rt
db
tt
H Y S 1
1)
H Y S 2
1)
H Y S 3
q
H
P
1)
These parameters are affected by the setting for the decimal place.
CC1B7865E
Value range
SPL-SPH
SPL-SPH
SPL-SPH
Section 8.1
«C111 Inputs»
SPL-SPH
Value range
-1999...+9999 digit
0...999.9 digit
0.1...999.9 digit
0...9999 s
0...9999 s
0...999.9 digit
10...3000 s
0...-199.9 digit
0... HYS3 digit
0...999.9 digit
0...999.9
0...4
-90...+90
February 10, 2000
12. Actual settings
Factory
Setting
setting
0
0
0
-
-
Factory
Setting
setting
0
1
10
80
350
1
15 s
-5
3
5
0
1
0