INSTALLATION GUIDE
Contents
Walls ...................................................3
Concrete Slab ........................................4
5
Vertical Damper in a Masonry Wall against
slab ....................................................6
Cassette .............................................. 7
Actuators .............................................8
Periodic maintenance ..............................9
Control Mode Installation Procedure .............................. 9
Wiring Diagrams .......................................................... 10
Actionair SmokeShield PTC ...........................................11
Actionair FireShield ...................................................... 13
Troubleshooting ....................................14
DWFX-F Installation Method
Drawings
Please visit our website to download the installation dra-
wings, which are located on the relevant product down-
load section.
Applies to...
• Actionair SmokeShield PTC
• Actionair FireShield
Health and safety
• This process must be undertaken by competent per-
• Standard site PPE should be used (minimum steel toe
• All waste materials should be collected and disposed of
• Actuators: All wiring should be carried out in accor-
sons. More than one person may be required to ensure
the safe handling of large dampers and other materi-
als. Use must be made of access equipment to ensure
unsafe practices are not used to approach walls or diffi-
cult access areas.
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as defined by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
as defined by the relevant supplier.
dance with the wiring details provided by the IEE and
BS regulations and by a competent person. Care must
be taken when installing and inspecting dampers, as
they are likely to close without warning due to loss of
electrical power or a temperature rise in the ductwork.
This is their prime function. Do not insert any items,
fingers or limbs between the blades. Larger dampers
must be handled in accordance with current regula-
tions and good practice due to weight.

Advertisement

Table of Contents
loading

Summary of Contents for Swegon actionair DWFX-F

  • Page 1: Table Of Contents

    INSTALLATION GUIDE DWFX-F Installation Method Contents Drawings CE Installation Method Overview ....2 Please visit our website to download the installation dra- wings, which are located on the relevant product down- Vertical Damper Installation in Plasterboard load section. Walls ...........3 Vertical Damper Installation (Top Flange Applies to...
  • Page 2: Ce Installation Method Overview

    BS EN 12101-8 and drive open, drive closed without failsafe position, see our website for informa- tion on the Actionair SmokeCommand smoke con- trol damper documentation and suitable installation methods. Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 3: Vertical Damper Installation In Plasterboard Walls

    9. Install the damper and fasten. 10. Back fill and complete penetration seal as per the 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 4: Vertical Damper Installation (Top Flange Removed) In A Plasterboard Wall Under Concrete Slab

    7. Frame out the hole sides and bottom with stud and track and cover this with board. Finish edges with joint filler. 8. Drill clearance holes in the three damper flange sides at Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 5: Vertical Damper Installation In Masonry Walls

    A minimum of 200 mm between fire dam- pers installed in separate ducts and 75 mm between fire damper and a construction element (wall/floor). 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 6: Slab

    7. Dampers are supplied with cleats and only need to be used to help/assist with the installation before faste- ning the flange to the wall. 8. Back fill with mineral/stone wool and to retain this use Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 7: Self Latching Removable Release Mechanism Cassette

    Reset Operation Single hand operation. Each blade pushes the latch back under spring Access tension. On full blade reset the latch springs out to secure. Non Access 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 8: Actuators

    14. The ETR cable must not cut to shorten or lengthen, and care must be taken not to damage it. Either will render the unit inoperable and void any warranties. This is due to a built in safety feature. Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 9: Periodic Maintenance

    • A comprehensive example of the maintenance pro- cedure is given in Annex D of the standard. Some 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 10: Wiring Diagrams

    (MUST BE FITTED TO DUCTING FOR DAMPER OPERATION) . (Connect 24V via a safety isolating transformer.) (SPRING BIASED TEST SWITCH) IP54 Rated. DIAGRAMS SHOWS ACTUATOR IN FULLY CLOSED STATE Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 11: Dwfx-F Damper Dimensional Data

    OVERALL FLANGE HEIGHT = DUCT DIA + 245mm             FOR DUCT WIDTHS BETWEEN 970mm - 1000mm OVERALL WIDTH OF INSTALLATION FRAME IS 1198mm 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 12 For Ducts with widths and heights of 200 - 1000mm OVERALL FLANGE WIDTH DUCT WIDTH + 198mm OVERALL FLANGE HEIGHT DUCT HEIGHT + 195mm           Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 13: Actionair Fireshield

    Series 201 spigots 5mm under duct size) 100 – 249 high, use Series 101 Damper as Series 301 spigots 3mm under duct size) Series 401 spigots 3mm under duct size) 20220503 - LNNN00354 (4.0) Swegon reserves the right to alter specifications.
  • Page 14: Troubleshooting

    Foreign matter is Check and remove impeding blade movement Motor location Fit new pointer pointer omitted Mode not screwed Check and tighten down correctly Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
  • Page 15: Inspection And Handover Check Sheet

    Inspection and handover check sheet This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when instal- ling fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.