8.2.6 Access levels for the
Parameter levels P02 to P23 can be accessed if password 5 or the password for the operating mode parameter is selected in parame-
ter P01. If parameter P07 has the value 2, this parameter level is accessible without a password.
Parameters depicted in italics cannot be changed.
Indication of the selected parameters in the display during parameter entry.
Function
Password
Nominal temperature
Defrosting cycle [hr]
Defrosting duration [min]
Humidity
(evaporator fan operating mode)
LO=run time w. condenser
(low rel. humidity)
HI=continuous run
(high rel. humidity)
Language
d = German
e = English
f = French
Keyboard release
P07 = 0 : Keyboard lock is switched on
P07 = 1 : Keyboard is released
P07 = 2 : The parameters P02 to P09 can be pro
cessed without password.
P07 = 3 : The nominal temperature can be pro-
cessed without password.
Display of evaporator temperature
Display of condenser temperature
The following parameters are indicated only if the value x2 is set in P30 and a DCF radio clock receiver is connected.
current time [hr]
current time [min]
Defrosting time 1
Defrosting time 2
Defrosting time 3
Defrosting time 4
Defrosting time 5
Defrosting time 6
Defrosting time 7
Defrosting time 8
Defrosting time 9
Defrosting time 10
Defrosting time 11
Defrosting time 12
Access levels for the refrigeration specialist company: Access to the levels beyond P29 (access levels for the refrigeration specia-
list company) is possible only if the password for the Operating mode parameter has been selected in parameter P01 (see special

Parameter list).

If a new key actuation does not take place within 10 sec., parameter entry will be ended and the coldroom temperature will be indica-
ted. The yellow LED in the "Stop-Start-Enter" key goes out; this key takes over the "Stop-Start" function.
The Control unit functions can be monitored continuously via several parameters. In this case, the yellow LED in the "Stop-Start-
Enter" key blinks. By actuating the the "Stop-Start-Enter" key, the LED goes to continuous operation for 10 sec.; the indication then
jumps back to normal operation.
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or
regarding a certain purpose always require a special written agreement.
Page No. 22-GB
System operator
Parameter
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
P22
P23
German
English
P01
P01
SL.t.
n.t.
Ab.h
dE.C
Ab.d
dE.t
r.F.
HU.
P06
P06
tA.F
bo.E
P08
P08
P09
P09
P10
P10
P11
P11
t.01
t.01
t.02
t.02
t.03
t.03
t.04
t.04
t.05
t.05
t.06
t.06
t.07
t.07
t.08
t.08
t.09
t.09
t.10
t.10
t.11
t.11
t.12
t.12
8.2.6
French
Unit
P01
t.n.
°C
c.dE
hours
d.dE
minutes
HU.
P06
bo.E
P08
°C
P09
°C
P10
hours
P11
minutes
t.01
hh.m (x10)
t.02
hh.m (x10)
t.03
hh.m (x10)
t.04
hh.m (x10)
t.05
hh.m (x10)
t.06
hh.m (x10)
t.07
hh.m (x10)
t.08
hh.m (x10)
t.09
hh.m (x10)
t.10
hh.m (x10)
t.11
hh.m (x10)
t.12
hh.m (x10)
We reserve the right to make technical changes!
Range
0-99
P31...P32
1...24
5...60
0...3; 10....13
-50...50/OFF
0...99/OFF
0...23
0...59
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5
00.0...23.5