Installation Of A Split Unit In A; Viessmann Cold Storage Cell; Installation Of The Condenser Unit - Viessmann CS Installation And Operating Instructions Manual

Refrigeration units with sd control unit
Table of Contents

Advertisement

5. Installation of a Split unit in a

Viessmann cold storage cell

5.1

Installation of the condenser unit

The condenser unit is installed outside the cold storage
cell. The length of the electric lines on the condenser unit,
including plug, is 15 m. This is also the maximum distance
between the condenser unit and the evaporator unit.
The minimum distance to the room ceiling must be at least
250 mm in order to warrant a good air flow.
Attention!
This minimum distance must be checked prior to instal-
lation of the condenser unit!
Attention!
Assembly and installation of the Refrigeration unit in
the split version must be carried out by a refrigeration
specialist company according to applicable refrigerati-
on-related regulations!
Loosen the locking screws (4 ea.) on the front access cover.
Remove the front access cover by pulling upwards and for-
ward.
Attach the condenser unit to the wall through the prescri-
bed bore holes on the back-side of the unit, using the
attachment materials included in the enclosed accessory kit.