INSTALLATION GUIDE
ThermShield MF(1 & 2) Installation Method
Contents
Applies to... .......................................... 1
Health and safety .................................. 1
CE Installation Method Overview ..................... 2
frame .................................................................... 6
frame (circular) .................................................... 9
frame .................................................................. 10
Periodic maintenance .............................14
Actuators ............................................15
Wiring Diagrams ...................................18
Dimensional Data ................................. 20

Applies to...

• Actionair ThermShield FD
• Actionair ThermShield FD-C

Health and safety

• This process must be undertaken by competent
persons. More than one person may be required to
ensure the safe handling of large dampers and other
materials. Use must be made of access equipment to
ensure unsafe practices are not used to approach walls
or difficult access areas.
• Standard site PPE should be used (minimum steel toe
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as defined by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
• All waste materials should be collected and disposed of
as defined by the relevant supplier.
• Actuators: All wiring should be carried out in
accordance with the wiring details provided by the IEE
and BS regulations and by a competent person. Care
must be taken when installing and inspecting dampers,
as they are likely to close without warning due to
loss of electrical power or a temperature rise in the
ductwork. This is their prime function. Do not insert
any items, fingers or limbs between the blades. Larger
dampers must be handled in accordance with current
regulations and good practice due to weight.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Actionair ThermShield MF and is the answer not in the manual?

Questions and answers

Summary of Contents for Swegon Actionair ThermShield MF

  • Page 1: Table Of Contents

    INSTALLATION GUIDE ThermShield MF(1 & 2) Installation Method Contents Applies to... • Actionair ThermShield FD Applies to..........1 • Actionair ThermShield FD-C Health and safety ........1 Health and safety CE Installation Method Overview ..... 2 Fire damper installation square openings ..3 •...
  • Page 2: Ce Installation Method Overview

    Fire/Smoke damper. • Under the Fire Damper Product standard BS EN 15650 our Fire Damper products are tested to BS EN 1366-2 and classified under BS EN 13501-3. Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 3: Fire Damper Installation Square Openings

    (distance from wall limit to the end of fire damper is 125mm). This does not apply for Applique / MF2 kit installations. Check the operation of the fire damper before commencing the installation! 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 4: Fire Damper Installation Circular Openings

    (distance from wall limit to the end of fire damper is 215mm). This does not apply for Applique/ MF1/ MF2 kit installations. Check the operation of the fire damper before commencing the installation! Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 5: Rigid Wall Installation Mf2 Installation Frame

    Damper blade must be closed during installation! 2. Insert fire damper into wall and fasten with screws (12 pcs, 6x160 mm) Ensure that the damper is sufficiently supported. Test the operation of the damper blade! 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 6: Flexible Wall Installation Mf2 Installation Frame

    Damper blade must be closed during installation! 2. Fasten the fire damper with screws. (12 pcs, 6x160 Ensure that the damper is sufficiently supported. Test the operation of the damper blade! Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 7: Shaft Wall Installation Mf2 Installation Frame

    3. Insert fire damper into wall and fasten with screws (12 pcs, 6x160 mm). Ensure that the damper is sufficiently supported. Test the operation of the damper blade! = N MP = DETAIL C SCALE 1 : 5 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 8: Minimal Seperation Dampers (Square)

    Before filling the gap between wall and fire damper, close the damper blade and install the wooden supports as seen in the drawings below. Place the wooden support as close as possible to the fire damper blade! Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 9: Rigid Wall Installation Mf1/Mf2 Installation Frame (Circular)

    2. Place the damper in the opening. 3. Fasten the fire damper with screws FDC25- 4pcs, 6x160 mm, FDC40- 12pcs, 6x160 mm. Ensure that the damper is sufficiently supported. Test the operation of the damper blade! 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 10: Flexible Wall Installation Mf1/Mf2 Installation Frame

    2. Place the fire damper in the opening. 3. Fasten the fire damper with screws FDC25- 4pcs, 6x160 mm, FDC40- 12pcs, 6x160 mm. Ensure that the damper is sufficiently supported. Test the operation of the damper blade! Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 11: Shaft Wall Installation Mf2 Installation Frame

    * Dimension G depending of the damper type is: G=10 mm for FDC25 G=25 mm for FDC40 Ensure that the damper is sufficiently supported. Test the operation of the damper blade! 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 12: Minimal Seperation Dampers (Circular)

    30 mm between wall/ceiling and 30 mm from other dampers. 2. Insert the fire dampers into the wall and fill the space between the casings with mineral wool (140kg/m³) up to flanges. Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 13 Subframe should be prepared according to the drawings below. FDC25 FDC40 (d+80)/2 (d+80) (d+80) FDC25-MF1 FDC40-MF2 (d+25)/2 (d+10) (d+25) 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 14: Periodic Maintenance

    • A comprehensive example of the maintenance procedure is given in Annex D of the standard. Some Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 15: Actuators

    Ambient temperature min. -30 °C, max. 50 °C range 95% r.h., Ambient humidity non-condensing Service life Min. 30,000 cycles Maintenance Maintenance-free (see page 14) Weight R25/R40 0,5 kg / 1,7 kg 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 16 < 120 s Running spring time ~ 20 s ~ 20 s ~ 20 s ~ 20 s ~16 s ~16 s return Ambient temperature min. -30 °C, max. 50 °C range Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 17 Min. 10,000 cycles @ 10 s, min Min. 10,000 cycles @ 10 s, min Service life 1000 cycles @ 1s 1000 cycles @ 1s Maintenance Maintenance-free Maintenance-free Weight 3,5 kg 3,5 kg 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 18: Wiring Diagrams

    (ambient temperature) max. 72 °C Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 19 Thermal fuse is located on the underside of the fire damper. side as Belimo actuator (below). same side as Belimo actuator. Bottom View Side view Side view Electric Actuator Schischek ExMax 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 20: Dimensional Data

    ThermShield MF(1 & 2) Installation Guide Dimensional Data Square FD25-MF2-R B+196 B+60 123,5 103,5 FD25-MF2-M 123,5 B+60 103,5 B+196 FD40-MF2-M 123,5 B+60 103,5 B+196 Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 21 ThermShield MF(1 & 2) Installation Guide Dimensional Data Circular FDC25-MF1-R Ød +118 Dn+118 Dn+118 FDC25-MF1-M Ød +118 Dn+118 D n + 1 1 8 3 8 0 FDC25-MF2-R Ød +118 103,5 65 20210615 - L00014 Swegon reserves the right to alter specifications.
  • Page 22 ThermShield MF(1 & 2) Installation Guide FDC25-MF2-M Ød +118 103,5 65 FDC40-MF2-M Ød +120 103,5 Swegon reserves the right to alter specifications. 20210615 - L00014...
  • Page 23: Inspection And Handover Check Sheet

    ThermShield MF(1 & 2) Installation Guide Inspection and handover check sheet This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when installing fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.