Arcteq AQ-M210 Instruction Manual

Motor protection ied
Hide thumbs Also See for AQ-M210:
Table of Contents

Advertisement

Quick Links

AQ-M210
Motor protection IED
Instruction manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AQ-M210 and is the answer not in the manual?

Questions and answers

Summary of Contents for Arcteq AQ-M210

  • Page 1 AQ-M210 Motor protection IED Instruction manual...
  • Page 2: Table Of Contents

    5.1. Functions included in AQ-M210 ........
  • Page 3 7.1. Connections AQ-M210 ........
  • Page 4 11. Contact and reference information ..........© Arcteq Relays Ltd...
  • Page 5 Nothing contained in this document shall increase the liability or extend the warranty obligations of the manufacturer Arcteq Relays Ltd. The manufacturer expressly disclaims any and all liability for any damages and/or losses caused due to a failure to comply with the instructions contained herein or caused by persons who do not ful l the aforementioned requirements.
  • Page 6 AQ-M210 Instruction manual Version: 2.01 Copyright Copyright © Arcteq Relays Ltd. 2018. All rights reserved. © Arcteq Relays Ltd...
  • Page 7: Manual Revision Notes

    1.2. Version 1 revision notes Revision 1.00 Date 8.4.2013 Changes -       The rst revision for AQ-M210. Revision 1.01 Date 29.8.2013 -       Application example for ARON input connection added to chapter 8.0. -       Application example for trip circuit supervision.
  • Page 8 -       Fault view description added -       New U> and U< function measurement modes documented -       Order code revised Revision 1.09 Date 14.8.2018 -       Added mA output option card description and ordercode Changes -       Added HMI display technical data © Arcteq Relays Ltd...
  • Page 9: Abbreviations

    RMS – Root mean square SF – System failure TMS – Time multiplier setting TRMS – True root mean square VAC – Voltage alternating current VDC – Voltage direct current SW – Software uP - Microprocessor © Arcteq Relays Ltd...
  • Page 10: General

    I/O requirements and the software determines the available functions. This manual describes the speci c application of the AQ-M210 motor protection IED. For other AQ-200 series products please consult the respective device manuals.
  • Page 11: Ied User Interface

    The sixteen freely con gurable LEDs are located on the right side of the display. Their activation and color (green or yellow) are based on the settings the user has put in place in the software. © Arcteq Relays Ltd...
  • Page 12: Mimic And Main Menu

    ) takes you to the password menu where you can enter the passwords for the various user levels (User, Operator, Con gurator, and Super-user).  4.2.2. Navigation in the main con guration menus All the settings in this device have been divided into the following six (6) main con guration menus: General Protection Control © Arcteq Relays Ltd...
  • Page 13: General Menu

    Figure. 4.3. - 4. Device info. The Device info tab in the General menu displays the following information: The set name and location of the device. The device's serial number and software version. The hardware con guration (i.e. the order code). © Arcteq Relays Ltd...
  • Page 14: Protection Menu

    For example, the I> (overcurrent) protection stage can be found in the "Current" module, whereas the U< (undervoltage) protection stage can be found in the "Voltage" module. © Arcteq Relays Ltd...
  • Page 15 "Current" module, and selects the I> stage for further inspection. Figure. 4.4. - 7. Accessing the submenu of an individual activated stage. Each protection stage and supporting function has ve sections in their stage submenus: "Info", "Settings",  " Registers", "I/O" and "Events". INFO © Arcteq Relays Ltd...
  • Page 16 Active settings: displays the setting group and its settings (other setting groups can be set in the "Settings" section). While the function is activated and disabled in the Stage selection  submenu, you can disable the function through the "Info" section ("Function mode" at the top of the section). SETTINGS © Arcteq Relays Ltd...
  • Page 17 The stage settings vary depending on which protection function they are a part of. By default only one setting group of the eight available setting groups is activated. You can enable more groups in the Control menu, although they are set here in the "Settings" section. REGISTERS © Arcteq Relays Ltd...
  • Page 18 You can clear the the operation register by choosing "Clear registers" → "Clear". "Stage event log" stores the event registers generated by the stage. These general event registers cannot be cleared. © Arcteq Relays Ltd...
  • Page 19 "Blocking input control" allows you to block stages. The blocking can be done by using any of the following: digital inputs logical inputs or outputs the START, TRIP or BLOCKED information of the stage object status information. EVENTS © Arcteq Relays Ltd...
  • Page 20: Control Menu

    ( Objects) , setting the various control functions ( Control functions)  and controlling the inputs and outputs ( Device I/O) . The available control functions depend on the model of the device in use. Figure. 4.5. - 13. Control menu view. © Arcteq Relays Ltd...
  • Page 21 Force SG change: this setting allows the activation of a setting group at will (please note that Force SG change enable must be "Enabled"). Used setting groups: this setting allows the activation of setting groups SG1...SG8 (only one group is active by default). © Arcteq Relays Ltd...
  • Page 22 Each activated object is visible in the  Objects submenu. By default all objects are disabled unless speci cally activated in the Controls enabled submenu. Each active object has four sections in their submenus: "Settings", "Application control" ("App contr"), "Registers" and "Events". SETTINGS © Arcteq Relays Ltd...
  • Page 23 Clear statistics: statistics can be cleared by choosing "Clear statistics" and then "Clear". An object has Open and Close inputs (connected to physical output relays). A withdrawable object has In and Out inputs. Both "Object Ready" and "Synchrocheck" have status inputs. © Arcteq Relays Ltd...
  • Page 24 Each control function that has been activated is listed in the Control functions submenu (see the middle image above). Every function includes the same sections as the protections stages: "Info", "Settings", "Registers", "I/O" and "Events" (for a more detailed breakdown of their contents, please refer to the "Protection menu" chapter of this document). © Arcteq Relays Ltd...
  • Page 25 LEDs in the Device I/O matrix Figure. 4.5. - 21. Digital inputs section. All settings related to digital inputs can be found in the "Digital inputs" section. © Arcteq Relays Ltd...
  • Page 26 NOTE! An NC signal goes to the default position (NO) if the relay loses the auxiliary voltage or if the system is fully reset. However, an NC signal does not open during voltage or during System full reset. Normally closed output signal does not open during a Communication or Protection reset. © Arcteq Relays Ltd...
  • Page 27 The "LED settings" subsection allows you to modify the individual label text attached to an LED ("LED description settings"); that label is visible in the LED quick displays and the matrices. You can also modify the color of the LED ("LED color settings") between green and yellow; by default all LEDs are green. © Arcteq Relays Ltd...
  • Page 28 These signals can be used in a variety of situations, such as for controlling the logic program, for function blocking, etc. You can name each switch and set the access level to determine who can control the switch. © Arcteq Relays Ltd...
  • Page 29: Communication Menu

    (can be found in the Connections submenu). As a standard, the devices support the following communication protocols: NTP, IEC 61850, Modbus/TCP, Modbus/RTU, IEC 103, IEC 101/104, SPA and Modbus/IO. You can also have other protocols with additional, speacialized communication interface modules. © Arcteq Relays Ltd...
  • Page 30 NOTE! When communicating with a device through a front Ethernet port connection, the IP address is always 192.168.66.9. Protocols Figure. 4.6. - 28. View of the Protocols submenu.  The Protocols submenu offers access to the various communication protocol con guration menus: © Arcteq Relays Ltd...
  • Page 31: Measurement Menu

    Transformers submenu, while the system nominal frequency is speci ed in the Frequency submenu. Other submenus are mainly for monitoring purposes. Transformers Figure. 4.7. - 29. Transformers submenu. © Arcteq Relays Ltd...
  • Page 32 When "Sampling mode" is set to "Tracking", the device uses the measured frequency value as the system nominal frequency. There are three reference measuring points; the order of the reference points can be changed. © Arcteq Relays Ltd...
  • Page 33 (and then set the parameters) for the Energy dose counter mode. "Power measurements" displays all three-phase powers as well as the powers of individual phases. "Energy measurements" displays the three-phase energy as well as the energies of the individual phases. © Arcteq Relays Ltd...
  • Page 34: Monitoring Menu

    ( Disturbance REC ) and accessing the device diagnostics ( Device diagnostics ). The available monitoring functions depend on the type of the device in use. Figure. 4.8. - 33. Monitoring menu view. © Arcteq Relays Ltd...
  • Page 35 Con guring monitor functions is very similar to con guring protection stages. They, too, have the ve sections that display information ("Info"), set the parameters ("Settings"), show the inputs and outputs ("I/O") and present the events and registers ("Events" and "Registers"). © Arcteq Relays Ltd...
  • Page 36 "Recording mode" can be selected to replace the oldest recording ("FIFO") or to keep the old recordings ("FILO"). "Analog channel samples" determines the sample rate of analog channels, and it can be selected to be 8/16/32/62 samples per cycle. © Arcteq Relays Ltd...
  • Page 37 If you see something out of the ordinary in the Device diagnostics submenu and cannot reset it, please contact the closest representative of the manufacturer or the manufacturer of the device itself © Arcteq Relays Ltd...
  • Page 38: Con Guring User Levels And Their Passwords

    Operator: Can view any menus and settings but cannot change any settings BUT can operate breakers and other equipment. Con gurator: Can change most settings such as basic protection pick-up levels or time delays, breaker control functions, signal descriptions etc. and can operate breakers and other equipment. © Arcteq Relays Ltd...
  • Page 39 AQ-M210 Instruction manual Version: 2.01 Super user: Can change any setting and can operate breakers and other equipment. NOTE! Any user level with a password automatically locks itself after half an hour (30 minutes) of inactivity. © Arcteq Relays Ltd...
  • Page 40: Functions

    AQ-M210 Instruction manual Version: 2.01 5. Functions 5.1. Functions included in AQ-M210 The AQ-M210 motor protection relay includes the following functions as well as the number of stages for those functions. Table. 5.1. - 1. Protection functions of AQ-M210. Name (number of ANSI Description stages) I>...
  • Page 41: Measurements

    For the measurements to be correct the user needs to ensure that the measurement signals are connected to the correct inputs, that the current direction is connected to the correct polarity, and that the scaling is set according to the nominal values of the current transformer. © Arcteq Relays Ltd...
  • Page 42 Example of CT scaling The following gure presents how CTs are connected to the relay's measurement inputs. It also shows example CT ratings and nominal current of the load. Figure. 5.2.1. - 39. Connections. © Arcteq Relays Ltd...
  • Page 43 (in this case they are the set primary and secondary currents of the CT). If the protected object's nominal current is chosen to be the basis for the per-unit scaling, the option "Object in p.u." is selected for the "Scale meas to In" setting (see the image below). © Arcteq Relays Ltd...
  • Page 44 Figure. 5.2.1. - 42. Residual I01 CT scaling (coarse). The ring core CT is connected to the CTM directly, which requires the use of sensitive residual current measurement settings: the "I02 CT" settings are set according to the ring core CT's ratings (10/2 A). © Arcteq Relays Ltd...
  • Page 45 As the images above show, the scaling selection does not affect how primary and secondary currents are displayed (as actual values). The only effect is that the per-unit system in the relay is scaled either to the CT nominal or to the object nominal, making the settings input straightforward. © Arcteq Relays Ltd...
  • Page 46 The residual I0CT scaling is set according to the zero sequence CT's ratings, in this case 200/1.5 mA (see the image below). Based on these values, the earth fault protection setting (1 × I0n) makes the function pick-up when the primary current is at 200 mA (see the image below). © Arcteq Relays Ltd...
  • Page 47 The measured current amplitude does not match one of the measured phases./ Check the wiring connections between the injection device or the CTs and the relay. The calculated I0 is measured even though it should not. © Arcteq Relays Ltd...
  • Page 48 I2: 0.67 × In / -60.00 deg I0Calc: 0.67 × In / 60.00 deg Solution options: - switch the wires between the connectors 3 and 4 in the CT module - invert the polarity of IL2 ( Measurement → Transformers  →  Phase CT scaling ) © Arcteq Relays Ltd...
  • Page 49 IL3: 1.00 × In / 240.00 deg Sequence currents: I1: 0.00 × In / 0.00 deg I2: 1.00 × In / 0.00 deg I0Calc: 0.00 × In / 0.00 deg Solution: -  switch the wires between the connectors 1 and 3 in the CT module © Arcteq Relays Ltd...
  • Page 50 1…25 Nominal 0.001 100.000 The nominal current of the protected object. This setting is only visible if the option 000.000 current In "Object In p.u." has been selected in the "Scale meas. to In" setting. © Arcteq Relays Ltd...
  • Page 51 A relay feedback value; the calculated scaling factor that is the ratio between the scaling primary current and the secondary current. factor P/S Measurements The following measurements are available in the measured current channels. Table. 5.2.1. - 10. Per-unit phase current measurements. Name Range Step Description © Arcteq Relays Ltd...
  • Page 52 Table. 5.2.1. - 15. Primary residual current measurements. Name Range Step Description Primary residual 0.00…1 000 0.01 The primary fundamental frequency RMS current measurement from the current I0x 000.0 A residual current channel I01 or I02. ("Pri.Res.curr.I0x") © Arcteq Relays Ltd...
  • Page 53 000.0 A sequence current. ("Pri.Neg.seq.curr.") Primary zero sequence 0.00…1 000 0.01 The primary measurement from the calculated zero sequence current 000.0 A current. ("Pri.Zero seq.curr.") Table. 5.2.1. - 20. Secondary sequence current measurements. Name Range Step Description © Arcteq Relays Ltd...
  • Page 54: Frequency Tracking And Scaling

    Measurement sampling can be set to the frequency tracking mode or to the xed user- de ned frequency sampling mode. The bene t of frequency tracking is that the measurements are within a pre-de ned accuracy range even when the fundamental frequency of the power system changes. © Arcteq Relays Ltd...
  • Page 55 This has been achieved by adjusting the sample rate of the measurement channels according to the measured system frequency; this way the FFT calculation always has a whole power cycle in the buffer. The measurement accuracy is further improved by Arcteq's patented calibration algorithms that calibrate the analog channels against eight (8) system frequency points for both magnitude and angle.
  • Page 56 0: Use track 0: Use De nes the start of the sampling. Sampling can begin with Start sampling with frequency track a previously tracked frequency, or with a user-set nominal ("Start smpl with") 1: Use nom frequency frequency. frequency © Arcteq Relays Ltd...
  • Page 57: General Menu

    Enables the Measurement recorder tool. The Measurement recorder 0: Disabled 0: Disabled recorder is con gured in Tools  → Misc → Measurement recorder. 1: Enabled 0: - Mimic recon gure Reload the mimic to the unit. 0: - Recon gure © Arcteq Relays Ltd...
  • Page 58: Protection Functions

    5.4. Protection functions 5.4.1. General properties of a protection function The following flowchart describes the basic structure of any protection function. The basic structure is composed of analog measurement values being compared to the pick-up values and operating time characteristics. © Arcteq Relays Ltd...
  • Page 59 ). The reset ratio of 97 % is built into the function and is always relative to the value. If a function's pick-up characteristics vary from this description, they are de ned in the function section in the manual. Figure. 5.4.1. - 48. Pick up and reset. © Arcteq Relays Ltd...
  • Page 60 There are three basic operating modes available for the function: Instant operation: gives the trip signal with no additional time delay simultaneously with the start signal. © Arcteq Relays Ltd...
  • Page 61 The setting is active and visible when the delay type is selected to IDMT. Delay curve Delay curve series for an IDMT operation following either IEC or IEEE/ANSI series IEEE standard de ned characteristics. © Arcteq Relays Ltd...
  • Page 62 The setting is active and visible when the delay type is selected to IDMT. 0.0000… 0.0001 0.0200 250.0000 Constant C for IEEE characteristics. Figure. 5.4.1. - 51. Inverse operating time formulas for IEC and IEEE standards. © Arcteq Relays Ltd...
  • Page 63 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.1. - 52. De nite time (DT) operating characteristics. © Arcteq Relays Ltd...
  • Page 64 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.1. - 53. IEC prede ned characteristics NI, VI, LTI and EI © Arcteq Relays Ltd...
  • Page 65 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.1. - 54. IEEE/ANSI prede ned characteristics EI, LTI, NI and VI © Arcteq Relays Ltd...
  • Page 66 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.1. - 55. IEEE prede ned characteristics EI, MI and VI © Arcteq Relays Ltd...
  • Page 67 In addition to the previously mentioned delay characteristics, some functions also have delay characteristics that deviate from the IEC or IEEE standards. These functions are the following:  overcurrent stages residual overcurrent stages directional overcurrent stages directional residual overcurrent stages. © Arcteq Relays Ltd...
  • Page 68 Time calculation characteristics selection. If activated, the operating time during release counter continues until a set release time even if the pick-up element is reset. time The behavior of the stages with different release time con gurations are presented in the gures below. © Arcteq Relays Ltd...
  • Page 69 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.1. - 57. No delayed pick-up release. Figure. 5.4.1. - 58. Delayed pick-up release, delay counter is reset at signal drop-off. © Arcteq Relays Ltd...
  • Page 70 Figure. 5.4.1. - 60. Delayed pick-up release, delay counter value is decreasing during the release time. The resetting characteristics can be set according to the application. The default setting is delayed 60 ms and the time calculation is held during the release time. © Arcteq Relays Ltd...
  • Page 71: Non-Directional Overcurrent (I>; 50/51)

    The basic design of the protection function is the three-pole operation. The inputs for the function are the following: operating mode selections setting parameters digital inputs and logic signals measured and pre-processed current magnitudes.  © Arcteq Relays Ltd...
  • Page 72 The selection of the AI channel in use is made with a setting parameter. In all possible input channel variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from START or TRIP event. © Arcteq Relays Ltd...
  • Page 73 If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and the function does not process the situation further. If the START function has been activated before the blocking signal, it resets and the release time characteristics are processed similarly to when the pick- up signal is reset. © Arcteq Relays Ltd...
  • Page 74 Phase A Trip OFF 1294 NOC1 Phase B Trip ON 1295 NOC1 Phase B Trip OFF 1296 NOC1 Phase C Trip ON 1297 NOC1 Phase C Trip OFF 1344 NOC2 Start ON 1345 NOC2 Start OFF © Arcteq Relays Ltd...
  • Page 75 1425 NOC3 Phase C Trip OFF 1472 NOC4 Start ON 1473 NOC4 Start OFF 1474 NOC4 Trip ON 1475 NOC4 Trip OFF 1476 NOC4 Block ON 1477 NOC4 Block OFF 1478 NOC4 Phase A Start ON © Arcteq Relays Ltd...
  • Page 76: Non-Directional Earth Fault (I0>; 50N/51N)

    CT saturation. The operational logic consists of the following: input magnitude selection input magnitude processing saturation check threshold comparator block signal check © Arcteq Relays Ltd...
  • Page 77 Fundamental RMS measurement of sensitive residual current measurement input I02 5 ms I02TRMS TRMS measurement of coarse sensitive current measurement input I02 5 ms I0Calc Fundamental RMS value of the calculated zero sequence current from the three phase currents 5 ms © Arcteq Relays Ltd...
  • Page 78 Table. 5.4.3. - 39. Internal inrush harmonic blocking settings. Name Description Range Step Default Inrush harmonic blocking (internal-only 0: No harmonic blocking 0: No trip) 1: Yes enable/disable 0.10…50.00 0.01 0.01  harmonic block limit (Iharm/Ifund) harmonic blocking limit fund fund fund © Arcteq Relays Ltd...
  • Page 79 1730 NEF2 Trip ON 1731 NEF2 Trip OFF 1732 NEF2 Block ON 1733 NEF2 Block OFF 1792 NEF3 Start ON 1793 NEF3 Start OFF 1794 NEF3 Trip ON 1795 NEF3 Trip OFF 1796 NEF3 Block ON © Arcteq Relays Ltd...
  • Page 80: Current Unbalance (I2>; 46)

    ANSI standard time delays as well as custom parameters. The operational logic consists of the following: input magnitude selelction input magnitude processing threshold comparator block signal check time delay characteristics output processing. The inputs for the function are the following: © Arcteq Relays Ltd...
  • Page 81 The selection of the AI channel currently in use is made with a setting parameter. In all possible input channel variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from the START or TRIP event. © Arcteq Relays Ltd...
  • Page 82 The operating timers’ behavior during a function can be set for TRIP signal and also for the release of the function in case the pick-up element is reset before the trip time has been reached. There are three basic operating modes available for the function: © Arcteq Relays Ltd...
  • Page 83 Table. 5.4.4. - 44. Setting parameters for operating time characteristics. Name Range Step Default Description Selection of the delay type time counter. The selection possibilities Delay type are dependent (IDMT, Inverse De nite Minimum Time) and IDMT independent (DT, De nite Time) characteristics. © Arcteq Relays Ltd...
  • Page 84 Time calc time counter is reset after a set release time unless a pick-up element reset after is activated during this time. When disabled, the operating time counter is reset release time directly after the pick-up element reset. © Arcteq Relays Ltd...
  • Page 85 2179 CUB3 Trip OFF 2180 CUB3 Block ON 2181 CUB3 Block OFF 2240 CUB4 Start ON 2241 CUB4 Start OFF 2242 CUB4 Trip ON 2243 CUB4 Trip OFF 2244 CUB4 Block ON 2245 CUB4 Block OFF © Arcteq Relays Ltd...
  • Page 86: Harmonic Overcurrent (Ih>; 50H/51H/68H)

    (3) output signal. In the instant operating mode the function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp resolution is 1 ms. The function also provides a resettable cumulative counter for the START, TRIP and BLOCKED events. © Arcteq Relays Ltd...
  • Page 87 The magnitudes (RMS) of phase L1 (A) current components: - Fundamental  harmonic harmonic harmonic harmonic IL1FFT 5 ms  harmonic th  harmonic th  - 11 harmonic - 13  harmonic - 15  harmonic th  - 17 harmonic - 19 harmonic. © Arcteq Relays Ltd...
  • Page 88 The selection of the AI channel, the monitored harmonic, and the monitoring type (per unit or percentage of fundamental frequency) is made with setting parameters. In all possible input channel variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from START or TRIP event. © Arcteq Relays Ltd...
  • Page 89 Table. 5.4.5. - 50. Pick-up settings. Name Range Step Default Description Pick-up setting 0.05…2.00 × I 0.01 × I 0.20 × I (per unit monitoring) Pick-up setting Ih/IL 5.00…200.00 % 0.01 % 20.00 % (percentage monitoring) © Arcteq Relays Ltd...
  • Page 90 2368 HOC1 Start ON 2369 HOC1 Start OFF 2370 HOC1 Trip ON 2371 HOC1 Trip OFF 2372 HOC1 Block ON 2373 HOC1 Block OFF 2432 HOC2 Start ON 2433 HOC2 Start OFF 2434 HOC2 Trip ON © Arcteq Relays Ltd...
  • Page 91: Circuit Breaker Failure Protection (Cbfp; 50Bf)

    The outputs of the function are CBFP START, RETRIP, CBFP ACT and BLOCKED signals. The circuit breaker failure protection function uses a total of eight (8) separate setting groups which can be selected from one common source. Additionally, the function's operating mode can be changed via setting group selection. © Arcteq Relays Ltd...
  • Page 92 Description Time base IL1RMS Fundamental RMS measurement of phase L1 (A) current 5 ms IL2RMS Fundamental RMS measurement of phase L2 (B) current 5 ms IL3RMS Fundamental RMS measurement of phase L3 (C) current 5 ms © Arcteq Relays Ltd...
  • Page 93 The pick-up activation of the function is not directly equal to the START signal generation of the function. The START signal is allowed if the blocking condition is not active. There is no delay between the activation of the monitored signal and the activation of the pick-up when using binary signals. © Arcteq Relays Ltd...
  • Page 94 CBFP starts the timer. This setting de nes how long the starting condition has to CBFP 0.200 s 1800.000 s last before the CBFP signal is activated. The following gures present some typical cases of the CBFP function. © Arcteq Relays Ltd...
  • Page 95 The CBFP signal is wired normally from its device output contact to the incomer breaker. Below are a few operational cases regarding the various applications. © Arcteq Relays Ltd...
  • Page 96 CBFP is also sent to the incomer breaker. If the primary protection function clears the fault, both counters (Retrip and CBFP) are reset as soon as the measured current is below the threshold settings. © Arcteq Relays Ltd...
  • Page 97 This con guration allows the CBFP to be controlled solely on current-based functions and other function trips can be excluded from the CBFP functionality. © Arcteq Relays Ltd...
  • Page 98 (RETRIP and CBFP) are reset as soon as the measured current is below the threshold settings and the tripping signal is reset. This con guration allows the CBFP to be controlled solely on current-based functions with added security from current monitoring. Other function trips can also be included to the CBFP functionality. © Arcteq Relays Ltd...
  • Page 99 Probably the most common application is when the device's trip output controls the circuit breaker trip coil and a single, dedicated CBFP contact controls the CBFP. Below are a few operational cases regarding the various applications and settings of the CBFP function. © Arcteq Relays Ltd...
  • Page 100 CBFP is sent to the incomer breaker. If the primary protection function clears the fault, the counter for CBFP resets as soon as the measured current is below the threshold settings. © Arcteq Relays Ltd...
  • Page 101 This con guration allows the CBFP to be controlled solely on current-based functions and other function trips can be excluded from the CBFP functionality. © Arcteq Relays Ltd...
  • Page 102 CBFP counter is reset as soon as the measured current is below the threshold settings and the tripping signal is reset. This con guration allows the CBFP to be controlled solely on current-based functions with added security from current monitoring. Other function trips can also be included to the CBFP functionality. © Arcteq Relays Ltd...
  • Page 103 AQ-M210 Instruction manual Version: 2.01 Device is con gured as a dedicated CBFP unit. Figure. 5.4.6. - 75. Device is con gured as a dedicated CBFP unit. © Arcteq Relays Ltd...
  • Page 104 The user can select the status ON or OFF for messages in the main event buffer. The triggering event of the function (RETRIP, CBFP-ACTIVATED or BLOCKED) is recorded with a time stamp and with process data values. © Arcteq Relays Ltd...
  • Page 105: Restricted Earth Fault/Cable End Differential (I0D>; 87N)

    The outputs of the function are TRIP and BLOCKED signals. The function uses a total of eight (8) separate setting groups which can be selected from one common source. The operating mode of the function can be changed via setting group selection. © Arcteq Relays Ltd...
  • Page 106 Fundamental RMS measurement of phase L1 (A) current 5 ms IL2RMS Fundamental RMS measurement of phase L2 (B) current 5 ms IL3RMS Fundamental RMS measurement of phase L3 (C) current 5 ms I01RMS Fundamental RMS measurement of residual input I01 5 ms © Arcteq Relays Ltd...
  • Page 107 1.00 Turnpoint Setting for rst turn point in the bias axe of the differential characteristics. 50.00 × I × I × I 0.01… 0.01 Slope 1 10.00 % Setting for the rst slope of the differential characteristics. 150.00 % © Arcteq Relays Ltd...
  • Page 108 The equations for the differential characteristics are the following: Figure. 5.4.7. - 79. Differential current (the calculation is based on user-selected inputs and direction). Figure. 5.4.7. - 80. Bias current (the calculation is based on the user-selected mode). Figure. 5.4.7. - 81. Characteristics settings. © Arcteq Relays Ltd...
  • Page 109 When the current natural unbalance is compensated in this situation, the differential settings may be set to be more sensitive and the natural unbalance does not, therefore, affect the calculation. Figure. 5.4.7. - 83. Cable end differential when a fault occurs. © Arcteq Relays Ltd...
  • Page 110 TRIP-activated and BLOCKED signals. The user can select the status ON or OFF for messages in the main event buffer. The triggering event of the function (TRIP-activated or BLOCKED) is recorded with a time stamp and with process data values. © Arcteq Relays Ltd...
  • Page 111: Motor Status Monitoring

    The signals can be used in indication or in application logics. They are also the basis of the events the function generates (if so chosen). The following gure presents a simpli ed function block diagram of the motor status monitoring function. © Arcteq Relays Ltd...
  • Page 112 Figure. 5.4.8. - 86. Simpli ed function block diagram of the motor status monitoring function. The function's outputs are dependent on the motor data the user has set. The following two diagram present the function's outputs in various situations. Figure. 5.4.8. - 87. Activation of the function's outputs. © Arcteq Relays Ltd...
  • Page 113 The following gure presents how the START signals behave during s motor start-up. Also note that the Motor starting signal can be used to block the overcurrent stage. © Arcteq Relays Ltd...
  • Page 114 LOGIC_OUT2 signal (for example) to change the active setting group of the I> function to operate instantly. Picture 2 (bottom left). The LOGIC_OUT1 signal is connected to the I> blocking input (NOC1, rst stage overcurrent) function to block the stage in motor start-ups. © Arcteq Relays Ltd...
  • Page 115 This setting is used for automatic curve selection and 6.0 x I starting (Tm>; 49M) calculation. Also, the nominal starting capacity calculation current - Motor start is based on this value. monitoring (Ist>; 48) - Load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 116 If the measured current exceeds this setting limit it is rotor current - Motor start considered to be overcurrent fault and corresponding monitoring measures can be applied to disconnect the feeder and (Ist>; 48) motor from the supply. - Load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 117 If the (Tm>; 49M) service factor is not known, this parameter should be left at its default setting of 1.00 x I © Arcteq Relays Ltd...
  • Page 118 The number of allowed starts per x hours for a hot motor. start protection (N>; 48) - Motor status monitoring - Frequent The number of hours when the parameters of the number Starts in hours 1…100 h start of allowed starts (hot and cold) apply. protection (N>; 48) © Arcteq Relays Ltd...
  • Page 119 Table. 5.4.8. - 66. Event codes. Event number Event channel Event block name Event code Description 3969 MST1 Motor Stopped OFF 3970 MST1 Motor Starting ON 3971 MST1 Motor Starting OFF 3972 MST1 Motor Running ON © Arcteq Relays Ltd...
  • Page 120: Motor Start/Locked Rotor Monitoring (Ist>; 48/14)

    Ist> function. The user can set both the allowed starting time and the speed switch input. The speed switch may be required by some high-mass applications when the start-up may last longer; the user should check and ensure that the motor is actually accelerating instead of standing still with its rotor locked. © Arcteq Relays Ltd...
  • Page 121 Ist> function for various situations. It is advised that the speed switch –if available–  is also used for the motor start monitoring, especially when the motor has a high load when starting, thus making the start-up take very long. © Arcteq Relays Ltd...
  • Page 122 If the starting of the motor takes longer than the function's set value, the function trips the breaker and halts the starting process; if the motor cannot start normally there is something wrong with the application. © Arcteq Relays Ltd...
  • Page 123 If the speed switch is in use while a similar situation happens (that is, that the motor starting is taking longer than it should), the speed switch ensures that the start-up of the motor is still going ne and the function lets the starting process continue. © Arcteq Relays Ltd...
  • Page 124 If the motor start-up with a speed switch exceeds the allowed safe stall time of the motor speci cations, the function trips. © Arcteq Relays Ltd...
  • Page 125 The function monitors either given de nite time, or the I value and the speed switch input. If given time is exceeded during the stall time the function initiates tripping of the motor from the stall condition. © Arcteq Relays Ltd...
  • Page 126 Motor In - Motor start selects Object In in the CT settings, this value should be 1.00. If Scaled monitoring scaled to the CT nominal, this value may vary. (Ist>; 48/14) - Undercurrent (I<; 37) Mechanical jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 127 3.5 x I rotor - Motor start automatic curve selection and the control only short time current monitoring constant (stall) are in use. (Ist>; 48/14) Mechanical jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 128 (Ist>; 48/14) Mechanical jam protection (Im>; 51M) - Motor status monitoring - Machine thermal overload protection overload 0.1...5000 (Tm>; 49M) 0.1 A The motor's maximum overload current in amperes. current - Motor start monitoring (Ist>; 48/14) Mechanical jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 129 The polarity of the speed switch signal, normally open ("NO") or normally Speed SW 0: NO 0: NO closed ("NC"). This setting is visible only if the "Speed switch in use" setting NO/NC 1: NC is active. © Arcteq Relays Ltd...
  • Page 130 3659 LCR1 Max cap Trip OFF 3660 LCR1 Blocked ON 3661 LCR1 Blocked OFF The function registers its operation into the last twelve (12) time-stamped registers. The table below presents the structure of the function's register content. © Arcteq Relays Ltd...
  • Page 131: Frequent Start Protection (N>; 66)

    (in hours) is then subtracted from this sum. This way the start counter can be applied to follow the motor's thermal status and the number of starts per hour accurately. © Arcteq Relays Ltd...
  • Page 132 In each start the counter is increased by this product which is then in every cycle deduct by starts/given time divided by program cycle time. This way the start-up counter can be precisely set for each motor. © Arcteq Relays Ltd...
  • Page 133 The following table shows the other functions that also use these settings. If these settings are edited through the frequent start protection function's setting view, they change in all other mentioned functions at the same time. Table. 5.4.10. - 72. Motor data settings. Protection Name Range Step Default Description functions © Arcteq Relays Ltd...
  • Page 134 The number of allowed starts per x hours for a cold motor. cold start protection (N>; 48) - Motor status monitoring Starts 1…100 - Frequent The number of allowed starts per x hours for a hot motor. when hot start protection (N>; 48) © Arcteq Relays Ltd...
  • Page 135 Date and time Event code Inhibit time on Start count start dd.mm.yyyy 3584-3589 If on, it shows how long the Time elapsed from last Starts used at the hh:mm:ss.mss Descr. inhibit is active starting triggering moment © Arcteq Relays Ltd...
  • Page 136: Undercurrent (I<; 37)

    RMS measurements. A -20 ms averaged value of the selected magnitude is used for pre-fault data registering. Table. 5.4.11. - 76. Measurement inputs of the I< function. Signal Description Time base IL1RMS Fundamental RMS measurement of phase L1 (A) current 5 ms © Arcteq Relays Ltd...
  • Page 137 No load overload condition when the current is below this setting value. Also, when 0.2 x I current< protection the current is below this value, the  undercurrent protection stage (Tm>; 49M) is locked. Undercurrent (I<; 37) © Arcteq Relays Ltd...
  • Page 138 The triggering event of the function (START, TRIP or BLOCKED) is recorded with a time stamp and with process data values. Table. 5.4.11. - 79. Event codes. Event number Event channel Event block name Event code Description © Arcteq Relays Ltd...
  • Page 139: Mechanical Jam Protection (Im>; 51M)

    START and TRIP events simultaneously with an equivalent time stamp. The time stamp resolution is 1 ms. The function also provides a cumulative counter for the START, TRIP and BLOCKED events. The following gure presents a simpli ed function block diagram of the load jam protection function. © Arcteq Relays Ltd...
  • Page 140 I exceeds the I value (in single, dual or all phases) it triggers the set  pick-up operation of the function. Table. 5.4.12. - 82. Motor data settings. Name Range Step Default Prot.funcs. Description © Arcteq Relays Ltd...
  • Page 141 - Motor status monitoring - Machine thermal  Nominal overload starting 0.1...5 protection 0.1 A The motor's locked rotor current in amperes. current 000.0 A (Tm>; 49M) - Motor start monitoring (Ist>; 48) - Load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 142 (Tm>; 49M) the short (stall) time constant. As long as the current stays below this current - Motor start setting value, the motor should run even when overloaded. monitoring (Ist>; 48) - Load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 143 0.01 x I 0.5 x I Pick-up setting The pick-up activation of the function is not directly equal to the START signal generation of the function. The START signal is allowed if the blocking condition is not active. © Arcteq Relays Ltd...
  • Page 144 ON event process data for START, TRIP or BLOCKED. The table below presents the structure of the function's register content. Table. 5.4.12. - 85. Register content. Fault Trigger Fault Pre-fault Trip time Date and time Event code Used SG type current current current remaining © Arcteq Relays Ltd...
  • Page 145: Machine Thermal Overload Protection (Tm>; 49M)

    = Long thermal cooling time constant (motor stopped) of the protected object (in minutes) τ = Long thermal cooling time constant (motor running) of the protected object (in minutes) = Correction factor between the times t and t © Arcteq Relays Ltd...
  • Page 146 100 % inde nitely but never exceeds it. With a single time constant model the cooling of the object follows this same behavior, the reverse of the heating when the current feeding is completely zero. © Arcteq Relays Ltd...
  • Page 147 The two diagrams below present examples of the calculation of the ambient temperature coef cient (a linear correction factor to the maximum allowed current): © Arcteq Relays Ltd...
  • Page 148 (10) pairs of temperature–correction factor pairs. The temperature and coef cient pairs are set to the Tm> function's settable correction curve. © Arcteq Relays Ltd...
  • Page 149 In practice this means that the thermal replica needs to have more settable time constants than one common constant for heating and cooling, as is the case with single time constant objects like cables. © Arcteq Relays Ltd...
  • Page 150 However, these loading factors only affect the maximum current- carrying capacity of the cable; they are not the cable's time constants. The only time constant to consider is the heating time constant, which is equal to the cooling time constant for underground cables. © Arcteq Relays Ltd...
  • Page 151 ) and heat generation that are part of its normal operation and happen every time the motor is started. The following gure describes the process of motor heating from the ambient temperature to the nominal temperature with direct-on-line (DOL) starting. © Arcteq Relays Ltd...
  • Page 152 Most motors are rotor- limited which results in the rotor heating up to dangerously high temperatures before the stator. © Arcteq Relays Ltd...
  • Page 153 Now, the heat transfer is stabilized and the heat generated in the motor is transferred to the surrounding air and the temperatures of the internal components are not increasing any longer. © Arcteq Relays Ltd...
  • Page 154 RTD elements. The rotor temperature is highest on the drive end becuase the cooling is the weakest there (as can be seen in the image below). © Arcteq Relays Ltd...
  • Page 155 1.15 and the ambient temperature was measured to be 24 degrees Celsius. In this case the motor was started without a load, and the loading was increased directly after starting in order to concentrate the heating effects of stable loading. © Arcteq Relays Ltd...
  • Page 156 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.13. - 111. Measured motor temperature in heating/cooling test. © Arcteq Relays Ltd...
  • Page 157 Motor thermal curves are useful when studying motor heating in possible overload and start-up situations. These are usually available upon request from manufacturers, and the relay operation can be set according to these. © Arcteq Relays Ltd...
  • Page 158 If the motor is continuously running with a constant load,  the cooling time constant is not that signi cant and can be estimated to be e.g. two to three times longer than the heating time constant. © Arcteq Relays Ltd...
  • Page 159 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.13. - 114. Comparing single time constant thermal replica tripping curves to given motor thermal characteristics. © Arcteq Relays Ltd...
  • Page 160 In the curve simulations the hot condition was de ned as 70 % of the thermal capacity. The following gures present the tripping and cooling curves of the thermal replica. © Arcteq Relays Ltd...
  • Page 161 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.13. - 116. Thermal tripping curves with single time constant, pre-load 0% (cold). Figure. 5.4.13. - 117. Thermal tripping curves with single time constant, pre-load 90% (hot). © Arcteq Relays Ltd...
  • Page 162 Instruction manual Version: 2.01 Figure. 5.4.13. - 118. Thermal tripping curves with dual dynamic time constants and correction factor, pre-load 0% (cold) Figure. 5.4.13. - 119. Thermal tripping curves with dual dynamic time constants and correction factor, pre-load 90% (hot). © Arcteq Relays Ltd...
  • Page 163 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.13. - 120. Thermal cooling curves, single cooling time constant. Figure. 5.4.13. - 121. Thermal cooling curves, dynamic dual time constant. © Arcteq Relays Ltd...
  • Page 164 Figure. 5.4.13. - 122. Thermal cooling curves, dynamic triple time constant (motor is running without load in the rst part with dedicated time constant). Figure. 5.4.13. - 123. NPS-biased thermal trip curves with k value of 1. © Arcteq Relays Ltd...
  • Page 165 AQ-M210 Instruction manual Version: 2.01 Figure. 5.4.13. - 124. NPS-biased thermal trip curves with k value of 3. Figure. 5.4.13. - 125. NPS-biased thermal trip curves with k value of 7. © Arcteq Relays Ltd...
  • Page 166 The time stamp resolution is 1 ms. The function also provides a resettable cumulative counter for the TRIP, ALARM 1, ALARM 2, INHIBIT and BLOCKED events. The following gure presents a simpli ed function block diagram of the machine thermal overload protection function. © Arcteq Relays Ltd...
  • Page 167 1: F compensation are shown in Celsius or in Fahrenheit. Table. 5.4.13. - 90. Settings of the motor status monitoring function and how they are shared by other protection functions. Name Range Step Default Prot.funcs. Description © Arcteq Relays Ltd...
  • Page 168 - motor status monitoring - machine thermal Nominal overload starting 0.1...5000.0 protection 0.1 A The motor's locked rotor current in amperes. current (Tm>; 49M) - motor start monitoring (Ist>; 48) - load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 169 (stall) time constant. As long as the current (Tm>; 49M) current stays below this setting value, the motor should run even when - motor start overloaded. monitoring (Ist>; 48) - load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 170 (Tm>; 49M) setting requires that the Machine thermal overload protection - motor start (Tm>) function is activated and in use. monitoring (Ist>; 48) - load jam protection (Im>; 51M) © Arcteq Relays Ltd...
  • Page 171 The setting for the long heating time constant. This setting is for "Cold" motor heat T 0…500.0 10.0 min conditions and is used when the calculated thermal capacity is below the set const value for "Hot condition theta limit". (cold) © Arcteq Relays Ltd...
  • Page 172 The cooling is typically faster in right after the motor has stopped. 0.0...3000 used 30.0 min This setting may need adjusting depending on the application for a perfect when match. This setting value is visible when the time constansts option "Multiple" is stop selected. © Arcteq Relays Ltd...
  • Page 173 This setting is visible if "Ambient lin. or curve" is set to "Linear est." temp. Amb. -50.0… The temperature reference points for the user-settable ambient temperature temp. ref. 500.0 15 deg coef cient curve. This setting is visible if "Ambient lin. or curve" is set to "Set curve". 1...10 © Arcteq Relays Ltd...
  • Page 174 If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and the function does not process the situation further. If the START function has been activated before the blocking signal, it resets and processes the release time characteristics similarly to when the pick-up signal is reset. © Arcteq Relays Ltd...
  • Page 175 TM> Setting Indicates if ambient k setting has been set wrong. Visible only when there is a setting fault. alarm Inconsistent setting of ambient k Table. 5.4.13. - 95. Measurements. Name Range Description / values © Arcteq Relays Ltd...
  • Page 176 4352 TOLM1 Alarm1 ON 4353 TOLM1 Alarm1 OFF 4354 TOLM1 Alarm2 ON 4355 TOLM1 Alarm2 OFF 4356 TOLM1 Inhibit ON 4357 TOLM1 Inhibit OFF 4358 TOLM1 Trip ON 4359 TOLM1 Trip OFF 4360 TOLM1 Block ON © Arcteq Relays Ltd...
  • Page 177: Resistance Temperature Detectors (Modbus Io) (49T)

    (2) separate alarms from one selected input. The user can set alarms and measurements to be either in degrees Celsius or Fahrenheit. The following gure shows the principal structure of the resistance temperature detection function. © Arcteq Relays Ltd...
  • Page 178 It can be invalid if communication is not working or if a sensor is broken. Settings Table. 5.4.14. - 99. Function settings for Channel x (Sx). Name Range Step Default Description 0: No Sx enable 0: No Enables/disables the selection of sensor measurements and alarms. 1: Yes © Arcteq Relays Ltd...
  • Page 179 (depends on the selected mode in "Sx Alarm2 >/<"). When the RTDs have been set, the values can be read to SCADA (or some other control system). The alarms can also be used for direct output control as well as in logics. © Arcteq Relays Ltd...
  • Page 180 S6 Alarm2 ON 4439 RTD1 S6 Alarm2 OFF 4440 RTD1 S7 Alarm1 ON 4441 RTD1 S7 Alarm1 OFF 4442 RTD1 S7 Alarm2 ON 4443 RTD1 S7 Alarm2 OFF 4444 RTD1 S8 Alarm1 ON 4445 RTD1 S8 Alarm1 OFF © Arcteq Relays Ltd...
  • Page 181 S16 Alarm2 OFF 4480 RTD2 S1 Meas Ok 4481 RTD2 S1 Meas Invalid 4482 RTD2 S2 Meas Ok 4483 RTD2 S2 Meas Invalid 4484 RTD2 S3 Meas Ok 4485 RTD2 S3 Meas Invalid 4486 RTD2 S4 Meas Ok © Arcteq Relays Ltd...
  • Page 182: Arc Fault Protection (Iarc>/I0Arc>; 50Arc/50Narc)

    This delay can be avoided by using arc protection. The arc protection card has a high speed output to trip signals faster as well as to extend the speed of arc protection. © Arcteq Relays Ltd...
  • Page 183 The arc protection card has four (4) sensor channels, and up to three (3) arc point sensors can be connected to each channel. The sensor channels support Arcteq AQ-01 (light sensing) and AQ- 02 (pressure and light sensing) units. Optionally, the protection function can also be applied with a phase current or a residual current condition: the function trips only if the light and overcurrent conditions are met.
  • Page 184 AQ-101 models are used to extend the protection of Zone 2 and to protect each outgoing feeder (Zone 3). Scheme IA1 is a single-line diagram with AQ-2xx series relays and with AQ-101 arc protection relays. The settings are for an incomer AQ-200 relay. © Arcteq Relays Ltd...
  • Page 185 ArcBI1. The next example is almost like the previous one: it is also a single-line diagram with AQ-2xx series relays. However, this time each outgoing feeder has an AQ-2xx protection relay instead of an AQ-101 arc protection relay. © Arcteq Relays Ltd...
  • Page 186 Arc protection uses samples based on current measurements. If the required number of samples is found to be above the setting limit, the current condition activates. The arc protection can alternatively use either phase currents or residual currents in the tripping decision. © Arcteq Relays Ltd...
  • Page 187 The variables the user can set are binary signals from the system. The blocking signal needs to reach the device minimum of 5 ms before the set operating delay has passed in order for the blocking to activate in time. © Arcteq Relays Ltd...
  • Page 188 4762 ARC1 Channel 1 Pressure ON 4763 ARC1 Channel 1 Pressure OFF 4764 ARC1 Channel 2 Light ON 4765 ARC1 Channel 2 Light OFF 4766 ARC1 Channel 2 Pressure ON 4767 ARC1 Channel 2 Pressure OFF © Arcteq Relays Ltd...
  • Page 189: Programmable Stage (Pgx >/<; 99)

    (10) depending on how many the application needs. In the image below, the number of programmable stages have been set to two which makes PS1 and PS2 to appear. Inactive stages are hidden until they are activated. © Arcteq Relays Ltd...
  • Page 190 1.0 and set the desired pick-up limit as the primary voltage. Similaryly, any chosen measurement value can be scaled to the desired form. © Arcteq Relays Ltd...
  • Page 191 2: Min (Mag1, Mag2, Mag3) The smallest value of the chosen signals is used in the comparison. 3: Mag1 OR Mag2 OR Mag3 Any of the signals ful lls the pick-up condition. Each signal has their own pick-up setting. © Arcteq Relays Ltd...
  • Page 192 Less than (absolute). If the absolute value of the measured signal is less than the set pick-up level, the comparison Under condition is ful lled. The user can also set a blocking limit: the comparison is not active when the measured value is (abs) < less than the set blocking limit. © Arcteq Relays Ltd...
  • Page 193  harmonic value (in p.u.) IL2 4 IL2 4 harmonic value (in p.u.) IL2 5 IL2 5 harmonic value (in p.u.) IL2 7 IL2 7 harmonic value (in p.u.) IL2 9 IL2 9 harmonic value (in p.u.) © Arcteq Relays Ltd...
  • Page 194 I02 Fundamental frequency value (in p.u.) I02 2 I02 2 harmonic value (in p.u.) I02 3 I02 3 harmonic value (in p.u.) I02 4 I02 4 harmonic value (in p.u.) I02 5 I02 5 harmonic value (in p.u.) © Arcteq Relays Ltd...
  • Page 195 I02 primary current of a current-resistive component I02CapP I02 primary current of a current-capacitive component Voltages Phase-to-phase voltages Description UL12Mag UL12 Primary voltage V UL23Mag UL23 Primary voltage V UL31Mag UL31 Primary voltage V Phase-to-neutral voltages Description UL1Mag UL1 Primary voltage V © Arcteq Relays Ltd...
  • Page 196 L2 Phase reactive power direction L2 Apparent power L3 S (kVA) Active power L3 P (kW) Reactive power L3 Q (kVar) tan L3 Phase active power direction L3 cos L3 Phase reactive power direction L3 © Arcteq Relays Ltd...
  • Page 197 Reactance X L2 secondary (Ω) RL3Sec Resistance R L3 secondary (Ω) XL3Sec Reactance X L3 secondary (Ω) Z1Pri Impedance Z L1 primary (Ω) Z2Pri Impedance Z L2 primary (Ω) Z3Pri Impedance Z L3 primary (Ω) Z1Sec Impedance Z L1 secondary (Ω) Z2Sec Impedance Z L2 secondary (Ω) © Arcteq Relays Ltd...
  • Page 198 Admittance Y L3 angle G0Pri Conductance G0 primary (mS) B0Pri Susceptance B0 primary (mS) G0Sec Conductance G0 secondary (mS) B0Sec Susceptance B0 secondary (mS) Y0Pri Admittance Y0 primary (mS) Y0Sec Admittance Y0 secondary (mS) Y0Angle Admittance Y0 angle Others © Arcteq Relays Ltd...
  • Page 199 Pick-up release delay 0.000…1800.000 s 0.005 s 0.06 s The pick-up activation of the function is not directly equal to the START signal generation of the function. The START signal is allowed if the blocking condition is not active. © Arcteq Relays Ltd...
  • Page 200 8582 PGS1 PS2 >/< Start ON 8583 PGS1 PS2 >/< Start OFF 8584 PGS1 PS2 >/< Trip ON 8585 PGS1 PS2 >/< Trip OFF 8586 PGS1 PS2 >/< Block ON 8587 PGS1 PS2 >/< Block OFF © Arcteq Relays Ltd...
  • Page 201 8623 PGS1 PS8 >/< Trip OFF 8624 PGS1 PS8 >/< Block ON 8625 PGS1 PS8 >/< Block OFF 8626 PGS1 PS9 >/< Start ON 8627 PGS1 PS9 >/< Start OFF 8628 PGS1 PS9 >/< Trip ON © Arcteq Relays Ltd...
  • Page 202: Control Functions

    The following gure presents a simpli ed function block diagram of the setting group selection function. Figure. 5.5.1. - 132. Simpli ed function block diagram of the setting group selection function. © Arcteq Relays Ltd...
  • Page 203 Disabled HMI. This parameter overrides the local control of the setting groups and it remains change Enabled on until the user disables it. © Arcteq Relays Ltd...
  • Page 204 SG requests will be processed regardless of the signal status of this setting Active group. Example applications for setting group control This chapter presents some of the most common applications for setting group changing requirements. © Arcteq Relays Ltd...
  • Page 205 The status of the Petersen coil controls whether Setting group 1 is active. If the coil is disconnected, Setting group 2 is active. This way, if the wire is broken for some reason, the setting group is always controlled by SG2. © Arcteq Relays Ltd...
  • Page 206 With a two wire connection the state of the Petersen coil can be monitored more securely. The additional logic ensures that a single wire loss will not affect the correct setting group selection. © Arcteq Relays Ltd...
  • Page 207 SG3 Disabled 4164 SG4 Enabled 4165 SG4 Disabled 4166 SG5 Enabled 4167 SG5 Disabled 4168 SG6 Enabled 4169 SG6 Disabled 4170 SG7 Enabled 4171 SG7 Disabled 4172 SG8 Enabled 4173 SG8 Disabled 4174 SG1 Request ON © Arcteq Relays Ltd...
  • Page 208 4207 SG3 Active OFF 4208 SG4 Active ON 4209 SG4 Active OFF 4210 SG5 Active ON 4211 SG5 Active OFF 4212 SG6 Active ON 4213 SG6 Active OFF 4214 SG7 Active ON 4215 SG7 Active OFF © Arcteq Relays Ltd...
  • Page 209: Object Control And Monitoring

    1 ms. The function also provides a resettable cumulative counter for OPEN, CLOSE, OPEN FAIL, and CLOSE FAIL events. The following gure presents a simpli ed function block diagram of the object control and monitoring function. © Arcteq Relays Ltd...
  • Page 210 (in and out) are active. If the 2: WDCart In status selected object type is not set to "Withdrawable circuit breaker", this 3: WDBad setting displays the "No in use" option . 4: Not in use © Arcteq Relays Ltd...
  • Page 211 Position indication of digital inputs and ("Objectx Open Status signal protection stage signals can be done by using IEC 61850 signals, GOOSE signals or In") selected logical signals. by the user (SWx) © Arcteq Relays Ltd...
  • Page 212 Determines the maximum length for a Open pulse from the output relay to the 0.02 command 500.00 0.2 s controlled object. If the object operates faster than this set time, the control pulse is pulse reset and a status change is detected. length © Arcteq Relays Ltd...
  • Page 213 The image below presents an example of an interlock application, where the closed earthing switch interlocks the circuit breaker close. © Arcteq Relays Ltd...
  • Page 214 OBJ1 Object Intermediate 2945 OBJ1 Object Open 2946 OBJ1 Object Close 2947 OBJ1 Object Bad 2948 OBJ1 WD Intermediate 2949 OBJ1 WD Out 2950 OBJ1 WD In 2951 OBJ1 WD Bad 2952 OBJ1 Open Request ON © Arcteq Relays Ltd...
  • Page 215 Close Command ON 3023 OBJ2 Close Command OFF 3024 OBJ2 Open Blocked ON 3025 OBJ2 Open Blocked OFF 3026 OBJ2 Close Blocked ON 3027 OBJ2 Close Blocked OFF 3028 OBJ2 Object Ready 3029 OBJ2 Object Not Ready © Arcteq Relays Ltd...
  • Page 216 Final trip ON 3099 OBJ3 Final trip OFF 3136 OBJ4 Object Intermediate 3137 OBJ4 Object Open 3138 OBJ4 Object Close 3139 OBJ4 Object Bad 3140 OBJ4 WD Intermediate 3141 OBJ4 WD Out 3142 OBJ4 WD In © Arcteq Relays Ltd...
  • Page 217 Close Request ON 3213 OBJ5 Close Request OFF 3214 OBJ5 Close Command ON 3215 OBJ5 Close Command OFF 3216 OBJ5 Open Blocked ON 3217 OBJ5 Open Blocked OFF 3218 OBJ5 Close Blocked ON 3219 OBJ5 Close Blocked OFF © Arcteq Relays Ltd...
  • Page 218: Indicator Object Monitoring

    ON/OFF events to the common event buffer from each of the following signals: OPEN, CLOSE, BAD and INTERMEDIATE event signals. The time stamp resolution is 1 ms. Settings Function uses available hardware and software digital signal statuses. These input signals are also setting parameters for the function. © Arcteq Relays Ltd...
  • Page 219 Close 6659 CIN1 6720 CIN2 Intermediate 6721 CIN2 Open 6722 CIN2 Close 6723 CIN2 6784 CIN3 Intermediate 6785 CIN3 Open 6786 CIN3 Close 6787 CIN3 6848 CIN4 Intermediate 6849 CIN4 Open 6850 CIN4 Close 6851 CIN4 © Arcteq Relays Ltd...
  • Page 220: Milliampere Outputs

    Table. 5.5.4. - 122. Settings for mA output channels. Name Range Step Default Description Enable mA 0: Disabled Enables and disables the selected mA output channel. If the output 0: Disabled 1: Enabled channel is disabled, the channel settings are hidden. channel © Arcteq Relays Ltd...
  • Page 221 Table. 5.5.4. - 124. Measurement values reported by mA output cards. Name Range Step Description mA in Channel 1 0.0000… 0.0001 Displayes the measured mA value of the selected input 24.0000 mA channel. mA in Channel 2 © Arcteq Relays Ltd...
  • Page 222 The Nyquist rate states that the lter time constant must be at least double the period time of the disturbance process signal. For example, the value for the lter time constant is 2 seconds for a 1 second period time of a disturbance oscillation. © Arcteq Relays Ltd...
  • Page 223 1 0: Not 0: Not Allows the user to create their own curve with up to twenty (20) curve curvepoint used used points, instead of using a linear curve between two points. 3...20 1: Used © Arcteq Relays Ltd...
  • Page 224: Programmable Control Switch

    Event block name Event code Description Switch 1 ON Switch 1 OFF Switch 2 ON Switch 2 OFF Switch 3 ON Switch 3 OFF Switch 4 ON Switch 4 OFF Switch 5 ON Switch 5 OFF © Arcteq Relays Ltd...
  • Page 225: Monitoring Functions

    1 ms. The function also provides a resettable cumulative counter for the CTS ALARM and BLOCKED events. The following gure presents a simpli ed function block diagram of the current transformer supervision function. © Arcteq Relays Ltd...
  • Page 226 Fundamental angle of phase L2 (B) current 5 ms IL3 Ang Fundamental angle of phase L3 (C) current 5 ms I01 Ang Fundamental angle of residual input I01 5 ms I02 Ang Fundamental angle of residual input I02 5 ms © Arcteq Relays Ltd...
  • Page 227 The pick-up activation of the function is not directly equal to the START signal generation of the function. The START signal is allowed if the blocking condition is not active. When the activation of the pick-up is based on binary signals, the activation happens immediately after the monitored signal is activated. © Arcteq Relays Ltd...
  • Page 228 Typical cases of current transformer supervision The following nine examples present some typical cases of the current transformer supervision and their setting effects. Figure. 5.6.1. - 143. All works properly, no faults. © Arcteq Relays Ltd...
  • Page 229 (secondary circuit fault) continues until the set time has passed, the function issues an alarm. This means that the function supervises both the primary and the secondary circuit. © Arcteq Relays Ltd...
  • Page 230 Figure. 5.6.1. - 147. Low current and heavy unbalance. If all of the measured phase magnitudes are below the I  low limit setting, the function is not activated even when the other conditions (inc. the unbalance condition) are met. © Arcteq Relays Ltd...
  • Page 231 Figure. 5.6.1. - 149. Broken secondary phase current wiring. When phase current wire is broken all of the conditions are met in the CTS and alarm shall be issued in case if the situation continues until the set alarming time is met. © Arcteq Relays Ltd...
  • Page 232 ALARM ACTIVATED and BLOCKED signals. The user can select the status ON or OFF for messages in the main event buffer. The function offers two (2) independent stages. The triggering event of the function is recorded with a time stamp and with process data values. © Arcteq Relays Ltd...
  • Page 233: Disturbance Recorder (Dr)

    Up to 20 analog recording channels and 95 digital channels are supported. The available analog channels vary according to the device type. Table. 5.6.2. - 134. Analog recording channels. Signal Description Phase current I Phase current I Phase current I Residual current I coarse* I01c © Arcteq Relays Ltd...
  • Page 234 (< 3 A). A ne signal is capable of sampling at very low currents and with high accuracy but cuts off at higher currents (I01 peaks at 15 A, I02 peaks at 8 A). © Arcteq Relays Ltd...
  • Page 235 Ux Angle Ux angle (U1, U2, U3, U4) System volt U0 ang Angle of the system voltage U0 Pos./Neg./Zero Positive/Negative/Zero sequence Ux Angle difference Ux angle difference (U1, U2, U3) Seq volt.Angle voltage angle © Arcteq Relays Ltd...
  • Page 236 B Primary neutral susceptance f meas qlty Quality of tracked frequency (Pri) Indicates which of the three voltage or Neutral Primary neutral admittance f meas from current channel frequencies is used admittance Y (Pri) by the relay. © Arcteq Relays Ltd...
  • Page 237 See calculation examples below in the section titled "Estimating the maximum length of total recording time". Table. 5.6.2. - 137. Recorder control settings. Name Range Step Default Description Recorder 0: Enabled Enables and disables the disturbance recorder function. enabled 1: Disabled Enabled © Arcteq Relays Ltd...
  • Page 238 Sets the recording length before the trigger. time 0…8 freely Selects the analog channel for recording. Please see the list of all Analog recording selectable available analog channels in the section titled "Analog and digital CH1...CH20 channels recording channels". © Arcteq Relays Ltd...
  • Page 239 The recorder is con gured by using the AQtivate software or relay HMI, and the results are analyzed with the AQviewer software (is automatically downloaded and installed with AQtivate). Registered users can download the latest tools from the Arcteq website (arcteq.
  • Page 240 ) .  Alternatively, the user can load the recordings individually ( Disturbance recorder → DR List ) from a folder in the PC's hard disk drive; the exact location of the folder is described in Tools →  Settings →  DR path . © Arcteq Relays Ltd...
  • Page 241 In the example the line-to-neutral voltages UL1, UL2 and UL3 are selected and moved to the window on the right. Con rm the selection by clicking the "OK" button. Figure. 5.6.2. - 153. Adding another plotter General use and zooming © Arcteq Relays Ltd...
  • Page 242 4098 Recorder memory cleared 4099 Oldest record cleared 4100 Recorder memory full ON 4101 Recorder memory full OFF 4102 Recording ON 4103 Recording OFF 4104 Storing recording ON 4105 Storing recording OFF 4106 Newest record cleared © Arcteq Relays Ltd...
  • Page 243: Measurement Recorder

    If the recording is done in the relay, only the recording interval needs to be set before recording can be started. AQtivate estimates the maximum recording time, which depends on the recording interval. When the measurement recorder is running, the measurements can be viewed in graph form with the AQtivate PRO software (see the image below). © Arcteq Relays Ltd...
  • Page 244 L2 Exp.React.Ind.E.kvarh Sec.Res.Curr.I01 U2Volt Pri TRMS L2 Imp.React.Ind.E.Mvarh Sec.Res.Curr.I02 U3Volt Pri TRMS L2 Imp.React.Ind.E.kvarh Sec.Calc.I0 U4Volt Pri TRMS L2 Exp/Imp React.Ind.E.bal.Mvarh Pha.Curr.IL1 TRMS Sec Pos.Seq.Volt.Pri L2 Exp/Imp React.Ind.E.bal.kvarh Pha.Curr.IL2 TRMS Sec Neg.Seq.Volt.Pri L3 Exp.Active Energy MWh © Arcteq Relays Ltd...
  • Page 245 TM> Time to 100% T Res.Curr.angle I01 System Volt UL2 mag TM> Reference T curr. Res.Curr.angle I02 System Volt UL2 mag (kV) TM> Active meas curr. Calc.I0.angle System Volt UL3 mag TM> T est.with act. curr. © Arcteq Relays Ltd...
  • Page 246 Pha.Curr.I”L1 TRMS L3 Cos(phi) L3 Diff current Pha.Curr.I”L2 TRMS 3PH Apparent Power (S) L3 Char current Pha.Curr.I”L3 TRMS 3PH Active Power (P) HV I0d> Bias current I” Pos.Seq.Curr. 3PH Reactive Power (Q) HV I0d> Diff current © Arcteq Relays Ltd...
  • Page 247: Circuit Breaker Wear

    However, the circuit breaker wear function is an independent function and it initializes as an independent instance which has its own events and settings not related to the object it is linked to. Figure. 5.6.4. - 155. Example of the circuit breaker interrupting life operations. © Arcteq Relays Ltd...
  • Page 248 Circuit breaker characteristics settings The circuit breaker characteristics are set by two operating points, de ned by the nominal breaking current, the maximum allowed breaking current and their respective operation settings. This data is provided by the circuit breaker's manufacturer. © Arcteq Relays Ltd...
  • Page 249 Let us examine the settings, using a low-duty vacuum circuit breaker (ISM25_LD_1/3) manufactured by Tavrida as an example. The image below presents the technical speci cations provided by the manufacturer, with the data relevant to our settings highlighted in red: © Arcteq Relays Ltd...
  • Page 250 With these settings, Alarm 1 is issued when the cumulative interruption counter for any of the three phases dips below the set 1000 remaining operations ("Alarm 1 Set"). Similarly, when any of the counters dips below 100 remaining operations, Alarm 2 is issued. © Arcteq Relays Ltd...
  • Page 251: Total Harmonic Distortion (Thd)

    The user can also set the alarming limits for each measured channel if the application so requires. The monitoring of the measured signals can be selected to be based either on an amplitude ratio or on the above-mentioned power ratio. The difference is in the calculation formula (as shown below): © Arcteq Relays Ltd...
  • Page 252 The time stamp resolution is 1 ms. The function also provides a resettable cumulative counter for the START, ALARM ACT and BLOCKED events. The following gure presents a simpli ed function block diagram of the total harmonic distortion monitor function. © Arcteq Relays Ltd...
  • Page 253 Step Default Description 0: CT1 De nes which current measurement module the function THD> in side 0: CT1 1: CT2 uses. Measurement De nes which available measured magnitude the function Amplitude magnitude Amplitude uses. 2: Power © Arcteq Relays Ltd...
  • Page 254 The blocking signal can also be tested in the commissioning phase by a software switch signal when the relay's testing mode "Enable stage forcing" is activated ( General → Device ). © Arcteq Relays Ltd...
  • Page 255 THD Alarm Phase OFF 3528 THD1 THD Alarm I01 ON 3529 THD1 THD Alarm I01 OFF 3530 THD1 THD Alarm I02 ON 3531 THD1 THD Alarm I02 OFF 3532 THD1 Blocked ON 3533 THD1 Blocked OFF © Arcteq Relays Ltd...
  • Page 256: Measurement Value Recorder

    , harmonic 11 , harmonic 13 h., 15 h., 17 h., 19 harmonic 15 , harmonic 17 , harmonic 19 harmonic current. The positive sequence current, the negative sequence current and the zero sequence I1, I2, I0Z current. © Arcteq Relays Ltd...
  • Page 257 The motor thermal temperature. F thermal T The feeder thermal temperature. T thermal T The transformer thermal temperature. RTD meas 1…16 The RTD measurement channels 1…16. Ext RTD meas 1…8 The external RTD measurement channels 1…8 (ADAM module). © Arcteq Relays Ltd...
  • Page 258 The user can select the status ON or OFF for messages in the main event buffer. Table. 5.6.6. - 154. Event codes. Event number Event channel Event block name Event code Description 9984 VREC1 Recorder triggered ON 9985 VREC1 Recorder triggered OFF © Arcteq Relays Ltd...
  • Page 259: System Integration

    The device supports both Modbus/TCP and Modbus/RTU communication. Modbus/TCP uses the Ethernet connection to communicate with Modbus/TCP clients. Modbus/RTU is a serial protocol that can be selected for the available serial ports. The following Modbus function types are supported: © Arcteq Relays Ltd...
  • Page 260: Modbus I/O

    Modbus I/O implementation. These are named I/O Module A, I/O Module B and I/O Module C. Each of the modules can be con gured using parameters in the following two tables. © Arcteq Relays Ltd...
  • Page 261: Iec 61850

    Time synchronization The device's current IEC 61850 setup can be viewed with the IEC61850 tool ( Tools → IEC 61850 ). By browsing the 61850 tree one can see the full list of available logical nodes in the Arcteq implementation.
  • Page 262 Additionally, if the intention is to use the GOOSE publisher service, the parameters for GCB1 and GCB2 should also be set. See the following image of the main con guration window for the basic settings and the settings for GOOSE publishing. © Arcteq Relays Ltd...
  • Page 263 Control Block with the "RCB" button. This opens a new pop-up window. The assigning can be either to unbuffered reporting (URCBs) or to buffered reporting (BRCBs). If both of the GOOSE publisher data sets are un-checked, the GOOSE publisher service is disabled (see the image below). © Arcteq Relays Ltd...
  • Page 264 Figure. 6.1.4. - 162. Data selection on the data attribute level. Settings. The general setting parameters for the IEC 61850 protocol are visible both in AQtivate and in the local HMI. The settings are described in the table below. © Arcteq Relays Ltd...
  • Page 265: Goose

    /downloads/ → AQ-200 series → Resources). 6.1.5. GOOSE Arcteq relays support both GOOSE publisher and GOOSE subscriber. GOOSE subscriber is enabled with the "GOOSE subscriber enable" parameter at Communication → Protocols → IEC 61850/GOOSE.  The GOOSE inputs are con gured using either the local HMI or the AQtivate software.
  • Page 266 ID" (should be unique for the system) and "ConfRev" (checked by the subscriber). If VLAN switches have been used to build the sub-networks, both the "VLAN priority" and the "VLAN ID" parameters must be set to match the system speci cations. © Arcteq Relays Ltd...
  • Page 267: Iec 103

    (slave) station. The IEC 103 protocol can be selected for the serial ports that are available in the device. A primary (master) station can then communicate with the Arcteq device and receive information by polling from the slave device. The transfer of disturbance recordings is not supported.
  • Page 268: Dnp3

    Selects the variation of the double point signal. 1: Var 2 0: Var 1 1: Var 2 Group 20 variation (CNTR) 0: Var 1 Selects the variation of the control signal. 2: Var 5 3: Var 6 © Arcteq Relays Ltd...
  • Page 269: Iec

    The standards IEC 60870-5-101 and IEC 60870-5-104 are closely related. Both are derived from the IEC 60870-5 standard. On the physical layer the IEC 101 protocol uses serial communication whereas the IEC 104 protocol uses Ethernet communication. The IEC 101/104 implementation works as a slave in the unbalanced mode. © Arcteq Relays Ltd...
  • Page 270  The measurement scaling coef cients are available for the following measurements, in addition to the general measurement scaling coef cient: Active energy Reactive energy Active power Reactive power Apparent power Power factor Frequency Current Residual current Voltage Residual voltage Angle © Arcteq Relays Ltd...
  • Page 271 0.01 V 200 V voltage deadband 5000.00 V measurement. Angle Determines the data reporting deadband settings for this 0.1…5.0 deg 1 deg measurement deadband measurement. Integration time 0…10 000 ms 1 ms Displays the integration time of the protocol. © Arcteq Relays Ltd...
  • Page 272: Spa

    With the Real-time signals to communication menu the user can report to SCADA measurements that are not normally available in the communication protocols mapping. Up to eight (8) magnitudes can be selected. The recorded value can be either a per-unit value or a primary value (set by the user). © Arcteq Relays Ltd...
  • Page 273 RL12, RL23, RL31 XL12, XL23, XL31 RL1, RL2, RL3 Phase-to-phase and phase-to-neutral resistances, reactances and impedances. XL1, XL2, XL3 Z12, Z23, Z31 ZL1, ZL2, ZL3 Z12Ang, Z23Ang, Z31Ang, Phase-to-phase and phase-to-neutral impedance angles. ZL1Ang, ZL2Ang, ZL3Ang © Arcteq Relays Ltd...
  • Page 274 ("Available measured values") selected category. Displays the measured value of the selected magnitude of the selected slot. -10 000 000.000…10 000 Magnitude X 0.001 000.000 The unit depends on the selected magnitude (either amperes, volts, or per-unit values). © Arcteq Relays Ltd...
  • Page 275: Connections And Application Examples

    AQ-M210 Instruction manual Version: 2.01 7. Connections and application examples 7.1. Connections AQ-M210 Figure. 7.1. - 164. AQ-M210 variant without add-on modules. © Arcteq Relays Ltd...
  • Page 276 AQ-M210 Instruction manual Version: 2.01 Figure. 7.1. - 165. AQ-M210 variant with digital input and output modules. © Arcteq Relays Ltd...
  • Page 277: Application Example And Its Connections

    AQ-M210 Instruction manual Version: 2.01 Figure. 7.1. - 166. AQ-M210 application example with function block diagram. 7.2. Application example and its connections This chapter presents an application example for the motor protection IED. As can be seen in the image below, the example application has connected the three phase currents and the residual current (I01).
  • Page 278: Two-Phase, Three-Wire Aron Input Connection

    This chapter presents the two-phase, three-wire ARON input connection for any AQ-200 series IED with a current transformer. The example is for applications with protection CTs for just two phases. The connection is suitable for both motor and feeder applications. © Arcteq Relays Ltd...
  • Page 279: Trip Circuit Supervision (95)

    (52b) even after the circuit breaker is opened. This requires a resistor which reduces the current: this way the coil is not energized and the relay output does not need to cut off the coil's inductive current. © Arcteq Relays Ltd...
  • Page 280 Figure. 7.4. - 170. Settings for a digital input used for trip circuit supervision. Non-latched outputs are seen as hollow circles in the output matrix, whereas latched contacts are painted. See the image below of an output matrix where a non-latched trip contact is used to open the circuit breaker. © Arcteq Relays Ltd...
  • Page 281 There is one main difference between non-latched and latched control in trip circuit supervision: when using the latched control, the trip circuit (in an open state) cannot be monitored as the digital input is shorted by the IED's trip output. © Arcteq Relays Ltd...
  • Page 282 Logical output can be used in the output matrix or in SCADA as the user wants. The image below presents a block scheme when a non-latched trip output is not used. Figure. 7.4. - 173. Example block scheme. © Arcteq Relays Ltd...
  • Page 283: Construction And Installation

    In eld upgrades, therefore, the add-on module must be ordered from Arcteq Relays Ltd. or its representative who can then provide the module with its corresponding unlocking code to allow the device to operate correctly once the hardware con guration has been upgraded.
  • Page 284 5DO module, it reserves the designations "OUT6", "OUT7", "OUT8", "OUT9" and "OUT10" to this slot. Again, if Slot A also has a 5DO and has therefore already reserved these designations, the device reserves the designations "OUT11", "OUT12", "OUT13", "OUT14" and "OUT15" to this slot. © Arcteq Relays Ltd...
  • Page 285: Cpu Module

    CPU module, and ve (DO6…DO10) in Slot F. These same principles apply to all non-standard con gurations in the AQ-X210 IED family. 8.2. CPU module Figure. 8.2. - 176. CPU module. Module connectors Table. 8.2. - 174. Module connector descriptions. Connector Description © Arcteq Relays Ltd...
  • Page 286 Selects whether the status of the digital input is 1 or 0 when the input DIx Polarity 0: NO 1: NC (Normally is energized. closed) DIx Activation 0.000… 0.001 0.000 s De nes the delay for the status change from 0 to 1. delay 1800.000 s © Arcteq Relays Ltd...
  • Page 287: Current Measurement Module

    1…10 A. The secondary currents are calibrated to nominal currents of 1 A and 5 A, which provide ±0.5 % inaccuracy when the range is 0.005…4 ×  I The measurement ranges are as follows: Phase currents 25 mA…250 A (RMS) © Arcteq Relays Ltd...
  • Page 288: Digital Input Module (Optional)

    DIx + 2 DIx + 3 DIx + 4 Common earthing for the rst four digital inputs. DIx + 5 DIx + 6 DIx + 7 DIx + 8 X 10 Common earthing for the other four digital inputs. © Arcteq Relays Ltd...
  • Page 289 The selection of the normal state between normally open (NO) and normally closed (NC) de nes whether or not the digital input is considered activated when the digital input channel is energized. © Arcteq Relays Ltd...
  • Page 290: Digital Output Module (Optional)

    Figure. 8.5. - 180. Digital output module (DO5) with ve add-on digital outputs. Connector Description X 1–2 OUTx + 1 (1 and 2 pole NO) X 3–4 OUTx + 2 (1 and 2 pole NO) X 5–6 OUTx + 3 (1 and 2 pole NO) © Arcteq Relays Ltd...
  • Page 291: Arc Protection Module (Optional)

    Table. 8.6. - 177. Module connections. Connector Description Light sensor channels 1…4 with positive ("+"), sensor ("S") and earth connectors. HSO1 (+, NO) Common battery positive terminal (+) for the HSOs. HSO2 (+, NO) Binary input 1 (+ pole) Binary input 1 ( – pole) © Arcteq Relays Ltd...
  • Page 292: Rtd & Ma Input Module (Optional)

    ( Control  →  Device I/O ), they can only be programmed in the arc matrix menu ( Protection  →  Arc protection → I/O  → Direct output control and HSO control ). 8.7. RTD & mA input module (optional) Figure. 8.7. - 182. RTD & mA module connectors. © Arcteq Relays Ltd...
  • Page 293 There are also two mA input channels available in the module. Please note that if the mA input channels are in use, only the rst four channels are available for RTD and TC measurements. Figure. 8.7. - 183. Different sensor types and their connections. © Arcteq Relays Ltd...
  • Page 294: Serial Rs-232 Communication Module (Optional)

    COM F – RS-232 RX Serial based communications Pin 8 COM F – Pin 9 COM F – +3.3 V output Spare power source for external equipment (45 mA) Pin 10 (spare) COM F – Pin 11 © Arcteq Relays Ltd...
  • Page 295: Lc 100 Mbps Ethernet Communication Module (Optional)

    62.5/125 μm or 50/125 μm multimode (glass). COM D: Wavelength 1300 nm. The optional LC 100 Mbps Ethernet card supports both HSR and PRP protocols. The card has two PRP/HSR ports, which are 100 Mbps ber ports. © Arcteq Relays Ltd...
  • Page 296: Double St 100 Mbps Ethernet Communication Module (Optional)

    RSTP (Rapid Spanning Tree Protocol) supporting Ethernet switches. Each ring can only contain AQ-200 series devices. Any third party devices must be connected to separate ring.   For other redundancy options, see the 100LC option card. © Arcteq Relays Ltd...
  • Page 297 AQ-M210 Instruction manual Version: 2.01 Figure. 8.10. - 187. Ring connection example. Please note that third party devices should be connected in a separate ring. Figure. 8.10. - 188. Multidrop connection example. © Arcteq Relays Ltd...
  • Page 298: Double Rj45 10/100 Mbps Ethernet Communication Module (Optional)

    RSTP (Rapid Spanning Tree Protocol) supporting Ethernet switches. Each ring can only contain AQ-200 series devices. Any third party devices must be connected to separate ring.   For other redundancy options, see the 100LC option card. © Arcteq Relays Ltd...
  • Page 299 AQ-M210 Instruction manual Version: 2.01 Figure. 8.11. - 190. Ring connection example. Please note that third party devices should be connected in a separate ring. Figure. 8.11. - 191. Multidrop connection example. © Arcteq Relays Ltd...
  • Page 300: Milliampere (Ma) I/O Module (Optional)

    (¼) of the rack's width, meaning that a total of four devices can be installed to the same rack next to one another. © Arcteq Relays Ltd...
  • Page 301 AQ-M210 Instruction manual Version: 2.01 The gures below describe the device dimensions ( rst gure), the device installation (second), and the panel cutout dimensions and device spacing (third). Figure. 8.13. - 193. Device dimensions. © Arcteq Relays Ltd...
  • Page 302 AQ-M210 Instruction manual Version: 2.01 Figure. 8.13. - 194. Device installation. © Arcteq Relays Ltd...
  • Page 303 AQ-M210 Instruction manual Version: 2.01 Figure. 8.13. - 195. Panel cutout dimensions and device spacing. © Arcteq Relays Ltd...
  • Page 304: Technical Data

     < ±0.5 % < ±0.2° (I> 0.05 A) Angle measurement inaccuracy < ±1.0° (I≤ 0.05 A) Burden (50/60Hz) <0.1 VA Transient overreach <5 % Fine residual current input (I02) Rated current I 0.2 A (con gurable 0.2…10 A) © Arcteq Relays Ltd...
  • Page 305: Frequency Measurement

    Rated auxiliary voltage 85…265 V (AC/DC) < 7 W Power consumption < 15 W Maximum permitted interrupt time < 60 ms with 110 VDC DC ripple < 15 % Terminal block connection Terminal block Phoenix Contact MSTB 2,5/5-ST-5,08 © Arcteq Relays Ltd...
  • Page 306: Cpu Communication Ports

    Port Port media Copper Ethernet RJ-45 Number of ports Features IEC 61850 IEC 104 Modbus/TCP Port protocols DNP3 Telnet Data transfer rate 100 MB System integration Can be used for system protocols and for local programming © Arcteq Relays Ltd...
  • Page 307: Cpu Digital Inputs

    Make and carry 0.5 s 30 A Make and carry 3 s 15 A Breaking capacity, DC (L/R = 40 ms) at 48 VDC at 110 VDC 0.4 A at 220 VDC 0.2 A Control rate 5 ms Settings © Arcteq Relays Ltd...
  • Page 308: Option Cards

    Pick-up delay Software settable: 0…1800 s Drop-off delay Software settable: 0…1800 s Polarity Software settable: Normally On/Normally Off Terminal block connection Terminal block Phoenix Contact MSTB 2,5/5-ST-5,08 Solid or stranded wire 2.5 mm Maximum wire diameter © Arcteq Relays Ltd...
  • Page 309: Digital Output Module

    Make and carry 3 s Breaking capacity, DC (L/R = 40 ms) 1 A/110 W Control rate 5 ms Operation delay <1 ms Polarity Normally Off Contact material Semiconductor Terminal block connection Terminal block Phoenix Contact MSTB 2,5/5-ST-5,08 © Arcteq Relays Ltd...
  • Page 310: Milliampere Module (Ma Out & Ma In)

    Source signal scaling range -1 000 000.000…1 000 000.0000, setting step 0.0001 9.1.3.5. RTD & mA input module Table. 9.1.3.5. - 194. Technical data for the RTD & mA input module. Channels 1-8 2/3/4-wire RTD and thermocouple sensors © Arcteq Relays Ltd...
  • Page 311: Serial Ber Communication Module

    50/125 μm or 62.5/125 μm multimode (glass) 9.1.4. Display Table. 9.1.4. - 197. Technical data for the HMI LCD display. Dimensions and resolution Number of dots/resolution 320 x 160 Size 84.78 × 49.90 mm (3.34 × 1.96 in) Display Type of display Color Monochrome © Arcteq Relays Ltd...
  • Page 312: Functions

    Instant reset time and start-up reset <50 ms Note! The release delay does not apply to phase-speci c tripping. 9.2.1.2. Non-directional earth fault (I0>; 50N/51N) Table. 9.2.1.2. - 199. Technical data for the non-directional earth fault function. Input signals © Arcteq Relays Ltd...
  • Page 313: Current Unbalance (I2>; 46/46R/46L)

    I02 is 1…20 mA. The pick-up is tuned to be more sensitive and the operation times vary because of this. 9.2.1.3. Current unbalance (I2>; 46/46R/46L) Table. 9.2.1.3. - 200. Technical data for the current unbalance function. Input signals Current input magnitudes Phase current fundamental frequency RMS Pick-up © Arcteq Relays Ltd...
  • Page 314: Harmonic Overcurrent (Ih>; 50H/51H, 68)

    5.00…200.00 %, setting step 0.01 % (Ih/IL) Inaccuracy: <0.03 × I  (2 - Starting × I - Starting × Ih/IL <0.03 × I tolerance to Ih (2 Operation time De nite time function operating time setting 0.00…1800.00 s, setting step 0.005 s © Arcteq Relays Ltd...
  • Page 315: Circuit Breaker Failure Protection (Cbfp; 50Bf/52Bf)

    ±15 mA (0.005…4.0 × I Operation time De nite time function operating time setting 0.050…1800.000 s, setting step 0.005 s Inaccuracy: - Current criteria (I  ratio 1.05→) ±1.0 % or ±55 ms ±15 ms - DO or DI only © Arcteq Relays Ltd...
  • Page 316: Restricted Earth Fault/Cable End Differential (I0D; 87N)

    - Long cool T const (stop) 0.0…500.0 min, setting step 0.1 min - Short cool T const (stop) 0.0…500.0 min, setting step 0.1 min - Short cool T in use time 0.0…3000.0 min, setting step 0.1 min © Arcteq Relays Ltd...
  • Page 317: Motor Start/Locked Rotor Monitoring (Ist>; 48/14)

    <55 ms Reset Reset ratio 97 % of the pick-up current setting Reset time setting 0.010 …150.000 s, step 0.005 s Inaccuracy: Reset time ±1.0 % or ±35 ms Instant reset time and start-up reset <55 ms © Arcteq Relays Ltd...
  • Page 318: Frequent Start Protection (N>; 66)

    <50 ms Reset Reset ratio 103 % of the pick-up current setting Reset time setting 0.010…150.000 s, step 0.005 s Inaccuracy: Reset time ±1.0 % or ±35 ms Instant reset time and start-up reset <50 ms © Arcteq Relays Ltd...
  • Page 319: Mechanical Jam Protection (Im>; 51M)

    Operating time Typically <500 ms 9.2.1.13. Arc fault protection (IArc>/I0Arc>; 50Arc/50NArc) (optional) Table. 9.2.1.13. - 210. Technical data for the arc fault protection function. Input signals Sample-based phase current measurement Current input magnitudes Sample-based residual current measurement © Arcteq Relays Ltd...
  • Page 320: Control Functions

    <5 ms from receiving the control signal 9.2.2.2. Object control and monitoring Table. 9.2.2.2. - 212. Technical data for the object control and monitoring function. Signals Digital inputs Input signals Software signals Close command output Output signals Open command output © Arcteq Relays Ltd...
  • Page 321: Monitoring Functions

    9.2.3.2. Disturbance recorder Table. 9.2.3.2. - 214. Technical data for the disturbance recorder function. Recorded values Recorder analogue 0…20 channels channels Freely selectable 0…95 channels Recorder digital channels Freely selectable analogue and binary signals 5 ms sample rate (FFT) © Arcteq Relays Ltd...
  • Page 322: Circuit Breaker Wear Monitor

    ±0.5 % or ±10 ms - Instant operating time, when I  ratio > 3 Typically <20ms - Instant operating time, when I  ratio 1.05 < Typically <25 ms  < 3 Reset Reset time Typically <10 ms Reset ratio 97 % © Arcteq Relays Ltd...
  • Page 323: Tests And Environmental

    13.2…100 Hz, ± 1.0 g Shock and bump test EN 60255-1,EN 60255-27, IEC 60255-21-2 20 g, 1 000 bumps/dir. Table. 9.3. - 220. Environmental tests. Damp heat (cyclic) EN 60255-1, IEC 60068-2-30 Operational: +25…+55 °C, 93…97 % (RH), 12+12h Dry heat © Arcteq Relays Ltd...
  • Page 324 Height: 117 mm (4U) Dimensions Width: 127 mm (¼ rack) Depth: 174 mm (no cards & connectors) Weight 1.5 kg With packaging (gross) Height: 170 mm Dimensions Width: 242 mm Depth: 219 mm Weight 2 kg © Arcteq Relays Ltd...
  • Page 325: Ordering Information

    AQ-M210 Instruction manual Version: 2.01 10. Ordering information Accessories Order code Description Note Manufacturer AQ-ACC-ADAM4016 ADAM-4016 RTD 6 ch RTD module with Modbus Requires external Advanced Co. Ltd. (Pt100/1000, Balco500, Ni) power module © Arcteq Relays Ltd...
  • Page 326 Arcteq Ltd. (8000 Lux threshold) AQ-02B Pressure and light point sensor unit Max. cable length 200m Arcteq Ltd. (25000 Lux threshold) AQ-02C Pressure and light point sensor unit Max. cable length 200m Arcteq Ltd. (50000 Lux threshold) © Arcteq Relays Ltd...
  • Page 327: Contact And Reference Information

    Wolf ntie 36 F 12 65200 Vaasa, Finland Contacts Phone: +358 10 3221 370 Fax: +358 10 3221 389 URL: url: www.arcteq. email sales: sales@arcteq. Technical support site: https://arcteq. /support-landing/ Technical support: +358 10 3221 388 (EET 8:00 – 16:00) © Arcteq Relays Ltd...

Table of Contents