Function Ik4
Function Ik5
Function Ik6
42/56
As for lk3, but with inverted switching function.
Output 4
HYSt
7865d03e/0300
HYSt = switching differential
AL = interval from setpoint
Chapter 7 «Parameter settings»
Upper limit signaling
Function: relay inactive when measured value > (setpoint + limit value).
Example: w = 80 °C, AL = 10, HYSt = 2
Measured value rising: relay «K6» switches off at 91 °C.
Measured value falling: relay «K6» switches on at 89 °C.
Output 4
7865d05e/0300
w
As for lk5, but inverted switching function.
Output 4
7865d06e/0300
w
CC1B7865E
AL
Measured value
w
AL
HYSt
AL
HYSt
February 10, 2000
8. Configuration
Measured value
Measured value
Landis & Staefa Division