EMS controllers then update the self-learning matrix depending on how much activity is detected in
each 30 minute period as follows:
If the EMS controller detects activity during a 30 minute period, the EMS controller changes the state from mon-
l
itor (1) to ready (2)
If the EMS controller does not detect activity, the EMS controllers changes the state from monitor (1) to
l
saving (0).
Note:
The amount of activity required to change the state from monitor (1) to ready (2) depends on the setting of the
l
AF
activity frequency (
Therefore, at the end of day 1, (first 24 hours), the EMS controller has set all the 30 minutes to ready
(2) or saving (0) depending the outlet activity pattern as shown in the example matrix:
EMS controllers then copy the pattern learnt from day 1 to the remaining six days of the self-learning
matrix, as shown in the following example matrix:
) parameter.