12.1 Process data
Parameter
1)
Setpoint 1
1)
Setpoint 2 (option)
Digital setpoint shift (optional)
Outside temperature (optional)
Predefinition of external setpoint
1)
12.2 Parameter level
Parameter
Limit value of limit comparator
Switching differential for limit
1)
comparator
1)
Proportional band
Derivative time
Integral action time
Dead band (neutral zone)
Actuator running time
Switch-on threshold burner /
1)
stage II
Switch-off level stage II
Upper switch-off threshold
Response threshold
Heating curve slope
1).
Parallel displacement
56/57
Display
SP1
SP2
1)
dSP
TA
SP.E
1)
Setting of the decimal places has an impact on these parameters
Display
1)
AL
HYSt
Pb.1
dt
rt
1)
db
tt
H Y S 1
1)
H Y S 2
1)
H Y S 3
q
H
P
1)
Setting of the decimal place has an impact on these parameters
CC1B7865en
Value range
SPL-SPH
SPL-SPH
SPL-SPH
ð
Section 8.1
«C111 inputs»
SPL-SPH
Value range
-1999...+9999 digit
0...999.9 digit
0.1...999.9 digit
0...9999 s
0...9999 s
0...999.9 digit
10...3000 s
0...-199.9 digit
0... HYS3 digit
0...999.9 digit
0...999.9
0...4
-90...+90
05.12.2002
12. Actual settings
Factory
Setting
setting
0
0
0
-
-
Factory
Setting
setting
0
1
10
80
350
1
15 s
-5
3
5
0
1
0
HVAC Products