FusionModule800 Smart Small Data Center
User Manual
Maintenance Item
Glass door steel glass
cleaning
Issue 01 (2021-02-05)
Operation
Battery connection
● Use a soft cotton
cloth to clean the
glass.
● Clean the glass
with clean water.
Do not use any
organic solvent
such as alcohol,
thinner, or glass
cleaner.
● To avoid scratching,
do not use
excessive force
when cleaning the
glass door.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
1. When battery
strings are powered
off, check the
reliability of each
connection point
from positive
terminals to
negative terminals.
Check that all
points are
connected reliably.
2. Use a torque
wrench to check
the tightening
torque for each
battery screw. The
torque meets the
requirements of the
battery
manufacturer. After
checking that the
battery screws
meet the
requirements, mark
the screws for later
check.
-
6 O&M
Troubleshooting
1. Rectify any
abnormal
connection.
2. If the fault persists,
contact Huawei
technical support.
-