Spark Igniter Set Up - Schwank STS-JZ Installation & Owner's Manual

Low intensity tube type infra red heaters
Table of Contents

Advertisement

SPARK IGNITER SET UP

Use the following diagram to check the Igniter gap. If the gap is incorrect all adjustments
should be made to the GROUND PRONG/PIN ONLY! DO NOT BEND THE IGNITER
PRONG!!!!
USE THE BLACK BARS BELOW AS A GUIDE FOR AD-
JUSTMENT.
USE THE BARS THAT COINCIDE WITH
THE FORMAT & SIZE OF THIS PUBLICATION .
IF
this manual is in
"booklet" format
8.5" x 11"
(pages folded in half)
then use these bars
OR
IF this manual is printed
8.5" x 11" "full page" format
use these bars
SERVICE CHECKS
Flame current passes through the flame from
the sensor to ground. The minimum flame cur-
rent necessary to keep the system from lock-
out is 0.7 microamps. To measure flame cur-
rent, connect an analog DC microammeter to
the FC- FC+ terminals per figure at right.
Meter should read 0.7 µA or higher. If the me-
ter reads below "0" on scale, meter leads are
reversed. Disconnect power and reconnect
meter leads for proper polarity.
3/16"
1/4"
3/16"
1/4"
Multipurpose Meter
45
ADJUST
Use Microamp
scale
STS-JZ-F / IQ-F I&O Manual Z83.20-2016
IM101220
RD: APR 2019
RL: 20C