Error Message; Wi-Fi Reset & Wi-Fi Reload; Precaution For Initial Startup - Goodwe DNS Series User Manual

Solar inverter
Hide thumbs Also See for DNS Series:
Table of Contents

Advertisement

the button to check the result.
Main Menu
Sbu Menu
Long Press
Auto Test
Auto Testing
Pac=XXXX.XW
...
Choose auto test type between "Remote" and "Local" before starting the test. Under "Remote"
mode, the default setting is 1 and cannot be modified. Under "Local" mode, the default setting is
0 and can be set to 0 or 1 by calibrating the software. If it is 1 under "Local" mode, the testing order
will be 59.S1, 59.S2, 27.S1, 81>S1, 81<S1. Otherwise, the testing order will be 59.S1, 59.S2, 27.S1,
81>S2, 81<S2.
Connect AC, then the auto test will start after the inverter relay breaks off successfully: output
power is zero and LCD shows the information about testing.
If sub test finishes and LCD displays "Test ***** Ok", the inverter relay willbreak off and reconnect
to grid automatically according to CEI 0-21 requirement. Then the next test starts.
If sub test fails, the inverter relay breaks off and enter wait mode. To retry, the inverter needs to be
totally powered off and be restarted.
5.2.10 Operation Of Display When Commissioning
The LCD starts to work when the input voltage reaches the inveter's turn-on voltage. Then the
yellow light will be on and the LCD will display "Waiting". In a few seconds, more information will
be displayed. After the inveter connected to the grid, the LCD will display "Checking 30" and start
a 30s countdown. When the countdown goes to "00S" , you will hear the relay trigger 4 times and
see "Normal" display. The instant power output is displayed at the left bottom of the screen.

5.3 Error Message

An error message will be displayed on the LCD once a fault occurs.
Error code
Error message
03
Fac Fail
14
Isolation Fail
15
Vac Failure
17
PV Over Voltage
19
Over Temperature
23
Utility Loss
23
Main Menu
Wait
Normal
Pac=XXXX.XW
Main Menu
Short Press To Check The Value
Auto Test Result
Pac=XXXX.XW
Vac Fail
Test 59.S1 OK
Description
Grid frequency out of permissible range
The grund insulation impedance is too low
Grid voltage out of permissible range
Overvoltage at DC input
The temperature is too high
Utility is unavailable
5.4 Wi-Fi Reset & Wi-Fi Reload
These functions are only available for Wi-Fi model inverters.
Wi-Fi reload function is used to reconfigure the Wi-Fi to default. Please configure the Wi-Fi again
after using the function.
Short
Press
Short press the button until the LCD displays "Wi-Fi Reset", then long press the button until the
LCD displays "Wi-Fi Resetting�". Stop pressing until the LCD displays "Wi-Fi Reset OK" or "Wi-Fi
Reset Failed".
Main Menu
WiFi Reset
Pac=2595.5W
Short press the button until the LCD displays "Wi-Fi Reload", then long press the button until the
LCD displays "Wi-Fi Reloading�". Stop pressing until the LCD displays "Wi-Fi Reload OK" or "Wi-Fi
Reload Failed".
Main Menu
WiFi Reload
Pac=2595.5W

5.5 Precaution For Initial Startup

1. Make sure the AC circuit is connected and the AC breaker is off.
2. Make sure the DC cable between the inverter and the PV string is connected, and the PV voltage
is normal.
3. Turn on the DC switch, and set safety country according to the local regulation.
4. Turn on the AC breaker. Check whether the inverter can work normally.
Sub Menu
Long Press
Wait
WiFi Resetting
Sub Menu
Long Press
Wait
WiFi Reloading
WiFi Reset OK
WiFi Reset Fail
WiFi Reload OK
WiFi Reload Fail
24