4.9 Configuring user levels and their passwords................. 47 5 Functions unctions ...................................................... 50 5.1 Functions included in AQ-M210................... 50 5.2 Measurements........................51 5.2.1 Current measurement and scaling ................51 5.2.2 Frequency tracking and scaling ................. 64 5.3 Protection functions ......................67 5.3.1 General properties of a protection function ..............
Page 3
7 Connections and applic 7 Connections and applica a tion examples tion examples..................................299 7.1 Connections of AQ-M210 ....................299 7.2 Application example and its connections................301 7.3 Two-phase, three-wire ARON input connection ..............302 7.4 Trip circuit supervision (95) ....................303...
Page 4
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9.2.1.3 Negative sequence overcurrent/ phase current reversal/ current unbalance protection (I2>; 46/46R/46L)................... 339 9.2.1.4 Harmonic overcurrent protection (Ih>; 50H/51H/68H) ......... 339 9.2.1.5 Circuit breaker failure protection (CBFP; 50BF/52BF) ......... 340 9.2.1.6 Low-impedance or high-impedance restricted earth fault/ cable end differential protection (I0d>;...
Page 5
Nothing contained in this document shall increase the liability or extend the warranty obligations of the manufacturer Arcteq Relays Ltd. The manufacturer expressly disclaims any and all liability for any damages and/or losses caused due to a failure to comply with the instructions contained herein or caused by persons who do not fulfil the aforementioned requirements.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 1 Document information 1.1 Version 2 revision notes Table. 1.1 - 1. Version 2 revision notes Revision 2.00 Date 6.6.2019 - New more consistent look. - Improved descriptions generally in many chapters. - Improved readability of a lot of drawings and images.
- Improvements to many drawings and formula images. - Improved and updated IED user interface display images. - AQ-M210 Functions included list Added: Indicator objects, cold load pick-up, programmable control switches, mA output control, measurement recorder, non-directional undercurrent and running hour counter.
Page 9
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Changes - The first revision for AQ-M210. Revision 1.01 Date 29.8.2013 Application example for ARON input connection added to chapter 8.0. Application example for trip circuit supervision. Changes Added arc protection description and technical data.
Version: 2.04 3 General The AQ-M210 motor protection IED is a member of the AQ-200 product line. The hardware and software are modular: the hardware modules are assembled and configured according to the application's I/O requirements and the software determines the available functions. This manual describes the specific application of the AQ-M210 motor protection IED.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 4 IED user interface 4.1 Panel structure The user interface section of an AQ-200 series device is divided into two user interface sections: one for the hardware and the other for the software. You can access the software interface either through the front panel or through the AQtivate freeware software suite.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The sixteen freely configurable LEDs are located on the right side of the display. Their activation and color (green or yellow) are based on the settings the user has put in place in the software. Holding the I I (object control) button down for five seconds brings up the button test menu.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Control • Communication • Measurement • Monitoring. They are presented in the image below. The available menus vary according to the device type. Figure. 4.2.2 - 3. Main configuration menus. 4.3 General menu The General main menu is divided into two submenus: the Device info tab presents the information of the device, while the Function comments tab allows you to view all comments you have added to the...
Page 16
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Device info Figure. 4.3 - 5. Device info. Table. 4.3 - 3. Parameters and indications in the General menu. Name Range Step Default Description Device name Unitname The file name uses these fields when loading the .aqs configuration file from the AQ-200 unit.
Page 17
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: User defined 1: English 2: Finnish Changes the language of the parameter descriptions in 3: Swedish the HMI. If the language has been set to "Other" in the Language 4: Spanish 1: English...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.3 - 6. Function comments. 4.4 Protection menu General Figure. 4.4 - 7. Protection menu structure The Protection main menu includes the Stage activation submenu as well as the submenus for all the various protection functions, categorized under the following modules: "Arc protection", "Current", "Voltage", "Frequency", "Sequence"...
Page 19
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.4 - 8. Protection menu view. Stage activation You can activate the various protection stages in the Stage activation submenu (see the images below). Each protection stage and supporting function is disabled by default. When you activate one of the stages, its activated menu appears in the stage-specific submenu.
Page 20
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Example of a protection stage and its use Once a protection stage has been activated in the Stage activation submenu, you can open its own submenu. In the image series below, the user has activated three current stages. The user accesses the list of activated current stages through the "Current"...
Page 21
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Function condition: indicates the stage's condition which can be Normal, Start, Trip, or Blocked. • Expected operating time: Expected time delay from detecting a fault to tripping the breaker. This value can vary during a fault if an inverse curve time delay (IDMT) is used.
Page 22
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.4 - 13. Registers. Register menu content is not available in the HMI. It can only be accessed with AQtivate setting tool. Stored in the "Registers" section you can find both "Operation event register" and "General event register".
Page 23
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.4 - 14. I/O. The "I/O" section is divided into two subsections: "Direct output control" and "Blocking input control". In "Direct output control" you can connect the stage's signals to physical outputs, either to an output relay or an LED (START or TRIP LEDs or one of the 16 user configurable LEDs).
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.4 - 15. Events. You can mask on and mask off the protection stage related events in "Event mask". By default events are masked off. You can activate the desired events by masking them ("x"). Remember to save your maskings by confirming the changes with the check mark icon.
Page 25
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Controls enabled Figure. 4.5 - 16. Controls enabled submenu. You can activate the selected control functions in the Controls enabled submenu. By default all the control functions are disabled. All activated functions can be viewed in the Control functions submenu (see the section "Control functions"...
Page 26
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • SG loc SG local select al select: selects the local control for the different setting groups (can use digital inputs, logical inputs or outputs, RTDs, object status information as well as stage starts, trips or blocks).
Page 27
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 20. Settings section. OBJECT SET AND STATUS • L L oc ocal/R al/Remo emot t e sta e stat t us us: control access may be set to Local or Remote (Local by default; please note that when local control is enabled, the object cannot be controlled through the bus and vice versa).
Page 28
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • An object has both Open input Open input and C C lose input lose input signals which are used for indicating the status of the breaker on the HMI and in SCADA. Status can be indicated by any of the following: digital inputs, logical inputs or outputs.
Page 29
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 21. Application control section. You can connect object statuses directly to specific physical outputs in the "Signal connections" subsection ( Control → Application control ). A status can be connected to output relays, as well as to user-configurable LEDs.
Page 30
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The "Registers"section stores the function's specific fault data. There are twelve (12) registers, and each of them includes data such as opening and closing times, command types and request failures. The data included in the register depend on the protection function.
Page 31
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Each control function that has been activated is listed in the Control functions submenu (see the middle image above). This submenu includes the following sections: "Info", "Settings", "Registers", "I/O" and "Events".
Page 32
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The stage settings vary depending on which control function they are a part of. By default only one setting group of the eight available setting groups is activated. You can enable more groups in the Control →...
Page 33
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 28. I/O section. The "I/O" section is divided into two subsections: "Direct output control" and "Blocking input control". In "Direct output control" you can connect the stage's signals to physical outputs, either to an output relay or an LED (START or TRIP LEDs or one of the 16 user configurable LEDs).
Page 34
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 29. Events section. You can mask on and mask off events related to an object's stage in "Event mask". By default all events are masked off. You can activate the desired events by masking them ("x"). Please remember to save your maskings by confirming the changes with the check mark icon.
Page 35
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 31. Digital input section. All settings related to digital inputs can be found in the "Digital inputs" section. The "Digital inputs settings" subsection includes various settings for the inputs: the polarity selection determines whether the input is Normal Open (NO) or Normal Closed (NC) as well as the activation threshold voltage (16…200 V AC/DC, step 0.1 V) and release threshold voltage (10…200 V AC/DC, step 0.1 V) for each available input.
Page 36
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The "Digital outputs settings" subsection lets you select the polarity for each output; they can be either Normal Open (NO) or Normal Closed (NC). The default polarity is Normal Open. The operational delay of an output contact is approximately 5 ms.
Page 37
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 34. Device I/O matrix section. Through the "Device I/O matrix" section you can connect digital inputs, logical outputs, protection stage status signals (START, TRIP, BLOCKED, etc.), object status signals and many other binary signals to output relays, or to LEDs configured by the used.
Page 38
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 4.5 - 36. Programmable mimic indicators section Programmable mimic indicators can be placed into the mimic to display a text based on the status of a given binary signal (digital input, logical signal, status of function start/tripped/blocked signals etc.). When configuring the mimic with the AQtivate setting tool, it is possible to set a text to be shown when an input signal is ON and a separate text for when the signal is OFF.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 GOOSE inputs are mainly used for controlling purposes and in conjunction with the IEC 61850 communication protocol. There are 64 GOOSE inputs signal status bits, and their status can be either 0 or 1.
Page 40
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Connections Figure. 4.6 - 38. View of the Connections submenu. The Connections submenu offers the following bits of information and settings: ETHERNET ETHERNET This section defines the IP settings for the ethernet port in the back panel of the unit. •...
Page 41
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protocols Figure. 4.6 - 39. View of the Protocols submenu. The Protocols submenu offers access to the various communication protocol configuration menus. Some of the communication protocols use serial communication and some use Ethernet communication.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 4.7 Measurement menu Figure. 4.7 - 40. Measurement section. The Measurement menu includes the following submenus: Transformers , Frequency , Current measurement , Voltage measurement , Power and energy measurement , Impedance calculations , and Phasors .
Page 43
A A Q Q -M210 -M210 Instruction manual Version: 2.04 CT module Figure. 4.7 - 42. CT module section. The three main sections ("Phase CT scaling", "Residual I01 CT scaling" and "Residual I02 CT scaling") determine the ratio of the used transformers. Additionally, the nominal values are also determined in the CT module submenu.
Page 44
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Frequency measurements use the fixed sampling mode as the default, and "System nominal frequency" should be set to the desired level. When "Sampling mode" is set to "Tracking", the device uses the measured frequency value as the system nominal frequency.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Phasors Figure. 4.7 - 45. Phasors submenu. The Phasors submenu holds the vector displays for voltages and currents, as well as the various calculated components the IED may have (e.g. power, impedance). Phasors are helpful when solving incorrect wiring issues.
Page 46
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Monitors enabled Figure. 4.8 - 47. Monitors enabled submenu. You can activate the selected monitor functions in the Monitors enabled submenu. By default all the control functions are disabled. All activated functions can be viewed in the Monitor functions submenu (see the section "Monitor functions"...
Page 47
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Disturbance recorder Figure. 4.8 - 49. Disturbance recorder settings. The Disturbance recorder submenu has the following settings: • "Recorder enabled" enables or disables the recorder. • "Recorder status" indicates the status of the recorder. •...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Enabling "Auto. get recordings" allows the device to automatically upload recordings to the designated FTP folder (which, in turn, allows any FTP client to read the recordings from the IED's memory).
Page 49
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Super user (***) • Configurator (**) • Operator (*) • User ( - ) You can set a new password for a user level by selecting the key icon next to the user level's name. After this you can lock the user level by pressing the R R e e t t urn urn key while the lock is selected.
Page 50
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Configurator: Can change most settings such as basic protection pick-up levels or time delays, breaker control functions, signal descriptions etc. and can operate breakers and other equipment. • Super user: Can change any setting and can operate breakers and other equipment. NOTE! Any user level with a password automatically locks itself after half an hour (30 minutes) of inactivity.
Instruction manual Version: 2.04 5 Functions 5.1 Functions included in AQ-M210 The AQ-M210 motor protection relay includes the following functions as well as the number of stages for those functions. Table. 5.1 - 4. Protection functions of AQ-M210. Name (number...
ANSI Description CLPU CLPU Cold load pick-up Programmable control switch mA output Milliampere output control Table. 5.1 - 6. Monitoring functions of AQ-M210. Name ANSI Description Current transformer supervision Disturbance recorder Circuit breaker wear monitor Total harmonic distortion Running hour counter...
Page 53
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.2.1 - 51. Current measurement terminology P P RI: RI: The primary current, i.e. the current which flows in the primary circuit and through the primary side of the current transformer. SEC: SEC: The secondary current, i.e.
Page 54
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The relay calculates the scaling factors based on the set values of the CT primary, the CT secondary and the nominal current settings. The relay measures the secondary current, the current output from the current transformer installed into application's primary circuit.
Page 55
A A Q Q -M210 -M210 Instruction manual Version: 2.04 - the phase currents are connected to the I01 residual via a Holmgren connection - the starpoint of the phase current CT's secondary current is towards the line Phase CT scaling Next, to scale the current to per-unit values, we have to select whether the basis of the phase CT scaling is the protected object's nominal current or the CT primary value.
Page 56
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Once the measurement scaling is tied to the protected object's nominal current, the user must set the appropriate input for the "Nominal current In" setting. One can now see the differences between the two scaling options (CT nominal vs.
Page 57
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.2.1 - 57. Scalings display (based on the CT nominal). Figure. 5.2.1 - 58. Scalings display (based on the protected object's nominal current). As the images above show, the scaling selection does not affect how primary and secondary currents are displayed (as actual values).
Page 58
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.2.1 - 59. Connections of ZCT scaling. Troubleshooting When the measured current values differ from the expected current values, the following table offers possible solutions for the problems. NOTE! If you work with energized CTs, extreme caution needs to be taken when checking the connections! An opened CT secondary circuit may generate dangerously high voltages.
Page 59
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Problem Solution The phase currents are connected to the measurement module but the order or polarity of one or all phases is incorrect. In relay settings, go to Measurement → Phasors and check the "Phase current vectors"...
Page 60
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.2.1 - 60. Common phase polarity problems. The following image presents the most common problems with network rotation (mix phases). These problems can be difficult to find because the measurement result is always the same in the relay. If two phases are mixed together, the network rotation always follows the pattern IL1-IL3-IL2 and the measured negative sequence current is therefore always 1.00 (in.
Page 61
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.2.1 - 61. Common network rotation (mixed phases) problems. Settings Table. 5.2.1 - 8. Settings of the Phase CT scaling. Name Unit Range Step Default Description 0: CT Scale 0: CT The selection of the reference used in the relay's per-unit system nom p.u.
Page 62
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.2.1 - 9. Settings of the Residual I01 CT scaling. Name Unit Range Step Default Description I01 CT 0.2…25 000 0.00001 100 The rated primary current of the current transformer. primary I01 CT 0.1…10.000 0.00001 1...
Page 63
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.2.1 - 13. Secondary phase current measurements. Name Unit Range Step Description Secondary phase The primary RMS current measurement from each of the phase current ILx 0.00…300.00 0.01 current channels. ("Sec.Pha.curr.ILx") Secondary phase current ILx TRMS...
Page 64
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.2.1 - 18. Residual phase angle measurements. Name Unit Range Step Description Residual current angle The residual current angle measurement from the I01 or I02 current 0.00…360.00 0.01 input. ("Res.curr.angle I0x") calc.I0 Pha.angle 0.00…360.00 0.01...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.2.1 - 23. Harmonic current measurements. Name Range Step Default Description Harmonics 0: Percent calculation values Defines whether the harmonics are calculated as percentage or ("Harm Abs.or Percent absolute values. Absolute Perc.") 0: Per unit...
Page 66
FFT calculation always has a whole power cycle in the buffer. The measurement accuracy is further improved by Arcteq's patented calibration algorithms that calibrate the analog channels against eight (8) system frequency points for both magnitude and angle.
Page 67
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: No trackable channels 1: Reference 1 trackable 2: Reference 2 trackable Defines the frequency tracker quality. If the measured current 3: References 1 & Frequency (or voltage) amplitude is below the threshold, the channel 2 trackable...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: Not measurable 1: Avg Ref 1 2: Avg Ref 2 3: Avg Ref 3 measurement 4: Track Ref 1 Displays which reference is used for frequency measurement. from 5: Track Ref 2 6: Track Ref 3...
Page 69
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The protection function is run in a completely digital environment with a protection CPU microprocessor which also processes the analog signals transformed into the digital form.
Page 70
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.1 - 62. Principle diagram of the protection relay platform. In the following chapters the common functionalities of protection functions are described. If a protection function deviates from this basic structure, the difference is described in the corresponding chapter of the manual.
Page 71
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.1 - 64. Measurement range in relation to the nominal current. The I magnitude refers to the user set nominal current which can range from 0.2…10 A, typically 0.2 A, 1A or 5 A.
Page 72
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Inverse definite minimum time (IDMT): activates the trip signal after a time which is in relation to the set pick-up value X and the measured value X (dependent time characteristics). Both IEC and IEEE/ANSI standard characteristics as well as user settable parameters are available for the IDMT operation.
Page 73
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Selects the IEC standard delay characteristics. The options include the following: Normally Inverse ("NI"), 0: NI Extremely Inverse ("EI"), Very Inverse ("VI") and Long Time Inverse Delay 1: EI ("LTI") characteristics.
Page 74
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.1 - 66. Inverse operating time formulas for IEC and IEEE standards. Non-standard delay characteristics In addition to the previously mentioned delay characteristics, some functions also have delay characteristics that deviate from the IEC or IEEE standards. These functions are the following: •...
Page 75
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.1 - 28. Setting parameters for reset time characteristics. Name Name Range Range St Step Defa fault ult Descrip Description tion Delayed Resetting characteristics selection (either time-delayed or instant) after 0: No pick-up 1: Yes...
Page 76
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.1 - 68. Delayed pick-up release, delay counter is reset at signal drop-off. Figure. 5.3.1 - 69. Delayed pick-up release, delay counter value is held during the release time.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.1 - 70. Delayed pick-up release, delay counter value is decreasing during the release time. The resetting characteristics can be set according to the application. The default setting is delayed 60 ms and the time calculation is held during the release time.
Page 78
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The outputs of the function are the START, TRIP and BLOCKED signals. The non- directional overcurrent function uses a total of eight (8) separate setting groups which can be selected from one common source.
Page 79
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Measured input The function block uses analog current measurement values. However, when the peak-to-peak mode is selected for the function's "Measured magnitude" setting , the values are taken directly from the samples.
Page 80
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.2 - 31. Pick-up settings. Name Description Range Step Default Pick-up setting 0.10…50.00×I 0.01×I 1.20×I The pick-up activation of the function is not directly equal to the START signal generation of the function.
Page 81
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.2 - 33. Internal inrush harmonic blocking settings. Name Range Step Default Description Inrush harmonic blocking (internal- 0: No Enables and disables the 2 harmonic 0: No only trip) 1: Yes blocking.
Page 82
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 1291 NOC1 Phase C Start OFF 1292 NOC1 Phase A Trip ON 1293 NOC1 Phase A Trip OFF 1294 NOC1 Phase B Trip ON 1295 NOC1...
Page 83
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 1421 NOC3 Phase A Trip OFF 1422 NOC3 Phase B Trip ON 1423 NOC3 Phase B Trip OFF 1424 NOC3 Phase C Trip ON 1425 NOC3...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 5.3.3 Non-directional earth fault protection (I0>; 50N/51N) The non-directional earth fault function is used for instant and time-delayed earth fault protection. The number of stages in the function depend on the device model. The operating characteristics are based on the selected neutral current magnitudes which the function measures constantly.
Page 85
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.3 - 72. Simplified function block diagram of the I0> fucntion. Measured input The function block uses analog current measurement values. The user can select the monitored magnitude to be equal either to RMS values, to TRMS values, or to peak-to-peak values. TRMS mode uses values from the whole harmonic spectrum of 32 components.
Page 86
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description Range Default 1: RMS Measured Defines which available measured magnitude is used by the function. This 2: TRMS 1: RMS magnitude parameter is available when "Input selection" has been set to "I01" or "I02". 3: Peak- to-peak 1: I01...
Page 87
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Description meas at the 0.00...1250.00 0.01 The ratio between the measured current and the pick-up value. moment Function blocking The block signal is checked in the beginning of each program cycle. The blocking signal is received from the blocking matrix in the function's dedicated input.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 1666 NEF1 Trip ON 1667 NEF1 Trip OFF 1668 NEF1 Block ON 1669 NEF1 Block OFF 1728 NEF2 Start ON 1729 NEF2 Start OFF...
Page 89
A A Q Q -M210 -M210 Instruction manual Version: 2.04 There are two possible operating modes available: the I2 mode monitors the negative sequence current, while the I2/I1 mode monitors the ratio between the negative sequence current and the positive sequence current. The relay calculates the symmetrical component magnitudes in use from the phase current inputs I and I .
Page 90
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Measured input The function block uses analog current measurement values and always uses calculated positive and negative sequence currents. In the broken conductor mode (I2/I1) the function also uses the RMS values of all phase currents to check the minimum current.
Page 91
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Read-only parameters The relay's Info page displays useful, real-time information on the state of the protection function. It is accessed either through the relay's HMI display, or through the setting tool software when it is connected to the relay and its Live Edit mode is active.
Page 92
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • t = Operating time • I = Calculated negative sequence 2meas • k = Constant k value (user settable delay multiplier) • I = Pick-up setting of the function Figure.
Page 93
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.4 - 46. Event codes. Event Number Event channel Event block name Event Code Description 2048 CUB1 Start ON 2049 CUB1 Start OFF 2050 CUB1 Trip ON 2051 CUB1 Trip OFF 2052 CUB1...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 5.3.5 Harmonic overcurrent protection (Ih>; 50H/51H/68H) The harmonic overcurrent function is used for non-directional instant and time-delayed overcurrent detection and clearing. The number of stages in the function depends on the relay model. The function constantly measures the selected harmonic component of the selected measurement channels, the value being either absolute value or relative to the RMS value.
Page 95
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.5 - 75. Simplified function block diagram of the Ih> function. Measured input The function block uses analog current measurement values from phase or residual currents. Each measurement input of the function block uses RMS values and harmonic components of the selected current input.
Page 96
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Time base The magnitudes (RMS) of phase L2 (B) current components: - Fundamental harmonic harmonic harmonic harmonic harmonic IL2FFT 5 ms harmonic harmonic - 11 harmonic - 13 harmonic - 15 harmonic...
Page 97
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Time base The magnitudes (RMS) of residual I0 current components: - Fundamental harmonic harmonic harmonic harmonic harmonic I02FFT 5 ms harmonic harmonic - 11 harmonic - 13 harmonic - 15 harmonic - 17...
Page 98
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description IL1/IL2/ Measurement IL1/IL2/ Selection of the measurement input (either phase current or residual current). input Each function stage provides these same settings. Multiple stages of the function can be set to operate independently of each other.
Page 99
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Function blocking The block signal is checked in the beginning of each program cycle. The blocking signal is received from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when the pick-up element activates, a START signal is generated and the function proceeds to the time characteristics calculation.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 2496 HOC3 Start ON 2497 HOC3 Start OFF 2498 HOC3 Trip ON 2499 HOC3 Trip OFF 2500 HOC3 Block ON 2501 HOC3 Block OFF...
Page 101
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The operational logic consists of the following: • input magnitude processing • input magnitude selection • threshold comparator • block signal check • time delay characteristics • output processing. The inputs of the function are the following: •...
Page 102
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Time base IL3RMS RMS measurement of phase L3 (C) current I01RMS RMS measurement of residual input I01 I02RMS RMS measurement of residual input I02 I0Calc Calculated residual current from the phase current inputs DOIN Monitors digital output relay status DIIN...
Page 103
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: Current only 1: DO only 2: Signals only 3: Current and DO 4: Current or 5: Current and signals Selects the operating mode. The mode can be dependent on current Actmode 6: Current or Current...
Page 104
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Operating time characteristics The operating timers’ behavior during a function can be set depending on the application. The same pick-up signal starts both timers. When retrip is used the time grading should be set as follows: the sum of specific times (i.e.
Page 105
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Trip, Retrip and CBFP in the device configuration Figure. 5.3.6 - 77. Wiring diagram when Trip, Retrip and CBFP are configured to the device. The retrip functionality can be used in applications whose circuit breaker has a retrip or a redundant trip coil available.
Page 106
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 78. Retrip and CBFP when "Current" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, the current-based protection is activated and the counters for RETRIP and CBFP start calculating the set operating time. The tripping of the primary protection stage is not monitored in this configuration.
Page 107
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 79. Retrip and CBFP when "Current and DO" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, the current-based protection is activated.
Page 108
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 80. Retrip and CBFP when "Current or DO" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, or the TRIP signal reaches the primary protection stage, the function starts counting down towards the RETRIP and CBFP signals.
Page 109
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Trip and CBFP in the device configuration Figure. 5.3.6 - 81. Wiring diagram when Trip and CBFP are configured to the device. Probably the most common application is when the device's trip output controls the circuit breaker trip coil, while one dedicated CBFP contact controls the CBFP function.
Page 110
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 82. CBFP when "Current" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, the current-based protection is activated and the counter for CBFP starts calculating the set operating time. The tripping of the primary protection stage is not monitored in this configuration.
Page 111
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 83. CBFP when "Current and DO" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, the current-based protection is activated. At the same time, the counter for CBFP is halted until the monitored output contact is controlled (that is, until the primary protection operates).
Page 112
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.6 - 84. CBFP when "Current or DO" is the selected criterion. When the current threshold setting of I and/or I0 is exceeded, or the TRIP signal reaches the primary protection stage, the function starts counting down towards the CBFP signal.
Page 113
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Device configuration as a dedicated CBFP unit Figure. 5.3.6 - 85. Wiring diagram when the device is configured as a dedicated CBFP unit.
Page 114
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Some applications require a dedicated circuit breaker protection unit. When the CBFP function is configured to operate with a digital input signal, it can be used in these applications. When a device is used for this purpose, the tripping signal is wired to the device's digital input and the device's own TRIP signal is used only for the CBFP purpose.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 2820 CBF1 CBFP ON 2821 CBF1 CBFP OFF 2822 CBF1 Block ON 2823 CBF1 Block OFF 2824 CBF1 DO monitor ON 2825 CBF1 DO monitor OFF...
Page 116
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • differential characteristic comparator • block signal check • output processing. The inputs for the function are the following: • setting parameters • measured and pre-processed current magnitudes. The function's output signals can be used for direct I/O controlling and user logic programming. The function generates general time-stamped ON/OFF events to the common event buffer from each of the two (2) output signals.
Page 117
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Time base IL3 Ang Angle of phase L3 (C) current I01 Ang Angle of residual input I01 I02 Ang Angle of residual input I02 The selection of the used AI channel is made with a setting parameter. General settings The following general settings define the general behavior of the function.
Page 118
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The pick-up settings can be selected via setting groups. The pick-up activation of the function is not directly equal to the TRIP signal generation of the function. The TRIP signal is allowed if the blocking condition is not active.
Page 119
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Read-only parameters The relay's Info page displays useful, real-time information on the state of the protection function. It is accessed either through the relay's HMI display, or through the setting tool software when it is connected to the relay and its Live Edit mode is active.
Page 120
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.7 - 92. Cable end differential with natural unbalance in the phase current measurement. When calculating residual current from the phase currents, the natural unbalance can be around 10 % while the used CTs are still within the promised 5P class (which is probably the most common CT accuracy class).
Page 121
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.7 - 93. Cable end differential when a fault occurs. If a starting fault occurs in the cable end, the CED mode catches the difference between the ingoing and the outgoing residual currents. The resulting signal can be used for alarming or tripping purposes for the feeder with the failing cable end.
Page 122
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.7 - 94. Restricted earth fault outside a Y winding transformer. If the fault is located inside of the transformer and thus inside of the protection area, the function catches the fault with high sensitivity.
Page 123
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.7 - 95. Restricted earth fault inside a Y winding transformer. Events and registers The restricted earth fault function (abbreviated "REF" in event block names) generates events and registers from the status changes in TRIP-activated and BLOCKED signals. The user can select which event messages are stored in the main event buffer: ON, OFF, or both.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.7 - 65. Event codes. Event number Event channel Event block name Event code Description 4224 REF1 I0d> (87N) Trip ON 4225 REF1 I0d> (87N) Trip OFF 4226 REF1 I0d>...
Page 125
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.8 - 96. Simplified function block diagram of the motor status monitoring function. The function's outputs are dependent on the motor data the user has set. The following two diagram present the function's outputs in various situations.
Page 126
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The Mo Mot t or st or stopped opped signal is activated when the current is below the “No load current” limit for longer than 10 ms. When the current increases from this status to above the “Start detect current” setting, a start of the motor is detected and the Mo Mot t or star or starting...
Page 127
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.8 - 99. Blocking application in the relay configuration. In the example above, problems may arise if, during the start-up of a motor, a short-circuit fault occurs while the overcurrent stage is blocked. This may make the fault clearing take longer as the relay still considers the situation part of starting.
Page 128
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Picture 2 (bottom left). The LOGIC_OUT1 signal is connected to the I> blocking input (NOC1, first stage overcurrent) function to block the stage in motor start-ups. Picture 3 (right). The high overcurrent detection signal can also be directly connected to the output relay.
Page 129
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal overload The motor's locked rotor current with the nominal Nominal protection voltage. This setting is used for automatic curve 0.1…40.0xI 0.1xI 6.0xI...
Page 130
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal Maximum locked rotor current of the motor. This overload setting defines the current limit which is maximum protection current for the motor to draw in locked rotor situation Max locked...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal No load 0.1...5000A 0.1A overload The motor's no load current in amperes. current < A protection (Tm>;...
Page 132
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Frequent start protection (N>; 48) - Machine The safe stall time when the motor is hot. This setting thermal Safe stall time value is used for the hot thermal stall curve selection in...
Page 133
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: Not active The Mo Mot t or stalled or stalled signal is active when the measured current exceeds the "Max Motor 0: Not stalled active overload current"...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The function registers its operation into the last twelve (12) time-stamped registers. The table below presents the structure of the function's register content. Table. 5.3.8 - 70. Register content. Event Date and time L1 current L2 current...
Page 135
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 101. Simplified function block diagram of the motor start/ locked rotor monitoring function. A recommended setup for this function is for the I t mode to be used in starting; if motor running/ locked rotor situations at times occur in some parts of the duty cycle during normal use, the locked rotor protection must also be applied.
Page 136
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 102. Outputs in normal motor start, no speed switch. The Ist> function should be set so that it takes into account the application's required starting time for a normal motor start.
Page 137
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 103. Outputs when motor starting takes too long, no speed switch. There are many reasons why the motor starting takes too long. These include problems in the drive or in the application.
Page 138
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 104. Outputs in long motor starting, with a speed switch. The speed switch is also useful when the motor start is naturally very long due to a high accelerating mass.
Page 139
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 105. Outputs when motor starting takes too long, with a speed switch. If the starting condition lasts longer than the safe stall time that has been set, the function trips the breaker.
Page 140
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.9 - 106. Motor stall monitoring. Settings and signals The settings of the motor start/locked rotor monitoring function are mostly shared with other motor protection functions in the device's motor module. The following table shows the motor data settings of the Ist>...
Page 141
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal overload protection (Tm>; 49M) Motor In - Motor start 0.1...5000A 0.1A The motor's nominal current in amperes. monitoring (Ist>;...
Page 142
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal overload protection The motor's minimum locked rotor current. This setting locked (Tm>; 49M) defines the current limit for when this current is exceeded 0.1…40.0xI 0.1xI 3.5xI...
Page 143
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal overload The motor's maximum overload current. Exceeding this protection setting stalls the motor. This setting defines when the thermal (Tm>;...
Page 144
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status monitoring - Frequent start protection (N>; - Machine thermal The safe stall time when the motor is hot. This setting value is Safe stall overload used for the hot thermal stall curve selection in automatic...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Events and registers The motor start/locked rotor monitoring function (abbreviated "LCR" in event block names) generates events from the detected motor status. The data register is available, based on the changes in the events.
Page 146
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The frequent start protection function in a motor protection module operates with the motor status monitoring function and follows the motor data set there. Motor starting is monitored internally (MST signal out) in the N>...
Page 147
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.10 - 108. Updating the function's start counter (image not to scale with regard to time). In the example above the motor is allowed four starts within a specific time frame ( t ): the motor is started four times and the counter is updated accordingly.
Page 148
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.10 - 109. Updating the starts counter when thermal hot and cold status taken into consideration. If a motor's thermal load is monitored, a correct number of starts can be allowed for the motor when the device can update the available starts online and precisely monitor the motor's status.
Page 149
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.10 - 75. Motor data settings. Protection Name Range Step Default Description functions - Motor status monitoring - Frequent start protection Setting the motor's thermal limit in a hot or a cold situation. When (N>;...
Page 150
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Protection Name Range Step Default Description functions - Motor status Starts monitoring when 1…100 - Frequent The number of allowed starts per x hours for a hot motor. start protection (N>;...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.10 - 78. Register content. Time since last Date and time Event code Inhibit time on Start count start dd.mm.yyyy 3584-3589 If on, it shows how long the Time elapsed from last Starts used at the hh:mm:ss.mss Descr.
Page 152
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.11 - 110. Simplified function block diagram of the I< function. Measured input The function block uses analog current measurement values and uses RMS phase current measurements. A -20 ms averaged value of the selected magnitude is used for pre-fault data registering.
Page 153
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.11 - 80. Motor data settings. Protection Name Range Step Default Description functions - Motor status monitoring - Machine thermal overload protection (Tm>; 49M) The motor's nominal current scaled to per unit. If the user selects Motor In 0.1...
Page 154
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Operating time characteristics for trip and reset This function supports definite time delay (DT). For detailed information on these delay types please refer to the chapter "General properties of a protection function" and its section "Operating time characteristics for trip and reset".
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 3843 NUC1 Trip OFF 3844 NUC1 Block ON 3845 NUC1 Block OFF The function registers its operation into the last twelve (12) time-stamped registers. The register of the function records the ON event process data for START, TRIP or BLOCKED.
Page 156
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.12 - 111. Simplified function block diagram of the Im> function. Measured input The function block uses analog current measurement values and uses RMS phase current measurements. A -20 ms averaged value of the selected magnitude is used for pre-fault data registering.
Page 157
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.12 - 86. Motor data settings. Name Range Step Default Prot.funcs. Description - Motor status monitoring - Machine thermal overload protection (Tm>; 49M) The motor's nominal current scaled to per unit. If the user Motor In 0.1...
Page 158
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - Motor status monitoring - Machine thermal overload The motor's minimum locked rotor current. This setting defines locked protection the current limit for when this current is exceeded while the 0.1…40.0xI 0.1xI 3.5xI...
Page 159
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - Motor status monitoring - Machine thermal The motor's maximum overload current. Exceeding this setting overload stalls the motor. This setting defines when the thermal replica protection 0.1…40.0xI 0.1xI...
Page 160
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - Motor status monitoring - Frequent start protection The safe stall time when the motor is hot. This setting value is (N>; 48) Safe stall used for the hot thermal stall curve selection in automatic 0.1…600.0s 0.1s...
Page 161
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Function blocking The block signal is checked in the beginning of each program cycle. The blocking signal is received from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when the pick-up element activates, a START signal is generated and the function proceeds to the time characteristics calculation.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 5.3.13 Machine thermal overload protection (TM>; 49M) The thermal overload protection function for machines is used for the thermal capacity monitoring and protection of electric machines like synchronous and asynchronous motors and generators. This function can also be used for any applications with single or multiple time constansts, such as inductor chokes, certain types of transformers and any other static units which do not have active cooling apart from cables and overhead lines.
Page 163
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 113. Short time constant thermal image calculation. Where: • θ = Thermal image status in a previous calculation cycle (the memory of the function) • I = (see below) •...
Page 164
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 114. Thermal image calculation with nominal conditions: single time constant thermal replica. The described behavior is based on the assumption that the monitored object has a homogenous body which generates and dissipates heat with a rate proportional to the temperature rise caused by the current squared.
Page 165
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • t = Measured (set) ambient temperature (can be set in ̊ C or ̊ F ) • t = Maximum temperature (can be set in ̊ C or ̊ F ) for the protected object •...
Page 166
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 116. Ambient temperature coefficient calculation (linear approximation, indefinite points). As mentioned in the previous diagram, the reference temperature for electric machines usually is +40 ̊ C ; this gives a correction coefficient of 1.00 which can be referred to as the nominal temperature in this case.
Page 167
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 117. Factors affecting the cooling and current-carrying capacity of a cable. The current-carrying capacity of a cable mostly depends on the conductor's material and its diameter. The second most important factor is the cable's insulating material and how much it can withstand temperature.
Page 168
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • the rotor: rotates, its shaft used as a power outlet for the motor (drive end), • the stator: generates the electromagnetic field which induces into the rotor and makes it rotate (hence the name "induction motor"), •...
Page 169
A A Q Q -M210 -M210 Instruction manual Version: 2.04 When the motor is energized the stator generates a magnetic field which induces a voltage to the squirrel cage rotor. While the rotor is not yet rotating, the induced voltage and the current it causes are at maximum in the rotor.
Page 170
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Once the motor has started and is running with or without a load, the heat generation is switched between the rotor and the stator. When the rotor's rotating is within the range of the nominal slip, the magnetic fields of the rotor and the stator "cut"...
Page 171
A A Q Q -M210 -M210 Instruction manual Version: 2.04 If the motor is overloaded, the stator winding starts to heat up according to its heating time constant. If the overload is not released in time, it can lead to the melting of the stator's winding insulations which in turn leads to a short-circuit;...
Page 172
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 119. Running motor's temperature with thermal image camera. Measuring the rotor's temperature is very complicated due to its rotating nature. This is why normally there are no measurements available and why the protection of the rotor always requires a calculated thermal image.
Page 173
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 120. Measured motor temperature in heating/cooling test.
Page 174
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 121. Matching thermal replicas to the measured thermal capacity of the motor. As can be seen in the figures above, when the motor is loaded with a constant current both of the replicas (single and dual time constant) follow the motor heating quite accurately.
Page 175
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 122. Example of thermal limit curves in a motor. From motor thermal limit curves –if available– one can see the time constants for overloading as well as the safe stall times for hot and cold situations.
Page 176
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 123. Comparing single time constant thermal replica tripping curves to given motor thermal characteristics.
Page 177
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 124. Comparing dual time constant thermal replica tripping curves to given motor thermal characteristics. As the figures above have shown, with estimated time constants from the motor thermal limit curves the single time constant model underprotects the motor in the stall condition when the motor is cold.
Page 178
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 125. Thermal tripping curves with single time constant, pre-load 0% (cold). Figure. 5.3.13 - 126. Thermal tripping curves with single time constant, pre-load 90% (hot).
Page 179
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 127. Thermal tripping curves with dual dynamic time constants and correction factor, pre-load 0% (cold) Figure. 5.3.13 - 128. Thermal tripping curves with dual dynamic time constants and correction factor, pre-load 90% (hot).
Page 180
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 129. Thermal cooling curves, single cooling time constant. Figure. 5.3.13 - 130. Thermal cooling curves, dynamic dual time constant.
Page 181
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 131. Thermal cooling curves, dynamic triple time constant (motor is running without load in the first part with dedicated time constant). Figure. 5.3.13 - 132. NPS-biased thermal trip curves with k value of 1.
Page 182
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 133. NPS-biased thermal trip curves with k value of 3. Figure. 5.3.13 - 134. NPS-biased thermal trip curves with k value of 7.
Page 183
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 135. NPS-biased thermal trip curves with k value of 10. Function inputs and outputs The blocking signal and the setting group selection control the operating characteristics of the function during normal operation, i.e.
Page 184
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.13 - 136. Simplified function block diagram of the TM> function. Measured input The function block uses analog phase current measurement values. The function block uses TRMS values from the whole harmonic specter of 32 components. Table.
Page 185
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.13 - 95. Settings of the motor status monitoring function and how they are shared by other protection functions. Name Range Step Default Prot.funcs. Description - motor status monitoring - machine thermal overload...
Page 186
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - motor status monitoring - machine thermal overload protection The motor's minimum locked rotor current. This setting locked (TM>; 49M) defines the current limit for when this current is exceeded 0.1…40.0xI 0.1xI 3.5xI...
Page 187
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - motor status monitoring - machine thermal overload The motor's maximum overload current. Exceeding this protection setting stalls the motor. This setting defines when the (TM>;...
Page 188
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Prot.funcs. Description - motor status monitoring - frequent start protection (N>) Setting the thermal limit for a hot motor and a cold motor. - machine When this setting value is not exceeded while a locked thermal rotor situation occurs, the function uses a cold stall curve overload...
Page 189
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description The selection of whether the thermal replica uses single or multiple heating Time 0: Single and cooling time constants. If "Single" is selected, only the time constants 0: Single constants 1: Multiple...
Page 190
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description The correction factor between the currently used long and short time constants. With this setting the heating and cooling calculations can be fine-tuned. A setting value of 0.5 means that 50 % of the heating or cooling Wf factor calculation is based on the long time constant and another 50 % is based for L/S T...
Page 191
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description The temperature reference setting. The manufacturer's temperature Temp. presumptions apply and the thermal correction factor is 1.00 (rated reference -60…500 temperature). For underground cables the set value for this is usually 15 ̊ C 15 deg (tref) and for cables in the air it is usually 25 ̊...
Page 192
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Enable TM> 0: Disabled Disabled Enabling/disabling the INHIBIT signal and the IO. Rest 1: Enabled Inhibit TM> Inhibit 0.0…150.0 % 80 % INHIBIT activation threshold. level TM>...
Page 193
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Description 0: Stopped 1: Stalled The function's thermal image status. When the measured current is below 1 % of the nominal 2: Just current, the status "Light/No load" is shown. When the measured current is below the trip limit, Stopped the status "Load normal"...
Page 194
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Description / values - TM> Trip delay remaining: the time to reach 100% theta - TM> Trip time to rel.: the time to reach theta while staying below the trip limit during cooling - TM>...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description Event code 4352-4361 Descr. Time to reach 100 % theta seconds Ref. T current Active meas. current T at a given moment Max. temp. rise allowed degrees Temp. rise at a given moment degrees Hot spot estimate degrees...
Page 196
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Setting up an RTD measurement, the user first needs to set the measurement module to scan the wanted RTD elements. A multitude of Modbus-based modules are supported. Communication requires bitrate, databits, parity, stopbits and Modbus I/O protocol to be set; this is done at Communication → Connections .
Page 197
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Settings Table. 5.3.14 - 104. Function settings for Channel x (Sx). Name Range Step Default Description 0: No Enables/disables the selecion of sensor S1...S16 enable 0: No 1: Yes measurements and alarms. 0: InternalRTD1 Selects the measurement module.
Page 198
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The events triggered by the function are recorded with a time stamp and with process data values. The function registers its operation into the last twelve (12) time-stamped registers. Table. 5.3.14 - 105. Event codes. Event number Event channel Event block name...
Page 199
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 4451 RTD1 S9 Alarm2 OFF 4452 RTD1 S10 Alarm1 ON 4453 RTD1 S10 Alarm1 OFF 4454 RTD1 S10 Alarm2 ON 4455 RTD1 S10 Alarm2 OFF...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 4489 RTD2 S5 Meas Invalid 4490 RTD2 S6 Meas Ok 4491 RTD2 S6 Meas Invalid 4492 RTD2 S7 Meas Ok 4493 RTD2 S7 Meas Invalid...
Page 201
The arc protection card has four (4) sensor channels, and up to three (3) arc point sensors can be connected to each channel. The sensor channels support Arcteq AQ-01 (light sensing) and AQ-02 (pressure and light sensing) units. Optionally, the protection function can also be applied with a phase current or a residual current condition: the function trips only if the light and overcurrent conditions are met.
Page 202
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Outputs Activation condition I/I0 Arc> Ph. curr. START The measured phase current or the residual current is over the set limit. I/I0 Arc> Res. curr. START I/I0 Arc> Ph. curr. BLOCKED The phase current or the residual current measurement is blocked by an input.
Page 203
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.15 - 139. Scheme IA1 (with AQ-101 arc protection relays). To set the zones for the AQ-2xx models sensor channels start by enabling the protected zones (in this case, Zones 1 and 2). Then define which sensor channels are sensing which zones (in this case, sensor channels S1 and S2 are protecting Zone 1).
Page 204
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.3.15 - 140. Scheme IA1 (with AQ-200 protection relays). The settings for the relay supervising the incoming feeder are the same as in the first example. The relays supervising the busbar and the outgoing feeder, however, have a different setting. Both Zones 2 and 3 need to be enabled as there are sensors connected to both Zone 2 and 3 starts.
Page 205
A A Q Q -M210 -M210 Instruction manual Version: 2.04 General settings The following general settings define the general behavior of the function. These settings are static i.e. it is not possible to change them by editing the setting group. Table.
Page 206
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description Range Step Default Zone1/2/3/4 Light 1 0: Disabled Light detected in sensor channel 1 trips the zone. Enabled 1: Enabled Disabled Zone1/2/3/4 Light 2 0: Disabled Light detected in sensor channel 2 trips the zone. Enabled 1: Enabled Disabled...
Page 207
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Function blocking The block signal is checked in the beginning of each program cycle. The blocking signal is received from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when the pick-up element activates, a TRIP signal is generated.
Page 208
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 4755 ARC1 Phase current Start OFF 4756 ARC1 Residual current Blocked ON 4757 ARC1 Residual current Blocked OFF 4758 ARC1 Residual current Start ON 4759 ARC1...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.3.15 - 111. Register content. Event Phase A Phase B Phase C Residual Active Date and time Used SG code current current current current sensors dd.mm.yyyy 4736-4787 Trip -20ms Trip -20ms Trip -20ms Trip -20ms...
Page 210
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Setting up programmable stages Programmable stages can be set to follow one, two or three analog measurements with the PSx >/< Measurement setting parameter. The user must choose a measurement signal value to be compared to the set value, and possibly also set a scaling for the signal.
Page 211
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Mode Description Either of the chosen signals has to fulfill the pick-up condition. Both signals have their own pick-up 4: Mag1 OR Mag2 setting. Both of the chosen signals have to fulfill the pick-up condition. Both signals have their own pick-up 5: Mag1 AND Mag2 setting.
Page 212
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Mode Description 4: Mag1 AND Mag2 AND All of the signals need to fulfill the pick-up condition. Each signal has their own pick-up Mag3 setting. 5: (Mag1 OR Mag2) AND Signals 1 OR 2 AND 3 need to fulfill the pick-up condition.
Page 213
A A Q Q -M210 -M210 Instruction manual Version: 2.04 When setting the comparators, the user must first choose a comparator mode. The following modes are available: Mode Description 0: Over G G r r ea eat t er than er than.
Page 214
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Description IL1 15 IL1 15 harmonic value (in p.u.) IL1 17 IL1 17 harmonic value (in p.u.) IL1 19 IL1 19 harmonic value (in p.u.) Description IL2 ff (p.u.) IL2 Fundamental frequency RMS value (in p.u.) IL2 2 IL2 2 harmonic value (in p.u.)
Page 215
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Description I01 5 I01 5 harmonic value (in p.u.) I01 7 I01 7 harmonic value (in p.u.) I01 9 I01 9 harmonic value (in p.u.) I01 11 I01 11 harmonic value (in p.u.) I01 13 I01 13 harmonic value (in p.u.)
Page 216
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Description I02 Ang I02 angle of current I0CALC Ang Angle of calculated residual current I1 Ang Angle of positive sequence current I2 Ang Angle of negative sequence current I01ResP I01 primary current of a current-resistive component I01CapP I01 primary current of a current-capacitive component I01ResS...
Page 217
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description S3PH Three-phase apparent power S (kVA) P3PH Three-phase active power P (kW) Q3PH Three-phase reactive power Q (kvar) tanfi3PH Three-phase active power direction cosfi3PH Three-phase reactive power direction Apparent power L1 S (kVA) Active power L1 P (kW) Reactive power L1 Q (kVar)
Page 218
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description Z12Sec Impedance Z L12 secondary (Ω) Z23Sec Impedance Z L23 secondary (Ω) Z31Sec Impedance Z L31 secondary (Ω) Z12Angle Impedance Z L12 angle Z23Angle Impedance Z L23 angle Z31Angle Impedance Z L31 angle RL1Pri...
Page 219
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description GL3Pri Conductance G L3 primary (mS) BL3Pri Susceptance B L3 primary (mS) GL1Sec Conductance G L1 secondary (mS) BL1Sec Susceptance B L1 secondary (mS) GL2Sec Conductance G L2 secondary (mS) BL2Sec Susceptance B L2 secondary (mS) GL3Sec...
Page 220
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The outputs of the function are the START, TRIP and BLOCKED signals. The overvoltage function uses a total of eight (8) separate setting groups which can be selected from one common source. The function can operate on instant or time-delayed mode.
Page 221
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The blocking of the function causes an HMI display event and a time-stamped blocking event with information of the startup values of the selected signal and its fault type to be issued. The blocking signal can also be tested in the commissioning phase by a software switch signal when the relay's testing mode "Enable stage forcing"...
Page 222
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 8601 PGS1 PS5 >/< Start OFF 8602 PGS1 PS5 >/< Trip ON 8603 PGS1 PS5 >/< Trip OFF 8604 PGS1 PS5 >/<...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The function registers its operation into the last twelve (12) time-stamped registers. The register of the function records the ON event process data for START, TRIP or BLOCKED. The table below presents the structure of the function's register content.
Page 224
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Setting groups can be controlled either by pulses or by signal levels. The setting group controller block gives setting groups priority values for situations when more than one setting group is controlled at the same time: the request from a higher-priority setting group is taken into use.
Page 225
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: SG1 SG1...2 SG1...3 SG1...4 Used setting The selection of the activated setting groups in the application. Newly-enabled 0: SG1 groups setting groups use default parameter values. SG1...5 SG1...6 SG1...7...
Page 226
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Example applications for setting group control This chapter presents some of the most common applications for setting group changing requirements. A Petersen coil compensated network usually uses directional sensitive earth fault protection. The user needs to control its characteristics between varmetric and wattmetric;...
Page 227
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.4.1 - 144. Setting group control – two-wire connection from Petersen coil status.
Page 228
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.4.1 - 145. Setting group control – two-wire connection from Petersen coil status with additional logic. The images above depict a two-wire connection from the Petersen coil: the two images at the top show a direct connection, while the two images on the bottom include additional logic.
Page 229
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.4.1 - 146. Entirely application-controlled setting group change with the cold load pick-up function. In these examples the cold load pick-up function's output is used for the automatic setting group change.
Page 230
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 4168 SG6 Enabled 4169 SG6 Disabled 4170 SG7 Enabled 4171 SG7 Disabled 4172 SG8 Enabled 4173 SG8 Disabled 4174 SG1 Request ON 4175 SG1 Request OFF 4176...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 4206 SG3 Active ON 4207 SG3 Active OFF 4208 SG4 Active ON 4209 SG4 Active OFF 4210 SG5 Active ON 4211 SG5 Active OFF 4212...
Page 232
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The function generates general time stamped ON/OFF events to the common event buffer from each of the two (2) output signals as well as several operational event signals. The time stamp resolution is 1 ms.
Page 233
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description 0: Open Blocked 1: Open Allowed 2: Close Additional Blocked status 3: Close Displays additional information about the status of the object. information Allowed 4: Object Ready 5: Object Not Ready 6: Sync Ok...
Page 234
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.4.2 - 120. I/O. Signal Range Description Digital input or other logical Objectx Open input A link to a physical digital input. The monitored object's OPEN status. "1" refers signal selected ("Objectx Open Status to the active open state of the monitored object.
Page 235
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Maximum Open Determines the maximum length for a Open pulse from the output relay to the 0.02…500.00 0.02 command 0.2 s controlled object. If the object operates faster than this set time, the control pulse pulse is reset and a status change is detected.
Page 236
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.4.2 - 148. Example of an interlock application. In order for the blocking signal to be received on time, it has to reach the function 5 ms before the control command.
Page 237
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.4.2 - 123. Event codes of the OBJ function instances 1 – 5. Event Number Event channel Event block name Event Code Description 2944 OBJ1 Object Intermediate 2945 OBJ1 Object Open 2946 OBJ1...
Page 238
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event Number Event channel Event block name Event Code Description 3017 OBJ2 Open Request OFF 3018 OBJ2 Open Command ON 3019 OBJ2 Open Command OFF 3020 OBJ2 Close Request ON 3021 OBJ2 Close Request OFF...
Page 239
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event Number Event channel Event block name Event Code Description 3091 OBJ3 Close Blocked OFF 3092 OBJ3 Object Ready 3093 OBJ3 Object Not Ready 3094 OBJ3 Sync Ok 3095 OBJ3 Sync Not Ok 3096 OBJ3...
Page 240
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event Number Event channel Event block name Event Code Description 3201 OBJ5 Object Open 3202 OBJ5 Object Close 3203 OBJ5 Object Bad 3204 OBJ5 WD Intermediate 3205 OBJ5 WD Out 3206 OBJ5 WD In...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Description Close fail The cause of a "Close" command's failure. Open command The source of an "Open" command. Close command The source of an "Open" command. General status The general status of the function. 5.4.3 Indicator object monitoring The indicator object monitoring function takes care of the status monitoring of disconnectors.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Range Description IndicatorX Close Digital input or other input A link to a physical digital input. The monitored indicator's CLOSE status. "1" refers to logical signal selected ("Ind.X by the user the active "Close"...
Page 243
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • the simplest option to connect and configure • uses less wiring and connections than other signals, thus greatly reducing initial setup costs • good for travelling long distances, as current does not degrade over long connections like voltage does •...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Input value 0.001 The second input point in the mA output control curve. …10 Scaled mA The mA output value when the measured value is equal output 0.0000…24.0000mA 0.0001mA 0mA to or greater than Input value 2.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Settings. These settings can be accessed at Control → Device I/O → Programmable control switch . Table. 5.4.5 - 132. Settings. Name Range Default Description The user-settable name of the selected switch. The name can be up to Switch name Switchx 32 characters long.
Page 246
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • RTD inputs and mA inputs in "RTD & mA input" option cards • mA inputs in "mA output & mA input" option cards • Digital input voltages Table. 5.4.6 - 134. Main settings (input channel). Name Range Step...
Page 247
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The Nyquist rate states that the filter time constant must be at least double the period time of the disturbance process signal. For example, the value for the filter time constant is 2 seconds for a 1 second period time of a disturbance oscillation.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Scaled output 0.000 Scales the measured milliampere signal at Point 2..10 value 1 0: Not 0: Not Allows the user to create their own curve with up to twenty (20) curve curvepoint used used...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.4.8 - 152. Operation of logical input in "Hold" and "Pulse" modes. A logical input pulse can also be extended by connecting a DELAY-low gate to a logical output, as has been done in the example figure below.
Page 250
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.1 - 154. Secondary circuit fault in phase L1 wiring. The function constantly monitors the instant values and the key calculated magnitudes of the phase currents. Additionally, the residual current circuit can be monitored if the residual current is measured from a dedicated residual current CT.
Page 251
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • measured and pre-processed current magnitudes. The output signals can be used for direct I/O controlling and user logic programming. The function generates general time-stamped ON/OFF events to the common event buffer from each of the two (2) output signal.
Page 252
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.5.1 - 136. Measured inputs of the CTS function. Signal Description Time base IL1RMS RMS measurement of phase L1 (A) current IL2RMS RMS measurement of phase L2 (B) current IL3RMS RMS measurement of phase L3 (C) current I01RMS...
Page 253
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.5.1 - 138. Pick-up settings. Name Range Step Default Description Determines the pick-up threshold for phase current measurement. This setting limit defines the upper limit for the phase current's pick-up high element.
Page 254
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Operating time characteristics This function supports definite time delay (DT). For detailed information on this delay type please refer to the chapter "General properties of a protection function" and its section "Operating time characteristics for trip and reset".
Page 255
A A Q Q -M210 -M210 Instruction manual Version: 2.04 When a fault is detected and all conditions are met, the CTS timer starts counting. If the situation continues until the set time has passed, the function issues an alarm. Figure.
Page 256
A A Q Q -M210 -M210 Instruction manual Version: 2.04 If any of the phases exceed the I high limit setting, the operation of the function is not activated. This behavior is applied to short-circuits and earth faults even when the fault current exceeds the I high limit setting.
Page 257
A A Q Q -M210 -M210 Instruction manual Version: 2.04 When the residual condition is added with the "I0 input selection", the sum of the current and the residual current are compared against each other to verify the wiring condition. Figure.
Page 258
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.1 - 164. Primary side high-impedance earth fault. In this example there is a high-impedance earth fault. It does not activate the function, if the measurement conditions are met, while the calculated and measured residual current difference does not reach the limit.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.5.1 - 140. Register content. Date Time to Used Event code Trigger currents Ftype and time CTSact Time The status Setting The phase currents (L1, L2 & L3), the remaining dd.mm.yyyy code of the...
Page 260
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The function's output signals can be used for direct I/O controlling and user logic programming. The function generates general time-stamped ON/OFF events to the common event buffer from each of the two (2) output signal.
Page 261
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Pick-up for alarming For the alarm stages Alarm 1 and Alarm 2, the user can set the pick-up level for the number of operations left. The pick-up setting is common for all phases and the alarm stage picks up if any of the phases goes below this setting.
Page 262
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Now, we set the stage as follows: Parameter Setting Current 1 0.80 kA Operation 1 30 000 operations Current 2 16.00 kA Operations 2 100 operations Enable Alarm 1 1: Enabled Alarm 1 Set 1000 operations Enable Alarm 2...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Events and registers The circuit breaker wear function (abbreviated "CBW" in event block names) generates events and registers from the status changes in Triggered, Alarm 1 and Alarm 2 signals as well as in internal pick- up comparators.
Page 264
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.3 - 167. THD calculation formulas. While both of these formulas exist, the power ratio ( THD ) is recognized by the IEEE, and the amplitude ratio ( THD ) is recognized by the IEC.
Page 265
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.3 - 168. Simplified function block diagram of the total harmonic distortion monitor function. Measured input The function block uses analog current measurement values. The function always uses FFT measurement of the whole harmonic specter of 32 components from each measured current channel.
Page 266
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Pick-up The Phase , I01 and I02 s etting parameters control the the pick-up and activation of the function. They define the maximum allowed measured current before action from the function. Before the function activates alarm signals, their corresponding pick-up elements need to be activated with the setting parameters Enable phase THD alarm , Enable I01 THD alarm and Enable I02 THD alarm .
Page 267
A A Q Q -M210 -M210 Instruction manual Version: 2.04 If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and the function does not process the situation further. If the START function has been activated before the blocking signal, it resets and the release time characteristics are processed similarly to when the pick- up signal is reset.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Event number Event channel Event block name Event code Description 3529 THD1 THD Alarm I01 OFF 3530 THD1 THD Alarm I02 ON 3531 THD1 THD Alarm I02 OFF 3532 THD1 Blocked ON 3533 THD1...
Page 269
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description IL2” Phase current I (CT card 2) Phase current I (CT card 2) IL3” Residual current I coarse* (CT card 2) I01”c I01”f Residual current I fine* (CT card 2) Residual current I coarse* (CT card 2) I02”c...
Page 270
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 5.5.4 - 155. Digital recording channels – Measurements. Signal Description Signal Description Currents Primary phase current ILx Primary phase current TRMS (IL1, IL2, Pri.Pha.curr.ILx Pha.curr.ILx TRMS Pri (IL1, IL2, IL3) IL3) Phase angle ILx (IL1, IL2, Pha.angle ILx...
Page 271
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Signal Description Pos./Neg./Zero Positive/Negative/Zero Ux Angle difference Ux angle difference (U1, U2, U3) Seq volt.Angle sequence voltage angle Resistive and reactive currents ILx resistive current in per- ILx Resistive Pos.seq.
Page 272
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signal Description Signal Description Neutral Primary neutral susceptance B f meas qlty Quality of tracked frequency susceptance (Pri) Indicates which of the three voltage or Neutral Primary neutral admittance f meas from current channel frequencies is used by the admittance Y (Pri) relay.
Page 273
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The device has a maximum limit of 100 for the number of recordings. Even when the recordings are very small, their number cannot exceed 100. The number of analog and digital channels together with the sample rate and the time setting affect the recording size.
Page 274
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Step Default Description Selects what happens when the memory is full. 0: FIFO Recording mode 0: FIFO "FIFO" (= first in, first out) replaces the oldest stored recording 1: Keep olds with the latest one.
Page 275
The recorder is configured by using the setting tool software or relay HMI, and the results are analyzed with the AQviewer software (is automatically downloaded and installed with AQtivate). Registered users can download the latest tools from the Arcteq website (arcteq.fi./downloads/).
Page 276
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.4 - 169. Disturbance recorder settings. Figure. 5.5.4 - 170. Effects of recording length and pre-triggering time signals. This example is based on the settings shown above. When there is at least one recording in the device's memory, that recording can be analyzed by using the AQviewer software (see the image below).
Page 277
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The user can also launch the AQviewer software from the Disturbance recorder menu. AQviewer Opening f Opening folders olders Disturbance recordings can be opened by clicking on the "Open folder" icon or by going to File → Open (see the image below).
Page 278
A A Q Q -M210 -M210 Instruction manual Version: 2.04 1. You can remove plotters individually by using the red "—" icon (numbered "1" in the image below). Please note that the "Remove plotters" text appears when you move the cursor on top of the icon.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 5.5.5 Measurement recorder Measurements can be recorded to a file with the measurement recorder. The chosen measurements are recorded at selected intervals. In the "Measurement recorder" window, the measurements the user wants to be recorded can be selected by checking their respective check boxes.
Page 280
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 5.5.5 - 172. Measurement recorder values viewed with AQtivate PRO. Table. 5.5.5 - 161. Available analog signals. Curr Current mea ent measur surements ements P-P Curr.I”L3 L1 Imp.React.Ind.E.Mvarh Pri.Pha.Curr.IL1 P-P Curr.I”01 L1 Imp.React.Ind.E.kvarh Pri.Pha.Curr.IL2...
Page 281
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Pha.Curr.IL2 TRMS Sec Neg.Seq.Volt.Pri L3 Exp.Active Energy MWh Pha.Curr.IL3 TRMS Sec Zero.Seq.Volt.Pri L3 Exp.Active Energy kWh Sec.Pos.Seq.Curr. U1Volt Sec L3 Imp.Active Energy MWh Sec.Neg.Seq.Curr. U2Volt Sec L3 Imp.Active Energy kWh Sec.Zero.Seq.Curr.
Page 282
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Res.Curr.angle I01 System Volt UL2 mag TM> Reference T curr. Res.Curr.angle I02 System Volt UL2 mag (kV) TM> Active meas curr. Calc.I0.angle System Volt UL3 mag TM> T est.with act. curr. Pos.Seq.Curr.angle System Volt UL3 mag (kV) TM>...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Calc.I”0 L3 Tan(phi) L3 Bias current Pha.Curr.I”L1 TRMS L3 Cos(phi) L3 Diff current Pha.Curr.I”L2 TRMS 3PH Apparent Power (S) L3 Char current Pha.Curr.I”L3 TRMS 3PH Active Power (P) HV I0d> Bias current I”...
Page 284
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The user can set up to eight (8) magnitudes to be recorded when the function is triggered. An overcurrent fault type, a voltage fault type, and a tripped stage can be recorded and reported straight to SCADA.
Page 285
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Currents Description Rseq, Xseq, Zseq The positive sequence resistance, reactance and impedance values and angles. RseqAng, XseqAng, ZseqAng GL1, GL2, GL3, G0 BL1, BL2, BL3, B0 The conductances, susceptances and admittances. YL1, YL2, YL3, Y0 YL1angle, YL2angle, YL3angle The admittance angles.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 6 System integration 6.1 Communication protocols 6.1.1 NTP When enabled, the NTP (Network Time Protocol) service can use external time sources to synchronize the device's system time. The NTP client service uses an Ethernet connection to connect to the NTP time server.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 6.1.2 Modbus/TCP and Modbus/RTU The device supports both Modbus/TCP and Modbus/RTU communication. Modbus/TCP uses the Ethernet connection to communicate with Modbus/TCP clients. Modbus/RTU is a serial protocol that can be selected for the available serial ports. The following Modbus function types are supported: •...
AQ-25x frame units support both Edition 1 and 2 of IEC61850. The following services are supported by IEC 61850 in Arcteq devices: • Up to six data sets (predefined data sets can be edited with the IEC 61850 tool in AQtivate) •...
Page 291
The device's current IEC 61850 setup can be viewed and edited with the IEC61850 tool ( Tools → Communication → IEC 61850 ). By browsing the 61850 tree one can see the full list of available logical nodes in the Arcteq implementation. Settings.
(slave) station. The IEC 103 protocol can be selected for the serial ports that are available in the device. A primary (master) station can then communicate with the Arcteq device and receive information by polling from the slave device. The transfer of disturbance recordings is not supported.
DNP3 slave is compliant with the DNP3 subset (level) 2, but it also contains some functionalities of the higher levels. For detailed information please refer to the DNP3 Device Profile document (www.arcteq.fi/downloads/ → AQ-200 series → Resources). Settings The following table describes the DNP3 setting parameters.
Page 294
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Name Range Default Description 0: Var 1 Group 4 variation (DBI change) 1: Var 2 Selects the variation of the double point signal. 1: Var 2 0: Var 1 1: Var 2 Group 20 variation (CNTR) 0: Var 1 Selects the variation of the control signal.
IEC 104 protocol uses Ethernet communication. The IEC 101/104 implementation works as a slave in the unbalanced mode. For detailed information please refer to the IEC 101/104 interoperability document (www.arcteq.fi/ downloads/ → AQ-200 series → Resources → "AQ-200 IEC101 & IEC104 interoperability").
Page 296
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • Current • Residual current • Voltage • Residual voltage • Angle The range is the same for all of the scaling coefficients. By default, there is no scaling. • No scaling •...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 6.1.9 SPA The device can act as a SPA slave. SPA can be selected as the communication protocol for the COM B port (RS-485 port in the CPU module). When the device includes a serial RS-232 card connector, the SPA protocol can also be selected as the communication protocol for the COM E and COM F ports.
Page 298
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Measurable values Function block uses analog current and voltage measurement values. The relay uses these values as the basis when it calculates the primary and secondary values of currents, voltages, powers, impedances and other values.
Page 299
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Signals Description Z12Ang, Z23Ang, Z31Ang, Phase-to-phase and phase-to-neutral impedance angles. ZL1Ang, ZL2Ang, ZL3Ang Rseq, Xseq, Zseq Positive sequence resistance, reactance and impedance values and angles. RseqAng, XseqAng, ZseqAng GL1, GL2, GL3, G0 BL1, BL2, BL3, B0 Conductances, susceptances and admittances.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 As can be seen in the image below, the example application has connected the three phase currents and the residual current (I01). The digital inputs are connected to indicate the breaker status, while the digital outputs are used for breaker control.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 7.3 - 177. ARON connection. The ARON input connection can measure the load symmetrically despite the fact that one of the CTs is missing from the installation. Normally, Phase 2 does not have a current transformer installed as an external fault is much more likely to appear on Lines 1 or 3.
Page 305
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 7.4 - 178. Trip circuit supervision with one DI and one non-latched trip output. Note that the digital input that monitors the circuit is normally closed, and the same applies to the alarm relay if one is used.
Page 306
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 7.4 - 180. Non-latched trip contact. When the auto-reclosing function is used in feeder applications, the trip output contacts must be non- latched. Trip circuit supervision is generally easier and more reliable to build with non-latched outputs. The open coil remains energized only as long as the circuit breaker is opened and the IED output releases.
Page 307
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 7.4 - 181. Trip circuit supervision with one DI and one latched output contact. The trip circuit with a latched output contact can be monitored, but only when the circuit breaker's status is "Closed".
Page 308
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 7.4 - 182. Example block scheme.
In field upgrades, therefore, the add-on module must be ordered from Arcteq Relays Ltd. or its representative who can then provide the module with its corresponding unlocking code to allow the device to operate correctly once the hardware configuration has been upgraded.
Page 310
A A Q Q -M210 -M210 Instruction manual Version: 2.04 When an I/O module is inserted into the device, the module location affects the naming of the I/O. The I/O scanning order in the start-up sequence is as follows: the CPU module I/O, Slot A, Slot C, Slot E, Slot F.
Page 311
A A Q Q -M210 -M210 Instruction manual Version: 2.04 4. Scan Scans Slot C, and moves to the next slot if Slot C is empty. If the scan finds an 8DI module, it reserves the designations "DI4", "DI5", "DI6", "DI7", "DI8", "DI9", "DI10" and "DI11" to this slot. If Slot A also has an 8DI module (and therefore has already reserved these designations), the device reserves the designations "DI12", "DI13", "DI14", "DI15", "DI16", "DI17", "DI18"...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 8.2 CPU module Figure. 8.2 - 185. CPU module. Module connectors Table. 8.2 - 183. Module connector descriptions. Connector Description Communication port A, or the RJ-45 port. Used for the setting tool connection and for IEC 61850, Modbus/ COM A TCP, IEC 104, DNP3 and station bus communications.
Page 313
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Connector Description System fault's output relay, with a changeover contact. Pins 16 and 17 are closed when the unit has a system X 16:17:18 fault or is powered OFF. Pins 16 and 18 are closed when the unit is powered ON and there is no system fault. Power supply IN.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 8.3 Current measurement module Figure. 8.3 - 186. Module connections with standard and ring lug terminals. Connector Description CTM 1-2 Phase current measurement for phase L1 (A). CTM 3-4 Phase current measurement for phase L2 (B). CTM 5-6 Phase current measurement for phase L3 (C).
A A Q Q -M210 -M210 Instruction manual Version: 2.04 8.4 Digital input module (optional) Figure. 8.4 - 187. Digital input module (DI8) with eight add-on digital inputs. Description (x = the number of digital inputs in other modules that preceed this one in the Connector configuration) DIx + 1...
Page 316
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Setting up the activation and release delays The settings described in the table below can be found at Control → Device I/O → Digital input settings in the relay settings. Table.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 8.4 - 188. Digital input state when energizing and de-energizing the digital input channels. Digital input voltage measurements Digital input option card channels measure voltage on each channel. The measured voltage can be seen at Control →...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Connector Description X 5–6 OUTx + 3 (1 and 2 pole NO) X 7–8 OUTx + 4 (1 and 2 pole NO) X 9–10 OUTx + 5 (1 and 2 pole NO) The DO5 module is an add-on module with five (5) digital outputs.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Connector Description Binary input 1 (+ pole) Binary input 1 ( – pole) The arc protection module is an add-on module with four (4) light sensor channels, two (2) high-speed outputs and one (1) binary input.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 The RTD input module is an add-on module with eight (8) RTD input channels. Each input supports 2-wire, 3-wire and 4-wire RTD sensors as well as thermocouple (TC) sensors. The sensor type can be selected with software for two groups, four channels each.
Page 321
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Connector Name Description • Serial-based communications • Wavelength 660 nm Serial fiber (GG/ • Compatible with 50/125 μm, 62.5/125 μm, 100/140 μm, and COM E PP/GP/PG) 200 μm Plastic-Clad Silica (PCS) fiber •...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 8.10 Double ST 100 Mbps Ethernet communication module (optional) Figure. 8.10 - 195. Double ST 100 Mbps Ethernet communication module connectors. Connector Description • IRIG-B input Two-pin connector • Duplex ST connectors (IRIG-B input) •...
Page 324
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 8.10 - 196. Example of a ring configuration. Figure. 8.10 - 197. Example of a multidrop configuration.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 8.11 Double RJ-45 10/100 Mbps Ethernet communication module (optional) Figure. 8.11 - 198. Double RJ-45 10/100 Mbps Ethernet communication module. Connector Description • IRIG-B input Two-pin connector • Two Ethernet ports •...
Page 326
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Figure. 8.11 - 199. Example of a ring configuration. Figure. 8.11 - 200. Example of a multidrop configuration.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9 Technical data 9.1 Hardware 9.1.1 Measurements 9.1.1.1 Current measurement Table. 9.1.1.1 - 188. Technical data for the current measurement module. Connections Three phase current inputs: IL1 (A), IL2 (B), IL3 (C) Measurement channels/CT Two residual current inputs: Coarse residual current input I01, Fine residual current input inputs...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 < ±0.2° (I> 0.05 A) Angle measurement inaccuracy < ±1.0° (I≤ 0.05 A) Burden (50/60Hz) <0.1 VA Transient overreach <5 % Fine residual current input (I02) Rated current I 0.2 A (configurable 0.001…10 A) 25 A (continuous) 100 A (for 10 s) Thermal withstand...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Rated auxiliary voltage 85…265 V (AC/DC) < 7 W Power consumption < 15 W Maximum permitted interrupt time < 60 ms with 110 VDC DC ripple < 15 % Terminal block connection Terminal block Phoenix Contact MSTB 2,5/5-ST-5,08 Solid or stranded wire...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 IEC 61850 IEC 104 Modbus/TCP Port protocols DNP3 Telnet Data transfer rate 100 MB System integration Can be used for system protocols and for local programming Table. 9.1.2.2 - 194. Rear panel system communication port B. Port Port media Copper RS-485...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9.1.2.4 CPU digital outputs Table. 9.1.2.4 - 196. Digital outputs (Normally Open) Rated values Rated auxiliary voltage 265 V (AC/DC) Continuous carry Make and carry 0.5 s 30 A Make and carry 3 s 15 A Breaking capacity, DC (L/R = 40 ms) at 48 VDC...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Table. 9.1.3.3 - 201. High-Speed Outputs (HSO1…2) Rated values Rated auxiliary voltage 250 VDC Continuous carry Make and carry 0.5 s 15 A Make and carry 3 s Breaking capacity, DC (L/R = 40 ms) 1 A/110 W Control rate 5 ms...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Update cycle 5...10 000 ms, setting step 5 ms Response time @ 5 ms cycle ~ 15 ms (13...18 ms) Update cycle time inaccuracy Max. +20 ms above the set cycle mA input scaling range 0...4000 mA Output scaling range...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9.1.4 Display Table. 9.1.4 - 207. Technical data for the HMI LCD display. Dimensions and resolution Number of dots/resolution 320 x 160 Size 84.78 × 49.90 mm (3.34 × 1.96 in) Display Type of display Color...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Reset time setting 0.010…10.000 s, step 0.005 s Inaccuracy: Reset time ±1.0 % or ±50 ms Instant reset time and start-up reset <50 ms Not t e! e! • The release delay does not apply to phase-specific tripping. 9.2.1.2 Non-directional earth fault protection (I0>;...
Page 340
A A Q Q -M210 -M210 Instruction manual Version: 2.04 • The operation and reset time accuracy does not apply when the measured secondary current in I02 is 1…20 mA. The pick-up is tuned to be more sensitive and the operation times vary because of this.
Page 341
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Phase current inputs: I (A), I (B), I Current inputs Residual current channel I (Coarse) Residual current channel I (Fine) Pick-up Harmonic selection , 11 , 13 , 15 , 17 or 19 Harmonic per unit (×...
Page 342
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Phase current inputs: I (A), I (B), I Current inputs Residual current channel I (Coarse) Residual current channel I (Fine) RMS phase currents Current input magnitudes RMS residual current (I or calculated I Pick-up Monitored signals...
Page 343
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9.2.1.7 Machine thermal overload protection (TM>; 49M) Table. 9.2.1.7 - 214. Technical data for the machine thermal overload protection function. Measurement inputs Current inputs Phase current inputs: I (A), I (B), I Current input magnitudes TRMS phase currents (up to the 31...
Page 344
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Time settings Starting time setting 0.00…1800.00 s, setting step 0.005 s Definite time or cumulative I2t sum inverse operating time Operating mode With or without a speed switch input Monitors only starts or both starts and stall Start time Max.
Page 345
A A Q Q -M210 -M210 Instruction manual Version: 2.04 9.2.1.10 Non-directional undercurrent protection (I<; 37) Table. 9.2.1.10 - 217. Technical data for the undercurrent function. Measurement inputs Current inputs Phase current inputs: I (A), I (B), I Current input magnitudes RMS phase currents Pick-up Pick-up current setting...
Page 346
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Instant reset time and start-up reset <50 ms Not t e! e! • Mechanical jam protection requires that the motor running condition has been met before tripping is possible. 9.2.1.12 Resistance temperature detectors Table.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Reset Reset ratio for current 97 % of the pick-up setting Reset time <35 ms Not t e! e! • The maximum length of the arc sensor cable is 200 meters. 9.2.2 Control functions 9.2.2.1 Setting group selection Table.
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Phase current inputs: I (A), I (B), I Current inputs Residual current channel I (Coarse) (optional) Residual current channel I (Fine) (optional) RMS phase currents Current input magnitudes RMS residual current (I ) (optional) Pick-up Pick-up current settings:...
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Pick-up Power THD Operating modes Amplitude THD Pick-up setting for all comparators 0.10…200.00 % , setting step 0.01 % ±3 % of the set pick-up value > 0.5 × I setting;...
Page 350
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Electrostatic discharge (ESD): Air discharge 15 kV EN 60255-26, IEC 61000-4-2 Contact discharge 8 kV Electrical fast transients (EFT): Power supply input 4 kV, 5/50 ns, 5 kHz EN 60255-26, IEC 61000-4-4 Other inputs and outputs 4 kV, 5/50 ns, 5 kHz Surge: Between wires 2 kV, 1.2/50 µs...
Page 351
A A Q Q -M210 -M210 Instruction manual Version: 2.04 Temperature ranges Ambient service temperature range –35…+70 °C Transport and storage temperature range –40…+70 °C Other Altitude <2000 m Overvoltage category Pollution degree Casing and package Table. 9.3 - 232. Dimensions and weight. Without packaging (net) Height: 117 mm (4U) Dimensions...
Page 352
A A Q Q -M210 -M210 Instruction manual Version: 2.04 10 Ordering information Accessories Order code der code Descrip Description tion Not t e e Manufact Manufactur urer er...
Page 353
ADAM-4018+- External 8-ch Thermocouple mA Input module, pre- Requires an external power Advanced Co. configured module Ltd. AQX033 Raising frame 87 mm Arcteq Ltd. AQX070 Raising frame 40 mm Arcteq Ltd. AQX069 Combiflex frame Arcteq Ltd. AQX097 Wall mounting bracket Arcteq Ltd.
Page 354
A A Q Q -M210 -M210 Instruction manual Version: 2.04 11 Contact and reference information Manufacturer Arcteq Relays Ltd. Visiting and postal address Kvartsikatu 2 A 1 65300 Vaasa, Finland Contacts Phone: +358 10 3221 370 Fax: +358 10 3221 389 Website (general): arcteq.fi...