1.1.1.1
Pressure controller
Configuration of three possible pressure controller.
1.
Open CV or CPA
2.
Go to «Tools» > «Terminal» and send setup command s:02 according
to application needs. (possibility of adjustment see below)
Set
Get
This command selects pressure controller.
a
Pressure controller
0 = Adaptive downstream
1 = Fixed 1
2 = Fixed 2
3 = Soft pump
4.6.2.1
With CPA 3.0 direct setup (standard)
Open the CPA. In menu 'Pressure Control' / 'Setup', select the 'Pressure controller' and do the setup for
pressure control algorithm (parameter).
42/94
INSTALLATION
Local operation:
('Control View' or 'Control Performance Analyzer')
Command
s:02Z00a
configure pressure controller a
i:02Z00
get the actual pressure controller a
For easy setup (Local operation) of 'Pressure controller' and 'Pressure control
parameter' please use the VAT "Control Performance Analyzer" CPA 3.0.
There is a free download on the VAT home page, refer to:
http://www.vatvalve.com/customer-service/informations-and-downloads/control-
performance-analyzer
Edition 2017-11-24
Acknowledgement
(within 10ms after reception of
command)
Describtion
i:02Z00a
Series 642
Remote operation:
It is not possible with
remote operation.
605403ED