The table below describes the values for activity frequency (AF).
Value
Name
00
Low frequency
01
Medium frequency
02
High frequency
03
Automatic
Note:
AF
If
is set to 3, the EMS controller must run continuously for 48 hours to set the value of the activity frequency.
l
If power is lost during the 48 hour period, the EMS controller restarts the 48 hour period.
The EMS controller must complete the 48 hour period to determine the activity frequency before starting the
1-day or 7-day learning period.
9.32
Motion sensor enable (Sn)
The table below details the motion sensor enable (S n) parameter.
Display
Description
Enables the input from the motion sensor.
Considerations
Must be disabled if a motion sensor is not fitted.
Range
00 (disabled) or 01 (enabled)
Global default
01 (enabled)
9.33
Saving temperature disable (PEr)
The table below details the saving temperature disable (PE r) parameter.
Display
Disables the saving mode temperature so that the EMS controller maintains
Description
the ready mode temperature at all times.
Disabling the saving mode temperature does not affect the light functionality.
Considerations
None
Range
00 (off) or 01 (on)
Global default
00 (off)
9.34
Learning period (LP)
The table below details the learning period (L P) parameter.
Description
1 door opening or 1 motion count
1 door opening or 3 motion counts
2 door openings or 6 motion counts
The EMS controller runs continuously for 48 hours in the
ready mode. After 48 hours, the EMS controller sets the value
of the activity frequency to 0, 1, or 2.
77 of 86
27 February 2014