INSTALLATION GUIDE
Contents
CE Installation Method Overview ..................... 2
Wall with Pattress ............................................... 3
Wall without Pattress ......................................... 4
Wall against a Floor Slab .................................... 5
Cassette ..............................................6
Actuators ............................................. 7
Periodic maintenance ..............................8
Control Mode Installation Procedure .............................. 8
Mode 5 ......................................................................... 9
Mode 6 ......................................................................... 9
Mode 5 3P ..................................................................... 9
Troubleshooting ....................................13
DWFX-C Installation Method
Drawings
Please visit our website to download the installation
drawings, which are located on the relevant product
download section.
Applies to...
• Actionair SmokeShield PTC
• Actionair FireShield
Health and safety
• This process must be undertaken by competent per-
sons. More than one person may be required to ensure
the safe handling of large dampers and other materi-
als. Use must be made of access equipment to ensure
unsafe practices are not used to approach walls or diffi-
cult access areas.
• Standard site PPE should be used (minimum steel toe
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as defined by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
• All waste materials should be collected and disposed of
as defined by the relevant supplier.
• Actuators: All wiring should be carried out in accor-
dance with the wiring details provided by the IEE and
BS regulations and by a competent person. Care must
be taken when installing and inspecting dampers, as
they are likely to close without warning due to loss of
electrical power or a temperature rise in the ductwork.
This is their prime function. Do not insert any items,
fingers or limbs between the blades. Larger dampers
must be handled in accordance with current regula-
tions and good practice due to weight.

Advertisement

Table of Contents
loading

Summary of Contents for Swegon actionair DWFX-C

  • Page 1: Table Of Contents

    INSTALLATION GUIDE DWFX-C Installation Method Contents Drawings Please visit our website to download the installation CE Installation Method Overview ..... 2 drawings, which are located on the relevant product Vertical Damper Installation in a Plasterboard download section. Wall with Pattress ..........3 Applies to...
  • Page 2: Ce Installation Method Overview

    BS EN 12101-8 and drive open, drive closed without failsafe position, see our website for informa- tion on the Actionair SmokeCommand smoke con- trol damper documentation and suitable installation methods. Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 3: Vertical Damper Installation In A Plasterboard Wall With Pattress

    5. Insulate the wall with mineral/stone wool (if required). 6. Seal the damper to the partition with intumescent sealant and add pattresses to both sides down to the damper spigot, seal to the damper spigot with intu- 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 4: Vertical Damper Installation In A Plasterboard Wall Without Pattress

    6. A minimum of 200 mm between fire dampers installed in separate ducts and 75 mm between fire damper and a construction element (wall/floor). Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 5: Vertical Damper Installation In A Plasterboard Wall Against A Floor Slab

    Fasten the pattresses with drywall screws at 300mm centres on the sides and bottom such that they will allow screws to pull into the stud 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 6: Self Latching Removable Release Mechanism Cassette

    Reset Operation Single hand operation. Each blade pushes the latch back under spring Access tension. On full blade reset the latch springs out to secure. Non Access Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 7: Actuators

    14. The ETR cable must not cut to shorten or lengthen, and care must be taken not to damage it. Either will render the unit inoperable and void any warranties. This is due to a built in safety feature. 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 8: Periodic Maintenance

    • A comprehensive example of the maintenance pro- cedure is given in Annex D of the standard. Some Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 9: Dwfx-C Damper Wiring Diagrams

    (MUST BE FITTED TO DUCTING FOR DAMPER OPERATION) . (Connect 24V via a safety isolating transformer.) (SPRING BIASED TEST SWITCH) IP54 Rated. DIAGRAMS SHOWS ACTUATOR IN FULLY CLOSED STATE 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 10: Dwfx-C Damper Dimensional Data

    FOR DUCT WITH WIDTHS AND HEIGHTS OF 200 - 1000MM Flat O l Dampers Series 701                    Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 11 5mm under duct size) 100 - 249 high, use Series 101 Damper as OVERALL WIDTH OF INSTALLATION FRAME IS DUCT Series 301 WIDTH + 114 spigots 3mm under duct size) OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH + 114 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 12 Actionair DWFX-C Installation Guide Cleat dimensions SmokeShield PTC      FireShield Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
  • Page 13: Troubleshooting

    Foreign matter is Check and remove impeding blade movement Motor location Fit new pointer pointer omitted Mode not screwed Check and tighten down correctly 20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.
  • Page 14: Inspection And Handover Check Sheet

    Inspection and handover check sheet This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when instal- ling fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.