INSTALLATION GUIDE
ThermShield Standard Installation Method
Contents
Applies to... .......................................... 1
Health and safety .................................. 1
CE Installation Method Overview ..................... 2
Fire damper installation openings ..................... 3
Rigid wall installation (Fire Batt) ....................... 6
sealing) ................................................................ 8
sealing) .............................................................. 10
ceiling ................................................................. 14
Battery assembly installation 2x2 ................... 15
2x2 ..................................................................... 16
Battery assembly installation 1x2 ................... 17
Periodic maintenance ............................ 20
Actuators ............................................21
Wiring Diagrams .................................. 24
Dimensional Data ................................. 26
(Square/Rectangular)

Applies to...

• Actionair ThermShield FD

Health and safety

• This process must be undertaken by competent per-
sons. More than one person may be required to ensure
the safe handling of large dampers and other materi-
als. Use must be made of access equipment to ensure
unsafe practices are not used to approach walls or diffi-
cult access areas.
• Standard site PPE should be used (minimum steel toe
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as defined by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
• All waste materials should be collected and disposed of
as defined by the relevant supplier.
• Actuators: All wiring should be carried out in accor-
dance with the wiring details provided by the IEE and
BS regulations and by a competent person. Care must
be taken when installing and inspecting dampers, as
they are likely to close without warning due to loss of
electrical power or a temperature rise in the ductwork.
This is their prime function. Do not insert any items,
fingers or limbs between the blades. Larger dampers
must be handled in accordance with current regula-
tions and good practice due to weight.

Advertisement

Table of Contents
loading

Summary of Contents for Swegon Actionair ThermShield FD

  • Page 1: Table Of Contents

    INSTALLATION GUIDE ThermShield Standard Installation Method (Square/Rectangular) Contents Applies to... • Actionair ThermShield FD Applies to..........1 Health and safety ........1 Health and safety CE Installation Method Overview ..... 2 • This process must be undertaken by competent per- Fire damper installation openings .....
  • Page 2: Ce Installation Method Overview

    Fire/Smoke damper. • Under the Fire Damper Product standard BS EN 15650 our Fire Damper products are tested to BS EN 1366-2 and classified under BS EN 13501-3. Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 3: Fire Damper Installation Openings

    (distance from wall limit to the end of fire damper is 125mm). This does not apply for Applique / MF2 kit installations. Check the operation of the fire damper before commencing the installation! 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 4: Rigid Wall Installation (Mortar Sealing)

    30 mm between them. See page 18. * Build the support for installation according to the drawing Test the operation of the damper blade! Ensure that the damper is sufficiently supported! Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 5: Rigid Wall Installation (Mineral Wool Sealing)

    2. Fix the fire damper to the wall with the screws (refer to page 15). 3. Fill the space between casing and wall with mineral wool (3). 4. Cover the wool with gypsum boards (4) (12,5 mm thick). 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 6: Rigid Wall Installation (Fire Batt)

    (5) (density 140 kg/m³ or more, 50 mm thick, coated on one side). Seal the connections of mineral wool with wall and damper with intumescent (6) fire resistant sealant. Mineral wool and damper Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 7: Flexible Wall Installation (Mortar Sealing)

    Ø3,5x45 mm (bracket screw hole is 6 mm in diameter). 3. Fill the space between the damper and the wall with mortar sealing (2). Cover the mortar with (4) gypsum boards (12,5 mm thick). 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 8: Flexible Wall Installation (Mineral Wool Sealing)

    (≥100 kg/m³) (3). Cover the mineral wool with gypsum boards (12,5 mm thick) (4) and fix them with self-tapping screws Ø3,5x45 mm. Minimum seperation between fire dampers, either next Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 9: Flexible Wall Installation (Fire Batt)

    3. Fill the space between casing and wall, close with two layers of mineral wool (5) (density 140 kg/m³ or more, 50 mm thick, coated on one side). 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 10: Rigid Floor/Ceiling Installation (Mortar Sealing)

    2. Fix the damper to the floor/ceiling using screws. 3/3*. Fill the space between the damper and the floor/ ceiling with mortar. (2) Test the operation of the damper blade! Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 11: Rigid Floor/Ceiling Installation (Fire Batt)

    (5) (density 140 kg/m³ or more, 50mm thick, coated on one side). 3/3*. Connections of mineral wool should be sealed with (6) intumescent fire resistant sealant. Mineral wool 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 12: Suspension For Mortarless Floor Installation

    3. Suspend the fire damper to the steel C profiles. Close the space between casing and floor with Firestop board (Firebatt) 2x50mm (≥ 140 kg/m3) and coat the damper casing. Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 13: Suspension For Mortarless Ceiling Installation

    3. Suspend the fire damper to the steel C profiles. Close the space between casing and floor/ceiling with Firestop board (Firebatt) 2x50mm (≥ 140 kg/m3) and coat the damper casing. 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 14: Suspension For Mortarless Installation Close To Ceiling

    2. Insert fire damper into wall to the wall limit mark (7) on the damper and bend the fixing bracket (1) 90°. (screw hole is 6mm in diameter). Fix the C profile on the drop Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 15: Battery Assembly Installation 2X2

    Test the operation of the damper blade! 2. Place two lower dampers in the opening, and fix Ensure that the damper is sufficiently supported! dampers to the wall using screws (only 2 sides facing 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 16: Battery Assembly Installation (Floor/Ceiling) 2X2

    140mm and set all U profiles to a height of 118mm (use blocks of aerated concrete to keep distance between ceiling and profiles). 2. Arrangement of steel C profiles (27x18mm). 3. Place the dampers in the openings to the wall limit Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 17: Battery Assembly Installation 1X2

    3. Attach the installation kit to the dampers using the self- tapping screws every 150mm. 4. Fill the space between the dampers with mineral wool (100 kg/m³ of density). Ensure that the damper is sufficiently supported! 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 18: Minimal Seperation Damper Installation

    (140kg/m³) up to flanges. 3. Fill the rest of the wall openings in accordance with the relevant installation method. *Examples for Firebatt installation Ensure that the damper is sufficiently supported! Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 19 Place the wooden support as close as possible to the fire damper blade! Ensure that the damper is sufficiently supported! 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 20: Periodic Maintenance

    • A comprehensive example of the maintenance procedure is given in Annex D of the standard. Some Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 21: Actuators

    Ambient temperature min. -30 °C, max. 50 °C range 95% r.h., Ambient humidity non-condensing Service life Min. 30,000 cycles Maintenance Maintenance-free (see page 20) Weight R25/R40 0,5 kg / 1,7 kg 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 22 < 120 s Running spring time ~ 20 s ~ 20 s ~ 20 s ~ 20 s ~16 s ~16 s return Ambient temperature min. -30 °C, max. 50 °C range Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 23 Min. 10,000 cycles @ 10 s, min Min. 10,000 cycles @ 10 s, min Service life 1000 cycles @ 1s 1000 cycles @ 1s Maintenance Maintenance-free Maintenance-free Weight 3,5 kg 3,5 kg 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 24: Wiring Diagrams

    (ambient temperature) max. 72 °C Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 25 Thermal fuse is located on the underside of the fire damper. side as Belimo actuator (below). same side as Belimo actuator. Bottom View Side view Side view Electric Actuator Schischek ExMax 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 26: Dimensional Data

    B + 60 B + 30 B + 60 B + 30 Product [mm] [mm] [mm] [mm] FD 25 FD 40 Length of damper blade outside of casing: X=(H/2)-175 [mm] Swegon reserves the right to alter specifications. 20210615 - L00010...
  • Page 27 ThermShield Standard Square/Rectangular Installation Guide Automatic B + 30 B + 60 Actuator [mm] [mm] [mm] [mm] BFL (M) BFN (M) BF (M)* n/2+12 n/2+22 Length of damper blade outside of casing: X=(H/2)-175 [mm] 20210615 - L00010 Swegon reserves the right to alter specifications.
  • Page 28: Inspection And Handover Check Sheet

    ThermShield Standard Square/Rectangular Installation Guide Inspection and handover check sheet This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when installing fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.