Download Print this page

Hitachi FSXN1E Series Installation And Operation Manual page 80

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 15
Electrical wiring
10.6 FUNCTION SETTING
10.6.1 External input/output and function
setting

Start of setting
Turn ON DSW4-No.4. Press PSW1 for 3 seconds or more. "Menu
Mode" will be indicated.

End of setting
Press PSW1 for 3 seconds or more when "Menu Mode" is dis-
played. The display indication become normal. Turn OFF DSW4
number 4.
N O T E
Release "Menu Mode" after the setting is completed. Otherwise,
the air conditioner may not operate appropriately.
1 External input and output setting
By pressing the push-switches PSW3 ( ) and PSW5 ( ), the
function number can be selected.
PSW4 ( ): forward, PSW2 ( ): backward
Fill out the selected function setting number in the space of the
table as shown.
Example:
Item
1
Input Setting 1 CN17 (1-2 pin)
2
Input Setting 2 CN17 (2-3 pin)
3
Input Setting 3 CN18 (1-2 pin)
4
Output Setting 1 CN16 (1-2 pin)
5
Output Setting 2 CN16 (1-3 pin)
(Setting before shipment)
Before shipping, the input/output function settings are specified
to each input/output terminal according to above table. The de-
tails of function number and external input/output settings are as
shown below.
Setting of external input and output function:
Function
Input
number
1
Fixing heating operation mode
2
Fixing cooling operation mode
3
Demand stoppage
4
Outdoor fan motor start/stop
5
Forced stoppage
6
Demand current control 40%
7
Demand current control 60%
8
Demand current control 70%
9
Demand current control 80%
10
Demand current control 100%
11
Low noise setting 1
66
PMML0294A_rev.2_02-2014.indb 66
SEG2
SEG1
i1
1
i2
2
i3
3
o1
1
o2
2
Output
Operation signal
Alarm signal
Compressor ON signal
Defrost signal
-
-
-
-
-
-
-
PMML0294A rev.2 - 07/2014
Menu Mode
Check mode
CHEC
"
"
External input
and output
ioS
"
"
Function setting
Func
"
"
Function
number
12
Low noise setting 2
13
Low noise setting 3
0
No setting
The same input/output function setting cannot be set to different
input/output terminals. If set, a setting of larger function number
becomes invalid.
SET
Example: When setting of input 1 and input 2 are same, input 2
will be invalid.
2 Function Setting
By pressing the push-switches PSW3 ( ) and PSW5 ( ), the set-
ting can be changed.
PSW4 ( ): forward, PSW2 ( ): backward
Refer to the Service Manual for more details.
Fill out the selected function setting number in the space of the
table as shown.
Example:
Item
Circulator function at heating
1
Thermo-OFF
2
Night-Shift (Low noise)
Cancellation of outdoor ambient
3
temperature limit
Defrost for cold area (change of
4
defrost condition)
5
SLo (fan speed) defrost setting
6
Cancellation of hot start
7
Priority capacity mode
Compressor frequency control
8
target value for cooling
Compressor frequency control
9
target value for heating
Press PSW1 one
For more details, refer to
Checking
of outdoor unit by PCB
in the Service
Manual
For the setting mode, refer to  below
For the function setting, refer to 
below
Input
Output
-
-
No setting
SEG2
SEG1
FA
O
ni
O
G5
O
Jo
O
bJ
O
H
O
nU
O
Hc
O
Hh
O
SET
14/07/2014 12:28:39

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Fsxnh seriesFsxnhe seriesRas-8fsxn1eRas-10fsxn1eRas-12fsxn1eRas-14fsxn1e ... Show all