Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
• Set the HOST link unit No. for "Unit No.".
Settings of External Device
Use the level key, mode key, down key and up key in front of the Temperature Controller for communication
settings of the External Device.
Please refer to the manual of the Temperature Controller for more details.
Procedure
1. Press and hold the level key (3 minutes or more) to transfer from the operation level to the default level.
2. Press the level key again to transfer from the default level to the communication setting level.
3. Press the mode key to select the parameter.
4. Press the down/up keys to change the setting.
5. Press and hold the level key to transfer to the operation level.
Setting Value
PSEL
U-NO
BPS
LEN
SBIT
PRTY
SDWT
• Parameters to be set vary depending on the Temperature Controller. Please refer to the manual of
the Temperature Controller for more details.
• Set Wait to Send to 2ms or more. Adjust Wait to Send according to the communication status.
GP-Pro EX Device/PLC Connection Manual
CWF
1
9.6
7
2
EVEN
2
Temperature Controller CompoWay/F Driver
.
9