10 Installation Instruction

10.1. Select The Best Location

INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 7.5 m, additional refrigerant should be
added as shown in the table.
Piping size
Length
Model
Gas
Liquid
PC30EK
5/8"
3/8"
PC36EK
3/4"
3/8"
Example: For PC36EK
If the unit is installed at a 10m distance, the quantity of
additional refrigerant should 75 g ...... (10 - 7.5) m x 40 g/m =
100 g
Rated
Max.
Max.
Elevation
Piping
(m)
(m)
Length
(m)
5
20
30
5
20
30
10.2. Indoor/Outdoor Unit
Installation Diagram
Additional
Refrigerant
(g/m)
30
40
22